Kitchen Suppression Systems and Clogged Detection Lines

  Рет қаралды 70,196

Commercial Fire

Commercial Fire

9 жыл бұрын

Have you ever wondered what the kitchen suppression system does and how it works? Checkout the following video of a trained and licensed suppression manager explain one of the most common suppression deficiencies, a clogged detection line.

Пікірлер: 49
@andrewbandarovich1751
@andrewbandarovich1751 5 жыл бұрын
Great video. Unfortunately a lot of service companies just replace links and never cut test anything. Even worse, some just replace their tags to the ones with new dates and go.
@williamday3521
@williamday3521 4 жыл бұрын
I am about to disassemble an ansul fire suppression system. I found this video to be super helpful in understanding how this system works. thank you
@ricky11va
@ricky11va 7 жыл бұрын
Great educational video !
@ooommm4024
@ooommm4024 2 жыл бұрын
learning about all that engineering is fascinating. i always wondered how those fire suppression emergency systems worked?
@tomf7170
@tomf7170 Жыл бұрын
Why isn't there a fusible link in the duct?
@jukebox40000
@jukebox40000 2 жыл бұрын
🔥🔥🔥🔥
@rynesherman9099
@rynesherman9099 3 жыл бұрын
Thats why you should probably test end of line first. I mean that's what the book from ansul says to do.
@cannabros
@cannabros Жыл бұрын
he did test the end of line its called the terminal sensor
@daviddoherty1257
@daviddoherty1257 5 жыл бұрын
Didn’t use locking bar before screwing out cartridge
@joshuaborem7063
@joshuaborem7063 3 жыл бұрын
Lock bars are for scaredy cats who don’t trip systems. Me and my team don’t ever use lockout bars.
@haydeevalentin4670
@haydeevalentin4670 6 жыл бұрын
Hi , Please you repeat procedure spanish . The excelent explain . I need all visual complete prosedure , the all
@franciscoesterripa7912
@franciscoesterripa7912 Жыл бұрын
What certification you need to inspect systems like that
@tahernabieh6096
@tahernabieh6096 2 ай бұрын
WHERE IS THE CONNECTION WITH FIRE ALARM PANEL?
@josebermudez8364
@josebermudez8364 6 жыл бұрын
No protection on the opening.. a link must be install above every equipment and duct opening.. .
@Troacoli
@Troacoli 4 жыл бұрын
I think this is a training/demo system. But yes.
@stanlleypajdak8547
@stanlleypajdak8547 5 жыл бұрын
How do you reset the system
@Sophsfghds
@Sophsfghds 3 жыл бұрын
You need a Ansul tension resetting tool to reset the automatic & manual actuation pulley wire lines
@tonyhernandez3873
@tonyhernandez3873 Жыл бұрын
Why you say connect your appliances on ceriesl I guess it's on parallel to the contractors
@user-xh3zr8fh4k
@user-xh3zr8fh4k 4 жыл бұрын
you didn't say anything about the alarm?
@farrukhmahmood4099
@farrukhmahmood4099 3 жыл бұрын
Hello sir how are you. Sir my system is ansul pirhana. My problem is how to fix manual release and fuse ablelinks rope fixing in mechanical realease medole how to fix fuseable link cable???
@farrukhmahmood4099
@farrukhmahmood4099 3 жыл бұрын
Please reply me very soon
@justinlee4022
@justinlee4022 3 жыл бұрын
Yes if you still need help . Let me know as well
@joshuaborem7063
@joshuaborem7063 3 жыл бұрын
Your question is too vague to answer. “How to fix” isn’t specific enough.
@nrtxdragon1703
@nrtxdragon1703 3 жыл бұрын
get a trained Ansul engineer to do it? there the only one that should be touching a system
@khalidkhalid-dn2pt
@khalidkhalid-dn2pt 3 жыл бұрын
Where Is duct Link
@enjazalawsat1176
@enjazalawsat1176 Жыл бұрын
Hi sir how are you
@farrukhmahmood4099
@farrukhmahmood4099 3 жыл бұрын
Assalamualkum
@ThomasShue
@ThomasShue 4 жыл бұрын
You could use a zip tie for a test link.
@joshuaborem7063
@joshuaborem7063 3 жыл бұрын
Why would you do that? Just use a test link or a real link.
@nationalfireprotectioninc.843
@nationalfireprotectioninc.843 4 жыл бұрын
he is using wrong detection bracket . those detector bracket are for Range guard. you must use Ansul system detector or Ansul will not responsible for that.
@joshuaborem7063
@joshuaborem7063 3 жыл бұрын
I agree that you’re correct but it’s a useless fact. The bracket being the wrong brand will not affect system operation.
@nrtxdragon1703
@nrtxdragon1703 3 жыл бұрын
these detector are used all across the uk with no issues Ansul them self have no issues with these detectors
@suppression7630
@suppression7630 4 жыл бұрын
You are using wrong detector. Those detector are not for Ansul system
@nrtxdragon1703
@nrtxdragon1703 3 жыл бұрын
I'm a trained Ansul engineer in the uk this detector are correct. usless the only ones you have see are the old horse shoe ones that are now out dated and need to be replaced
@safety_news
@safety_news Жыл бұрын
I am Robert.Tamilnadu safety council. Secretary. Helping hearts foundation trust. Secretary. Safety Reach World.CEO. Iyarkai Foundation.NGO. Human Rights International Federation. Tirupur South president. Tirupur emergency response team. founder 💝👩‍🚒🙏
@pepperwilliams4428
@pepperwilliams4428 6 жыл бұрын
This guy did a great video, but probably need to exercise more. He sure was breathing heavily throughout.
@danbardales6734
@danbardales6734 6 жыл бұрын
Pepper Williams you might have a fitness body...
@wa6lie
@wa6lie 5 жыл бұрын
Hmmm... that detection line did not get that way in 6 months. The service company is NOT doing their job right. What happened to the REQUIRED detector in the exhaust duct just left of the end of line detector? In addition, the scissor links are NOT suppose to be positioned up in the bracket as shown. They are supposed to hang down freely. This also helps prevent additional drag on the cable for proper operation. To keep the scissor from falling off the cable, using a weight like vise grips to weight the cable without actually gripping the cable on the end of line detector, allowing it to move freely. This way, there is always some tension on the scissors so they don't fall apart while installing the other fusible links on the detection line. Every service, 6 months or more frequently, depending upon kitchen operation whereas grease build up is greater than normal. This may include restaurants open 24 hours with char broilers or Chinese Woks for example. Somebody needs to go back to ANSUL school. I have been installing and servicing "ANSUL" type of restaurant systems since 1982 and in this video the service company providing the service is doing a dis-service to our professional service technicians. Go to the fire system manufactures training school to know how to do it right, or not all.
@stephencarroll6590
@stephencarroll6590 5 жыл бұрын
"Install the linkage and the correct ANSUL approved fusible link in the remainder of the detector brackets. Make certain all detector linkages are positioned against either the front or back upper lip of the formed detector bracket." That is directly from the ANSUL manual. Might I suggest you follow your own advice and go back to ANSUL school?
@justinlee4022
@justinlee4022 3 жыл бұрын
Boom! Yes Stephen is correct! They do belong inside the detector housing just not straight up. Either front or back has a lip indent that the detector belongs in to prevent slag, the link detector is not suppose to be outside just hanging as the weight, vibration , and or cable can be running against something and could accidentally be cut/frayed overtime or damaged and you could have a accidental discharge. However , the rest of your information is correct. I have been testing,installing and selling Ansul systems for 10 years. Also was the department manager and sales person for service and contracting sales for the largest company in Arizona. Almost a million in Kitchen suppression system sales alone in a fiscal year .
@joshuaborem7063
@joshuaborem7063 3 жыл бұрын
You criticize them without any specifics except the scissors hanging down (of which you’re incorrect- because the Ansul book requires them to be tucked upward into the brackets )
@frankfarkle2924
@frankfarkle2924 6 жыл бұрын
the scissor isn't even crimped to stay on the line. Poor guy is going to sweat all day looking for the scissor that falls after testing.
@darrelldawson4823
@darrelldawson4823 5 жыл бұрын
I've seen "crimped" scissors cause cable fraying on the detection line, that's a terrible reccomendation. A technician should not spend time searching for the missing scissor either. After a system discharge due to a fire, the scissor containing the fusible link that separated should be replace as well as any other scissors exposed to extreme temperatures. ALL links should then be replaced.
@joshuaborem7063
@joshuaborem7063 3 жыл бұрын
Don’t crimp the scissors! My team has had 20 system dumps per year and no issue with finding the scissor. Besides that, if the scissor is missing then you just install a new one.
@ThomasShue
@ThomasShue 4 жыл бұрын
Good job reading a paper. Just be real and talk to us brother.
The basics of a kitchen fire suppression system
5:59
Defense Fire Protection Inc.
Рет қаралды 2,4 М.
Kitchen Inspection
3:40
Silco Fire & Security
Рет қаралды 7 М.
How Many Balloons Does It Take To Fly?
00:18
MrBeast
Рет қаралды 199 МЛН
Red❤️+Green💚=
00:38
ISSEI / いっせい
Рет қаралды 86 МЛН
A little girl was shy at her first ballet lesson #shorts
00:35
Fabiosa Animated
Рет қаралды 15 МЛН
World’s Largest Jello Pool
01:00
Mark Rober
Рет қаралды 99 МЛН
PRI-SAFETY Kitchen Fire Suppression System Installation Instruction
10:58
Buckeye system reset
5:21
jason360ize
Рет қаралды 16 М.
Jerry’s Corner (Hood & Duct Services)
12:24
Victory Hood Cleaning Commercial
Рет қаралды 130 М.
Maintaining Your Restaurant Fire Suppression System (English)
9:41
Western Fire Prevention
Рет қаралды 130 М.
Ansul system
11:44
jarisisimo4you
Рет қаралды 10 М.
FireDETEC Fire Suppression System for Commercial Kitchens
4:12
Rotarex Firetec
Рет қаралды 43 М.
Ansul Instructional Video for freddy
10:05
Michael Bushatz
Рет қаралды 12 М.
How Many Balloons Does It Take To Fly?
00:18
MrBeast
Рет қаралды 199 МЛН