Great video and on point. During my time in electrical industrial maintenance the most common PLC module we would find failed were both SLC relay output cards as well as Compactlogix. The relay outputs would typically be failed in the closed position especially on power open, power closed valves. Something to keep in mind is that 120V Triac outputs commonly leak current in the off state and can mimic almost full line voltage to a voltmeter with the output in the off state without a load attached.
@KletteTech Жыл бұрын
Well said! And Great advice. Thank you commenting and sharing your knowledge.
@Simple_But_Expensive5 ай бұрын
@@tektonelec4695 It is not just SLC and Compactlogix that suffer this. I was working with PLCs my entire career (earliest was a Goulds), and I never found any relay output cards that didn’t suffer this problem. I trained all my guys to always leave spare points when designing PLCs, so you could move a wire and get back to running right away (power plants only willingly shut down during scheduled maintenance outages), and to always use an interposing relay with a flyback diode to mitigate this problem. We used this method even with a 24 volt card powering a 24 volt circuit. It took up more real estate and cost more, but it greatly reduced the failure rate. We weren’t a professional PLC company, we were custom designing PLC control systems for the combined cycle power plant we worked at, so there was nobody to tell us it cost too much. Given the cost to our customer for down time, estimated at $250k/hour, we were able to show that doing it this way raised our run time from 95% to 97% in one year, netting out customer several million in increased profits, and us a nice increase in contract revenue. Of course myself and my techs only got a slight one time increase in our incentive bonus, but we expected that. The true value to us was pride in our work.
@EthanMiller-h6g22 күн бұрын
This video makes troubleshooting PLC outputs so clear! If you ever need hands-on electrical troubleshooting, Johnson Electric and Controls in California is the team to call. They’ve helped me out of more than one tricky situation. Highly recommend!
@jluke68612 күн бұрын
Thank you for the Great Video.
@bicoolelectricaladventurist7 күн бұрын
Very clear and informative. Thank you
@renzonieves41568 ай бұрын
Thank you so much; A very clear and slow explanation. Easy to understand, step by step.
@tjwiltube Жыл бұрын
Nice job, Pat!
@KletteTech Жыл бұрын
Thanks T-Dog.
@muscleman47992 ай бұрын
Really good plc troubleshoot thank you for your time man
@LidzDJ98645 ай бұрын
Is the pls short circuit protection on on the output side?
@maintenancetoronto10954 күн бұрын
5:44, The NO in the diagram should be connected between DC1.VAC and OUT1.
@naimhasan28778 ай бұрын
Very good explanation. I like it. Thank you so much for your informative tutorial.
@theelectricianguy8 ай бұрын
Good job sir, exactly how I would have done it. I’ve actually ran into this out in the field several times, had 2 output cards with bad relay terminals not putting out voltage. You don’t see it much but I always like to add circuit breakers on my outputs when I build and wire control panels, a lot of times the output in the field could possibly take out the output it’s attached to. Good video!
@Randylongoria814 ай бұрын
Could you check for another output on the plc? And how would you program that?
@alexzhitomirets5864 Жыл бұрын
Is it common to wire 120V load through the PLC outputs or better to wire a low voltage relay first? Let's say I have an air solenoid valve (120V).
@scoutsx_d4441 Жыл бұрын
solenoid valves are inductive loads which will generate back emf. Typically the solenoids come with built in diode protection, but it is always good to put an interposing relay to separate the output from the load. Cheap solution and much safer.
@alexzhitomirets5864 Жыл бұрын
Thanks, that's what I was thinking.
@KletteTech Жыл бұрын
Agreed. For simple pilot lights and other low current devices you can wire through the PLC
@deeperloveforphysics95137 ай бұрын
This is one of my best videos. Thank you so much. Please, help and make more videos on plc troubleshooting. If you've link to other topics on plc troubleshooting please , share with me. Thank you again.
@KletteTech4 ай бұрын
Glad it helped!
@jkim55955 ай бұрын
I think the internal relay contact on the wiring diagram should be shown between DC1 and Out1 to check yellow light.
@maintenancetoronto10954 күн бұрын
I have the same comment as well.
@gechoemiru99318 ай бұрын
Is it possible to attach the manual to see it clearly. It will be more clear for me if I can see the wiring diagram.
@emiliohuerta26589 ай бұрын
thank you so much im between a tech 2 and tech 3 at my profession and had a little hard time understanding this. Now if i may adk a question so in this case if i dont have a laptop available, how do i force the button to stay on while i check?
@KletteTech9 ай бұрын
I do not believe you can. You would have to know the logic that is in the program and activate the inputs
@ramya225527 күн бұрын
In what/which software are you running/using the plc programming ?
@KletteTech26 күн бұрын
RSLogix 500
@deeperloveforphysics95137 ай бұрын
I had 6 outputs from a plc, these are nozzles that were opening accordingly as programmed. However, after some times the began to operate inappropriately. Instead of opening and closing sequencially as programmed, they began to open and close in a wild manner, what could be the cause, any idea on what i should do?
@brianfirth5435Ай бұрын
If the PLC code has not been changed, then most likely you have a PLC input with a loose termination or a faulty input device.
@jordanneville71123 ай бұрын
Great video, How often do you see a PLC go bad particularly the relay type Mitsubishi plcs ?
@KletteTech3 ай бұрын
Depends on how much current is flowing through it
@lifevideo76284 ай бұрын
Thanks, I got a new and easy system to find out trouble
@KletteTech4 ай бұрын
Glad I could help
@ShujahHaider-b6y8 ай бұрын
So Super informative video thanks for nice shearing sir 🇵🇰💖
@juliogomez86363 ай бұрын
Hello what kind the Plc Do you have
@gechoemiru99318 ай бұрын
That is great. Thank you
@thumbsup92085 ай бұрын
What about if you do not have access to the PLC to put force on the terminal, how can continue the troubleshooting./
@enstad72585 ай бұрын
Then you need to activate the inputs that activate the output you are troubleshooting
@Simple_But_Expensive7 ай бұрын
What if it was wired with wetted voltage? If the output is sinking, the power goes to the bulb, and then to the output contact.
@vishnunath52029 ай бұрын
Great video. 👍
@KletteTech9 ай бұрын
Thanks 👍
@street2827 ай бұрын
Thanks 👍🏻
@mw3blackopsglitches11 ай бұрын
Great video!!
@KletteTech11 ай бұрын
Thanks!
@BurRun-kt3tf2 ай бұрын
Thank អរគុណ👏
@makiseCpenebas4 ай бұрын
what happen when u wrong insert power terminal on 1743-aent allen bradley mean u swap the +/- position
@k501599 ай бұрын
Thank you so much
@KletteTech9 ай бұрын
You Welcome
@wmdavis91014 ай бұрын
I'm confused on how exactly how the PLC output is bad. If your able to activate on the software wouldn't that imply it's still good. In other words how is the software able to activate the output if it's broken?
@Cesar-kc5un4 ай бұрын
No the plc true is just showing how it should be turned on .
@wmdavis91014 ай бұрын
@@Cesar-kc5un At 6:40 he forces output zero "on", then takes measure and it is producing 120V. How is the program able to force it on while the button is unable to?
@SolaniSibanyoni4 ай бұрын
Just like your phone.. You can switch the torch on and not get any light... The plc software can be 100% but the hardware maybe faulty
@donnellbaxter80505 ай бұрын
Thanks sir make more videos.
@KletteTech4 ай бұрын
Will do
@garrettsmith66799 ай бұрын
So you activated the output manually and it’s not coming on so you know it’s not the trigger signal or input to activate that output. But which input is suppose to active that output?
@KletteTech9 ай бұрын
That is determined by the logic that is programmed into RSLogix 500
@garrettsmith66799 ай бұрын
@@KletteTech so the plc receives data from whatever that light is referencing to? Also how do the inputs work, do they correlate directly with a certain output or do you program any input to whatever output you want? Thanks for the responses
@daveb93708 ай бұрын
@@garrettsmith6679you can program any input to any output. Another quick test is to use a jumper wire from the correct voltage source, in this case 120 vac, from the input to the output terminal, and if the device works, you know the output is bad.
@garrettsmith66798 ай бұрын
@@daveb9370right!!
@garrettsmith66798 ай бұрын
@@daveb9370 right!!
@ryanpate62157 ай бұрын
Report back to the bosses lol that had me laughing my ass off! Just move the output to another open spot or just add another 120v output card. PLCs lose Inputs and output all the time. Don't make a bigger problem than it really needs to be. If you know the bulb is good, go straight to the output and check it there.
@Adam-tl6jo3 ай бұрын
How common is a PLC replacement due to this specific fault do you see in the field?
@KletteTech2 ай бұрын
Totally depends on where you work. Most places if you can move the output to an available output you can.
@KNX-Expert-ilyass Жыл бұрын
Thanks for this vidio
@KletteTech Жыл бұрын
Most welcome
@israel35382 ай бұрын
Lmao your watch is repeating everything you say
@KletteTech2 ай бұрын
She is always listening
@kumarsaurabh3936Ай бұрын
Fluke multimeter 😅it's so costly.
@Finally_learning_pakods7 күн бұрын
They used to be worth it but now quality has gone down.
@chadtaylor61358 күн бұрын
“Most of the time the color code CAN be trusted”. LIES!!! 😅