MCQUAY SELF CONTAINED UNIT WITH AN ALARM FOR THE INLET GUIDE VANES AND HIGH STATIC

  Рет қаралды 1,924

Jason Johnson

Jason Johnson

3 ай бұрын

Пікірлер: 30
@Eddy63
@Eddy63 3 ай бұрын
Nice troubleshooting and nice vid JJ ... Thx
@jasonjohnsonHVAC
@jasonjohnsonHVAC 3 ай бұрын
Thank you sir.
@mechanicalenvironments
@mechanicalenvironments 3 ай бұрын
Nice video, gotta love when every wire is the same color...
@jasonjohnsonHVAC
@jasonjohnsonHVAC 3 ай бұрын
It wouldn't have been so bad if there was a wiring diagram to follow....its all good though...figured it out...we are gonna lick the vanes open and put a VFD in. Should run even better. These are 25 year old units
@OnyxtheFolf
@OnyxtheFolf 3 ай бұрын
I dont know why I was recommended this and have absolutely no idea what it is but it's intriguing and I'd love someone to explain it lol
@jasonjohnsonHVAC
@jasonjohnsonHVAC 3 ай бұрын
Its an old school way to modulate airflow in a duct system. Its using different sensors to use to calculate how much the vanes should be opened or closed to maintain a certain pressure in the duct system. It is doing this due to other smaller boxes that create a zoning of airflow throughout office buildings. Hopefully that'll answer your question a bit.
@petersmart1999
@petersmart1999 3 ай бұрын
I have run into sticky floors,they had VCT glue all over it.I asked the guy how are you supposed to walk on it,he said we wear golf shoes,with metal spikes!
@dimaslespier2688
@dimaslespier2688 27 күн бұрын
Typically we recommend vfd with an air pressure transducer about 2/3 down the duct or before the first supply air register 😊
@jasonjohnsonHVAC
@jasonjohnsonHVAC 27 күн бұрын
That is what was recommended....unfortunately the salesman is still dragging his feet on sending the quote....doesn't matter though...I don't work for that company any longer.
@subcoolHVAC
@subcoolHVAC 3 ай бұрын
Great video Jason, we had a few units with those guide vanes. You might be able to swap out the board relay with the unused ACT3 relay.
@jasonjohnsonHVAC
@jasonjohnsonHVAC 3 ай бұрын
The relay tested good, and the board was not spitting out the 12vdc to engage the coil on the relay. It's a 25 year old unit. We are gonna pin the vanes open, add a VFD to it. The chief engineer was all on board with it. He likes VFD'S. I called around, and the board has been discontinued for 8 years now. Lol. Thanks for watching and the comment buddy
@subcoolHVAC
@subcoolHVAC 3 ай бұрын
@@jasonjohnsonHVAC I figured it would be hard to get. VFD is perfect 👍. Keep em coming!!
@NROhvac
@NROhvac 2 ай бұрын
Very good
@jasonjohnsonHVAC
@jasonjohnsonHVAC 2 ай бұрын
🤘🤘
@GlenS123
@GlenS123 2 ай бұрын
Worked on hundreds of V.A.V. systems, converted tons to freq. drives. Never seen any system start with Vanes open, but maybe because it can't close them is why its doing that. System might prove they work by driving open then closed before starting.
@jasonjohnsonHVAC
@jasonjohnsonHVAC 2 ай бұрын
The vanes are supposed to be closed on start up. The board isn't outputting 12vdc to the relay coil. I could've closed it, started it up...but the next time it started up...would've been back in alarm
@dimaslespier2688
@dimaslespier2688 27 күн бұрын
Where is the board input to drive that motor? Is it air pressure switch or an analog signal to tell the board to modulate in either direction based on? Static pressure or the amount of vav that are closed? Are those older vav’s just open/close or maintain a specific min/max air set point if so? Based on what? From what I remember about those penn control thermostat they were just open/closed and bypass through the box into the plenum increasing the static to the minimum pressure to keep the unit from freezing up and the discharge air in the plenum with throttle the compressor down on temp? And the air switch would drive the vanes to a minimum and the only time those vanes were completely closed is on unit shut down completely. Again I haven’t worked on an inlet guide vane unit since 1990 so forgive me if I’m off
@petersmart1999
@petersmart1999 3 ай бұрын
Used to love the old Trane units(paper svhematics lasted as long as the warranty),follow the black wire #13,or is it #18, dadedadeda,ok and what,how the f-ck did I end up on # 32,repeat process!
@jasonjohnsonHVAC
@jasonjohnsonHVAC 3 ай бұрын
No kidding. This wasn't too bad. It was a fun little troubleshoot. Thanks for the comment my friend
@TheChillerGuys
@TheChillerGuys 3 ай бұрын
I worked for the factory and i have never seen anything like this, this is neat as hell! are those factory installed IGV's or aftermarket?
@jasonjohnsonHVAC
@jasonjohnsonHVAC 3 ай бұрын
Those are factory installed. Not many of them are still out there floating around. I was impressed that the Belimo actuator still worked. It was original to the unit. This unit is from 1999. Thanks for the comment
@TheChillerGuys
@TheChillerGuys 3 ай бұрын
​@@jasonjohnsonHVAC Thats awesome, I love when old stuff just works. I had a data center with 44 joy fans with pneumatic hubs that were still fully operational, and worked perfectly. The maintenance guy loved the building and he was there from the beginning and kept everything maintained and had a fresh coat of paint on everything when it needed it. that place was from 96 and everything looked brand new like it was just installed. For sure man, Tom sent me your way. good stuff brother, keep it up!
@tomn4838
@tomn4838 3 ай бұрын
Old school IGV.
@jasonjohnsonHVAC
@jasonjohnsonHVAC 3 ай бұрын
Yes, sir. Dont get to see too many anymore that haven't been converted....which is what we are gonna quote. This one is 25 years old. Thanks for watching
@fshn76
@fshn76 3 ай бұрын
What is 5 minute delay Alex
@jasonjohnsonHVAC
@jasonjohnsonHVAC 3 ай бұрын
The longest 5 minutes in HVAC.....waiting for something to start.
@subcoolHVAC
@subcoolHVAC 3 ай бұрын
😂
@dimaslespier2688
@dimaslespier2688 27 күн бұрын
Are those bypass boxes or in series?
@HEFTYLEFTY303
@HEFTYLEFTY303 3 ай бұрын
I think those relays on the board are replaceable
@jasonjohnsonHVAC
@jasonjohnsonHVAC 3 ай бұрын
They are, problem was that the 12VDC for the coil to switch the contacts. I pulled and tested the coil pins on the board. Never had 12v.
Самое Романтичное Видео ❤️
00:16
Глеб Рандалайнен
Рет қаралды 3,5 МЛН
路飞被小孩吓到了#海贼王#路飞
00:41
路飞与唐舞桐
Рет қаралды 29 МЛН
Hydroelectric Power Station
3:35
Oso
Рет қаралды 787
Watchmaking: Machining the Heart of a Watch
38:01
Chronova Engineering
Рет қаралды 661 М.
Little tour of the plant I was in this morning. Has a big AHU.
2:58
Variable Frequency Drives Explained - VFD Basics IGBT inverter
15:18
The Engineering Mindset
Рет қаралды 3,1 МЛН
Making a Crazy Part on the Lathe - Manual Machining
4:15
my mechanics insights
Рет қаралды 16 МЛН
Самое Романтичное Видео ❤️
00:16
Глеб Рандалайнен
Рет қаралды 3,5 МЛН