Really digging the videos! The oddball issues / more advanced level troubleshooting stuff is killer. Please keep it up!
@jezhz82 жыл бұрын
Thanks for the video. I recently came across this issue. The first thing I noticed as I was walking behind the condensers is that I could audibly hear something bypassing. Upon taking the covers off, I felt that the slave unit wasn't working as hard (in cooling) as the master was. Upon feeling the pipes in and out of the LHS 4 way valve on the slave, I noticed it wasn't working as intended. This video further solidified my diagnosis.
@dennisrodriguez26052 жыл бұрын
hey Vrf Madness thank you for posting . please ... post more videos from Mitsubishi equipment ..your videos are very educated. thanks man
@LC-qi5ff2 жыл бұрын
Thank you. Was it a problem with the 4 way valve?
@zebeddie012 жыл бұрын
Great diagnosis! Great to watch and always learn more. Thanks for sharing.
@naveedofficialchannel11 ай бұрын
So the action we take are pulling out the refrigerant from gas pipe that compressore become dry?
@hvacshinobi8047 Жыл бұрын
Great video. By any chance dose a PUMMY city multi have a recovery mode? I am having trouble pulling a vacuum just want to make sur my LEV is open at they air handler, thanks.
@Jc211599 ай бұрын
Hey Madness! I have a question. I just got a building with 250 FC’s and about 30 OC. I have the EA200 centralized controller. I’m getting a 1500 error code. Th15. Any pro Tip of how identify which OC is the unit with the alarm? Note- 30 OC on the Roof.
@michaelmiller55668 ай бұрын
Address on outdoor unit is set via a round dial inside the electrical panel. So address 51 will be 5 and 1 on the 2 dials
@Jc211598 ай бұрын
@@michaelmiller5566 thx 🙏 man
@naveedofficialchannel11 ай бұрын
Or try to operate the another unit?
@pualruiz Жыл бұрын
Have you ever seen a 1501 error code?
@naveedofficialchannel11 ай бұрын
Or turn off both twin unit for letting reach balance condition refrigerant?
@VrfMadness11 ай бұрын
If the accumulator is full its just going to sit there especially on a cold day.
@naveedofficialchannel11 ай бұрын
@@VrfMadness unfortunately its not happen on a cold day sir.
@naveedofficialchannel11 ай бұрын
@@VrfMadness we suck out liquid refrigerant from supply line. But still, compressor is wet and cool.
@Cannon-t6r6 күн бұрын
Could you do this without the service checker? Good video
@hkhvac2702 жыл бұрын
Thank you for sharing good luck
@NataliaBryan-p4b13 күн бұрын
I live in an apartment building and I’m getting this code. It works fine for hours then errors out. But aircon Gus say nothing wrong because when they come it’s running fine. Any advice please? Help please
@VrfMadness12 күн бұрын
@@NataliaBryan-p4b send them my video! They probably need to pull a little refrigerant out. There could be other issues but that's the most likely. They should be hooking up a laptop to diagnose. If they aren't, they are not Troubleshooting properly and likely don't know what they are doing.
@LC-qi5ff2 жыл бұрын
Which solenoid was stuck open/closed? Or was it the 4 way valve?
@VrfMadness2 жыл бұрын
It was one of the 4 ways.
@pablochinchilla4372 Жыл бұрын
A and b for heating, c for cooling
@VrfMadness Жыл бұрын
@@pablochinchilla4372 in the BC? no. Sva and svc for cooling. Svb is heating.
@rickysambilay65202 жыл бұрын
thank you for sharing, pls more video about Mitsubishi VRF,, piping wiring combination outdoor
@livingthedream154 Жыл бұрын
Do you work on water source mitsubishi?
@VrfMadness Жыл бұрын
Yes, I do
@chrisracer20079 ай бұрын
You like working on Mitsubishi or find it troublesome?
@VrfMadness9 ай бұрын
I love it! It's built with quality and attention to detail. Unlike a lot of other brands.
@naveedofficialchannel11 ай бұрын
Waiting your direction sir, thank you.
@naveedofficialchannel11 ай бұрын
Sorry i have this trouble right know that little bit serious issue in our AC
@workingshlub88617 ай бұрын
i am still learning these systems but i think the key is how good the installation was.....i had one where everything was labeled wrong in the AE200 causing all kinds of chaos...installer never wrote down the actual charge anywhere..
@VrfMadness7 ай бұрын
Yes exactly, installation is beyond important.
@jacobscyphers36302 жыл бұрын
Daikin stuff?
@VrfMadness2 жыл бұрын
Unfortunately I don't work on Daikin. Mainly mitsu and some LG (unfortunately, because LG is garbage.)
@derrickgarcia3032 жыл бұрын
Thanks for sharing
@nickyengle9668 Жыл бұрын
Thks!
@naveedofficialchannel11 ай бұрын
Our system is same condition that wet in compressor and accumulator. And low pressure 6bar. Low pressure pipe frozen, system will stop.