Looks like my Utica steam boiler I put in last fall Always nice workmanship!!
@Ericbakereb121 күн бұрын
Nice and clean install.
@davidlampe415321 күн бұрын
Interesting video thank you. Never occurred to me that no return flush would be from wet return, but it makes sense that collecting the dirt would be in the lowest part of the system. Now it’s clear why the dead men left long dirt pockets at the end of the steam mains and the wet returns are 6 inches above the dirt legs. I will need to get the dirt legs replaced in the next boiler.
@JamesBrown-db9pk21 күн бұрын
xcelent as allways nice work gordy
@captainwho121 күн бұрын
No shutoff valve on the Hartford Loop on this one? If I had one of those I'd be able to do your no return flush. The list of things I wish the previous owner had done is very long ha ha. The wet return has a 1-1/4 copper going to a 1/2" concentric bushing to a gate type drain valve. Lots of mud probably in there that never comes out.
@gordonschweizer515421 күн бұрын
The newer copper return was unlikely to have many issues, so I opted to get the boiler in operation test mode asap and isolate any likely issues with the old steel wet return.
@jazzcornertv20 күн бұрын
Just curious of a good place to dispose of the sludge without eventually clogging the drain line?
@gordonschweizer515420 күн бұрын
Most of the time, its just rusty water, and that's not a problem going down the drain. The water with "chunks in" can be decanted off, and the stuff at the bottom dumped outside in an unobtrusive location.
@jazzcornertv19 күн бұрын
@gordonschweizer5154 Thank you. I was concerned about how sediment builds in a pig tail, then multiply it on your drain but your explanation and suggestion of a less obstructive place is a great balance when needed.
@mikerefrigeration573621 күн бұрын
Quick question is it possible to replace a mechanical low water cutoff with a probe type on an older steam boiler?
@gordonschweizer515421 күн бұрын
It is possible if there is a plug on the boiler in the manufacture's "approved" location that can be removed. Beyond that, you will need to hang a Hydrolevel 711C manifold on the sight glass assembly and go from there.
@dannywilkins88721 күн бұрын
How long will the return flush take Gordon?,im guessing it would never be completely clean
@gordonschweizer515421 күн бұрын
The best result is to show that the return is not clogged. After that, you are absolutely correct, there is no reasonable end-point of "cleanliness" for such returns.
@BOSS_80521 күн бұрын
IS THERE ANY WAY TO CONTACT YOU THROUGH SOCIAL MEDIA OR MESSAGING? I HAVE SOME QUESTIONS THAT ARE PROBABLY SIMPLE TO YOU REGARDS TO STEAM HEAT
@gordonschweizer515421 күн бұрын
Your best bet is to post your questions and pictures on HeatingHelpDOTcom.