Finding fire alarm ground fault at a school Notifier NFS-320C

  Рет қаралды 20,916

NIC’S - SYSTEMS & ELECTRIC

NIC’S - SYSTEMS & ELECTRIC

Күн бұрын

Пікірлер: 44
@jepps1021
@jepps1021 2 жыл бұрын
Some ground fault trick&tips for notifier: -You could have multiple ground faults on NACs so always leave all the circuits unplugged - If the trouble says “Ground fault loop 1”,the fault is on your addressable loop/zones; if the trouble just says “ground fault” it’s on your panel NACs -bad battery’s can cause ground faults too
@bob5074
@bob5074 Жыл бұрын
Ancillary voltage can cause grounds (24vac control voltage for example) also, dissimilar ground potential. if you have remote amp cabinet with different ground and no ACT-1 audio coupling transformer, this can cause ground faults. Multiple chargers connected to the same set of batteries. 55ah batteries serving a 640 with an amplifier. If the charger isn’t disabled on the amplifier, you’ll get a ground.
@Roxxofoxxo
@Roxxofoxxo 2 жыл бұрын
Awesome vid!! Good job on trying to find the ground fault!! Ground faults are sucha pain in the ass to find!
@anythingalarm5429
@anythingalarm5429 2 жыл бұрын
Take out the guess work or waiting for the panel to clear by using your meter at the panel, each time you remove a circuit check resistance to ground on each wire and you will find out very quick which circuit your fault is on. It can also tell you a lot about what type of ground fault you are looking for, for instance low resistance to ground is most likely a pinched wire, higher or fluctuating resistance is usually water in a device.
@nics-systems-electric
@nics-systems-electric 2 жыл бұрын
Yeah we would start metering things if we couldn’t find it quickly but this was one of the quickest ground faults ever probably only a 25 minute job
@lumenfirealarms
@lumenfirealarms 2 жыл бұрын
Nice have fun!! ...
@Vallarasuselvaraj-k5t
@Vallarasuselvaraj-k5t 3 ай бұрын
Relay module how put address 01
@unbiasedventures2091
@unbiasedventures2091 8 ай бұрын
I appreciate the video. Headed into about 1,000,000 ft.² factory to trace the ground on Loop one and Loop two. The ground LED info will be very helpful. The ground fault disable switch does nothing on the CPU-640 board. Curious if the LEM has a disable jumper? I have my Fluke ready!
@chadrowland5234
@chadrowland5234 Жыл бұрын
I want to tell you, a ground fault can destroy a fire alarm panel...especially if it should happen to go into alarm. On some high end panels, it will shut off the troubled circuit and protect it and as soon as the ground fault is corrected, the panel will restore operation of the previously troubled circuit. However, many cheaper panels don't do this, particularly the Fire Lite MS-2 panel. On those, the second a ground fault occurs, done. The panel is garbage. And, on cheaper panels, if the ground fault occurs on the nac and the nac activates, say the panel goes into alarm, done...it will damage the nac. Higher end panels are far more forgiving so stick with higher end panels and watch out for ground faults.
@nics-systems-electric
@nics-systems-electric Жыл бұрын
As you Said it depends any panel should be fine with just a ground fault shouldn’t hurt anything just on some if it’s on the nac and actually goes into alarm but if it didn’t go into alarm any panel should be fine
@FireAlert
@FireAlert 2 жыл бұрын
Yea it can take upwards of 30 seconds for a ground to go away on those CPS-24 power supplies the 320, 640 and 3030 use. Its also a good idea to pull all 4 NACs and keep them off.
@garthpilkey5965
@garthpilkey5965 2 жыл бұрын
Clowns
@nics-systems-electric
@nics-systems-electric 2 жыл бұрын
Who
@garthpilkey5965
@garthpilkey5965 2 жыл бұрын
@@nics-systems-electric both guys in the video, too many errors due to lack of knowledge. Would have been better to either redo the video or edit out the mistakes.
@elsiebonilla7445
@elsiebonilla7445 2 жыл бұрын
Thank you for this video pickes
@mohamedali-sn2dl
@mohamedali-sn2dl Жыл бұрын
Hi
@bobnewbery8133
@bobnewbery8133 8 ай бұрын
Can humidity or dirt cause pull box ground fault?
@nics-systems-electric
@nics-systems-electric 8 ай бұрын
Water can
@richthepontiacguys1412
@richthepontiacguys1412 Жыл бұрын
Good job thats way you trouble shoot ground fault
@luyenhua5693
@luyenhua5693 Жыл бұрын
Can you tell me what the Gen-fault smoke detector is?
@nics-systems-electric
@nics-systems-electric Жыл бұрын
Probably generator room smoke detector that obviously has an issue
@icomradiouser7144
@icomradiouser7144 2 жыл бұрын
I'm crying
@vrryan6
@vrryan6 2 жыл бұрын
Cool
@gregbouchard414
@gregbouchard414 Жыл бұрын
U do a rally good job on KZbin
@nics-systems-electric
@nics-systems-electric Жыл бұрын
thank you
@connorrailfan76_csx90
@connorrailfan76_csx90 2 жыл бұрын
We have a 4007es that has a I’d nac power supply fault it is happening on and off
@connorrailfan76_csx90
@connorrailfan76_csx90 2 жыл бұрын
Ground fault
@connorrailfan76_csx90
@connorrailfan76_csx90 2 жыл бұрын
At my school
@KanoaDeCastro
@KanoaDeCastro 2 жыл бұрын
2:00 What is that? (The board)
@jpmojojack
@jpmojojack 7 ай бұрын
Looks like an XP-10 maybe? Multi-point monitor module.
@bansoytripadventures9103
@bansoytripadventures9103 Жыл бұрын
How to find the model & version in the panel sir
@nics-systems-electric
@nics-systems-electric Жыл бұрын
Notifier NFS - 320c
@bansoytripadventures9103
@bansoytripadventures9103 Жыл бұрын
Any honeywell notifier
@Twentythree33
@Twentythree33 Жыл бұрын
To find the version you have to hold the lamp test button for about ten seconds.
@abu0mhdy
@abu0mhdy 2 жыл бұрын
Can anyone please tell me what does NAC stands for?
@nics-systems-electric
@nics-systems-electric 2 жыл бұрын
Notification appliance circuit
@abu0mhdy
@abu0mhdy 2 жыл бұрын
@@nics-systems-electric thx 🙏
@bob5074
@bob5074 Жыл бұрын
If you have a mild ground on on one leg of an SLC…with SLC connected, short the non grounded leg of the SLC. If the ground is on the IDC side of a module, that module will go active. Make sure you’re disabled before doing this😂. This tip comes from a 30 year Notifier installer/programmer. When I started installing we were putting in 1010/2020s with AMG analog voice.
@nics-systems-electric
@nics-systems-electric Жыл бұрын
Oh yeah that could work I never thought of that thanks for that tip next time I run into a ground fault on a module or conventional system altogether I'll have to give that a try
@bob5074
@bob5074 Жыл бұрын
@@nics-systems-electric conventional system, you’ll just get an alarm on the zone you knew was faulted already.
@nics-systems-electric
@nics-systems-electric Жыл бұрын
@@bob5074 true but just to experiment with it to actually see the activation just for the concept
@doggishmonkey7950
@doggishmonkey7950 2 жыл бұрын
First
@Roxxofoxxo
@Roxxofoxxo 2 жыл бұрын
Okay no one cares.
@doggishmonkey7950
@doggishmonkey7950 2 жыл бұрын
You don’t have to be rude about it
Officer Rabbit is so bad. He made Luffy deaf. #funny #supersiblings #comedy
00:18
Funny superhero siblings
Рет қаралды 14 МЛН
EARTH FAULT - Fire Detection and Alarm System
17:36
FIRE PROTECTION GUY
Рет қаралды 7 М.
Chapter 23  - Troubleshooting Panel NFS-320 NOTIFIER
8:35
Lumen Fire Alarms
Рет қаралды 17 М.
สาเหตุของ Ground Fault Firealarm
10:44
Fire alarm Creator
Рет қаралды 13 М.
Notifier NFS-320C Fire alarm demo system test.
9:46
NIC’S - SYSTEMS & ELECTRIC
Рет қаралды 18 М.
Anular y Habilitar equipos Notifier NFS-320 y 640
2:38
Walter Gallegos
Рет қаралды 21 М.
Trouble Shooting an Open Circuit on a Fire Alarm System
14:26
Fire In My Generator Building Fire Alarm System Smoke Detector Activation Test
15:31
NIC’S - SYSTEMS & ELECTRIC
Рет қаралды 23 М.
SOLVING FIRE SYSTEM FAULTS #fire
11:10
FIRE PROTECTION GUY
Рет қаралды 3,9 М.