How much Voltage is needed between Earth and Neutral | Electrical Wireman | Electricals in Hindi

  Рет қаралды 628,571

Niket Shah Plus

Niket Shah Plus

Күн бұрын

Пікірлер: 610
@ravikumarjoshi2085
@ravikumarjoshi2085 Жыл бұрын
Sudhir Shah's comment is right. It is observed that due to loose connection at neutral point somewhere either in your house or main supply source, there will be higher than 10 - 15 volt between Neutral to Earth. This condition of supply line should be taken care of, otherwise higher the voltage between Neutral and Earth can lead to damage to sensitive electronic equipment and shock hazards to the equipment user.
@bakhshishsingh3165
@bakhshishsingh3165 Жыл бұрын
V good
@safuddinsardharwalla980
@safuddinsardharwalla980 Жыл бұрын
Thank u sir
@ravikumarjoshi2085
@ravikumarjoshi2085 Жыл бұрын
The ideal Voltage between Neutral and Earth should always be " 0 " . It should never be more than 5 volts. But to confirm that, Earth connection is in a proper working condition, the Voltage reading between Phase and Earth should be 5 to 10 volts less than voltage between Phase and neutral. If there is " 0 " voltage between Neutral to Earth as well as between Phase to Earth, then it is understood that, Earth connection is either disconnected or not provided to that point.
@sumansaha295
@sumansaha295 Жыл бұрын
If the voltage between earth and neutral is exactly zero and the continuity test is beeping when tested with multimeter, does it mean they are shorted?
@tahirakram2783
@tahirakram2783 Жыл бұрын
yes it is interesting aspect, but seems to be correct. I think one point why the voltage between neutral and earth appears which is due to unbalanced load on three phases from the distribution transformer. This reason has not been highlighted.
@mr.bhupendra24
@mr.bhupendra24 10 ай бұрын
Phase to Earth 220v and Phase to Neutral 220v ac. Neutral to Earth 2 to 3 volts, Neutral to Ground 0v ac.
@mustafashoque6704
@mustafashoque6704 Жыл бұрын
Very nicely described and in an easy way it is a mix of theory and practical...hearty congrates sirjee
@digamberthorve106
@digamberthorve106 11 ай бұрын
आपण खरोखरच फारच अनुभवी तज्ञ आहात.
@mohdsaud7920
@mohdsaud7920 3 ай бұрын
Very good perfect explanation regarding neutral and earth
@NiketShahPlus
@NiketShahPlus 3 ай бұрын
Thanks a lot.. do share this video with your family and friends also
@harshadkumarmakvana4298
@harshadkumarmakvana4298 Жыл бұрын
Lot's of thanks Sirji, For the valuable information about the voltage between Earth &Natural and also proper voltage mension in the house....
@NiketShahPlus
@NiketShahPlus Жыл бұрын
So nice of you
@anilkumardahariya8719
@anilkumardahariya8719 Жыл бұрын
सुपर सर जी , आप बहुत अच्छी तरह से समझाते हैं।❤
@ravijadhav538
@ravijadhav538 Жыл бұрын
Simple way to describe... superbbbbbb 👍👍👍 i like it
@shailendrasingh-mrj56
@shailendrasingh-mrj56 Жыл бұрын
I think it is correct to have voltage between earth and neutral around 3 to 5 volts, according to me, if there is more voltage than that, then there may be a fault in some device of the house.
@kirtysoma5345
@kirtysoma5345 Жыл бұрын
Perfect balance of explanation
@sudhirshah2005
@sudhirshah2005 Жыл бұрын
One more very important and reason should have been mentioned here which is happening majority time rather than other reasons. Sometime the neutral from the power company creates such problems in neutral level increases due to some fault there, but resolves on its on. During such period you get about 20 to 30 voltas between neutral and Earth. Please comment 🙏
@gunjansharma1918
@gunjansharma1918 Жыл бұрын
yes u r right the busbar they r using is only for phase and neutral, no proper earth is done
@AwaisAli457
@AwaisAli457 4 ай бұрын
I do have same.issue . Neutral from main supply from government is giving 80 volts . How to solve ?
@srvideoediting6646
@srvideoediting6646 Жыл бұрын
Good Informative Video. 👍👌
@hemchandmoosun4467
@hemchandmoosun4467 Жыл бұрын
Sir ji aapka explained karne ka tarika laajawaab hain 😊👍🙏
@aijazurrehman2478
@aijazurrehman2478 Жыл бұрын
atisundar hai apke batane ka trika ..dhanywad..
@deeneislam69
@deeneislam69 11 ай бұрын
Perfect explanation
@FrancisDsa-m1k
@FrancisDsa-m1k 2 ай бұрын
Every effort you have taken to teach appreciate brother 🙏 🙌
@NiketShahPlus
@NiketShahPlus 2 ай бұрын
So nice of you... Do share this video with others
@rameshatkare9997
@rameshatkare9997 Ай бұрын
Thank you sir very useful video your video always help me 2 or 3 volt ok good neutral and earthing common
@NiketShahPlus
@NiketShahPlus Ай бұрын
Always welcome.. do share this video with others
@prabhakarbhangare9205
@prabhakarbhangare9205 7 ай бұрын
Nutral aur phase कि wire एक ही gauge की लगणा चाहिए ये आज मैने पहिली बार सूना. And auther information is very nice Thanks
@NiketShahPlus
@NiketShahPlus 7 ай бұрын
Do share with your friends
@anupdev5845
@anupdev5845 22 күн бұрын
Usually electricians tend to loop the neutral wire and use the same wire to loop through multiple switch boards in multiple rooms. In such cases, it is important to actually oversize the neutral wire since one single neutral wire is used to serve as return path for multiple phase wires.
@rakeshsondkar5223
@rakeshsondkar5223 6 ай бұрын
सुंदर माहिती आहे धन्यवाद
@NiketShahPlus
@NiketShahPlus 6 ай бұрын
Thank you
@bluemoon4191
@bluemoon4191 Жыл бұрын
Very crystal clear information
@SunilAruldas
@SunilAruldas Жыл бұрын
Very clear tutorial. Thank you
@Hemantgora
@Hemantgora 3 ай бұрын
Apki saari baaton se hm sehmat hain👍
@NiketShahPlus
@NiketShahPlus 3 ай бұрын
Aapke vicharon ke liye dhanyavaad! Agar aapke paas koi aur sawal ya madad ki zaroorat ho, toh zaroor bataiye. Main yahan hoon madad ke liye! and do share this video with other also
@shansoti2588
@shansoti2588 Жыл бұрын
Helloo sir Mera ghar village area mei hey ...high hill mei parta hey .....udar weather mei bahut kharb hota hey lightning thandar ka problem hey .. ussee bachna kunsa earthing thik rahey ga?
@bhashkarrai4665
@bhashkarrai4665 Жыл бұрын
Bahut accha aap ne sikhaya sir
@rwggaming4236
@rwggaming4236 Жыл бұрын
Very nice 👍 some douts about Neutral and earthing is clear.. Thank you
@digamberthorve106
@digamberthorve106 11 ай бұрын
अगदी नविन माहिती ऐ कायला मिळाली आपला फारच आभारी आहे.
@vincentrodrigues655
@vincentrodrigues655 7 ай бұрын
Very informative briefing. 👍👍👍
@NiketShahPlus
@NiketShahPlus 7 ай бұрын
Glad it was helpful!do share with your friends
@RajeshBehera-lt8xw
@RajeshBehera-lt8xw Жыл бұрын
This is very useful and important video🎥 thanks sir
@NiketShahPlus
@NiketShahPlus Жыл бұрын
So nice of you
@sukhdevbhuyan9128
@sukhdevbhuyan9128 8 ай бұрын
Superb performance excellent explanation
@NiketShahPlus
@NiketShahPlus 8 ай бұрын
Thank you so much 🙂 do share with your friends
@jitendrasahu1908
@jitendrasahu1908 Жыл бұрын
Mujhe bahut pasand aaya sir ji
@MCTPrasad-jj6et
@MCTPrasad-jj6et 10 ай бұрын
Good explanation.
@sahabramverma7716
@sahabramverma7716 Жыл бұрын
Sir apki video bahut achhi lgi
@onyxury101
@onyxury101 Жыл бұрын
Thanks bro; it was really helpful
@sureshjadhav7645
@sureshjadhav7645 Жыл бұрын
Good information. Thanks
@singadisivakumar5014
@singadisivakumar5014 Жыл бұрын
Very nice bro , very useful
@rajneeshpandey1132
@rajneeshpandey1132 11 ай бұрын
Bahut badhiya video
@javedsheikh6447
@javedsheikh6447 Жыл бұрын
Sahi jankari di aapne
@jiwanjanoti8620
@jiwanjanoti8620 5 ай бұрын
Good and infomative tech video.
@NiketShahPlus
@NiketShahPlus 5 ай бұрын
Glad you liked it!.. do share this video with others also
@Fulldhamaalno1
@Fulldhamaalno1 Жыл бұрын
Thank you sir, good information, समझाने की तरीका बहुत ही खास है👌👌👍👍
@छत्रपतींछावा
@छत्रपतींछावा Жыл бұрын
सर बेस्ट नौलैज‌‌ ❤👆👌👌
@kareemjassani3443
@kareemjassani3443 Жыл бұрын
Namaste sir Very nice video
@kareemjassani3443
@kareemjassani3443 Жыл бұрын
Sir Mere yaha ek new machine ka connection diya hai Electrician ne loop karke neutral diya hai...jisse dusri machine mein body shot AA Raha hai. Kuch solution dijiye sir. . Thank you 🙏
@AmazingWorld_.
@AmazingWorld_. 3 ай бұрын
Good information 👍 ❤
@NiketShahPlus
@NiketShahPlus 3 ай бұрын
Thanks for liking. do share this video with others
@thomasjoseph2975
@thomasjoseph2975 Жыл бұрын
Very good teaching sir. Thank you very much.🙏
@vinodranavinodrana261
@vinodranavinodrana261 Жыл бұрын
Good suggestion
@anilghode8965
@anilghode8965 6 ай бұрын
बहोत खूब ❤
@NiketShahPlus
@NiketShahPlus 6 ай бұрын
Thank you.. do share this video with others
@sunilkshirodkar3053
@sunilkshirodkar3053 Жыл бұрын
Namasthe sar, your teach very good 👍.
@srvideoediting6646
@srvideoediting6646 Жыл бұрын
Anchor ma kon sa Modular Board's Best ha, Rider, Roma Clasic, Roma Plus, Roma urban, for Home.
@kamal2kotabagh
@kamal2kotabagh Жыл бұрын
Gret white brand ka switch badiya hota he, Gret white, Anchor brand ka aapas me purana relation he,Google search kar dekhana
@premprakash5204
@premprakash5204 Жыл бұрын
Very use full knowledge
@abdulkadar41234
@abdulkadar41234 10 ай бұрын
Very good. Ab. Kadar Khan.
@bhaveshpatel1280
@bhaveshpatel1280 Жыл бұрын
Singal fej miter mae nutral earthing kiya jata hai.
@DJNrv
@DJNrv Жыл бұрын
Ye problem summer me hi jyadatar hota hai kyo ki transformer ko Earth me paani nhi milta isliye... Or koii dusri vaja nhi hai ...
@vktismail5757
@vktismail5757 Жыл бұрын
very good. Well explained. Thank you sir
@robingupta1114
@robingupta1114 Жыл бұрын
Sir ev car charge battery 40 kw karne ke liye kitna solar panel lagega mere pass Nexon ev max hai
@bhilumeshkumarbhagavanbhai9504
@bhilumeshkumarbhagavanbhai9504 Жыл бұрын
3 to 5 volt between neutral to earth.
@PRNadh
@PRNadh Жыл бұрын
Neutral to earth not to zero, less than one volt, in case voltmeter select should adjust, neutral resistance less than one Ohm. As per the electrical engineering.
@Electricianprince_G
@Electricianprince_G 8 ай бұрын
Good work ❤❤❤❤
@NiketShahPlus
@NiketShahPlus 8 ай бұрын
Thanks ✌️do share with your friends
@UMESHPATEL-dt6zc
@UMESHPATEL-dt6zc Жыл бұрын
Agar neutral link se har room se neutral circuit ko lakar connect karte hai to wire material expenses double ho jayega sir ji
@narasinghasahu8875
@narasinghasahu8875 11 ай бұрын
Very nice sir🙏
@Electrical3442
@Electrical3442 Жыл бұрын
electronic equipment and server room Switched 2v is very necessary
@DineshShet-w3e
@DineshShet-w3e Жыл бұрын
0 volt
@ramraja7796
@ramraja7796 Жыл бұрын
Great Video but you must point out that this is only good for India, as it's wiring is spur for each room for sockets in UK and may be in Europe the Socket wiring is ring mains wiring and it uses 2.5mm wire for Live & Neutral and 1mm for Earth wire
@Imtiyaz5power
@Imtiyaz5power Жыл бұрын
Lovely Video ❤
@V98000
@V98000 Жыл бұрын
नमस्ते सर, अगर मेरे यहां फेस और न्यूट्रल में 250v आता है तो फेस और अर्थिंग प्वाइंट पर 230v मिलता है....क्या मेरी earthing strong मानी जाएगी? मैंने घर के लास्ट खंभे के स्टेक वायर से अर्थिंग ली है....और सेफ्टी के लिए जब खंभा लगाया जा रहा था तो स्टेक वायर और खंभे के बीच एक हेवी इंसुलेटर लगवा दिया था जिससे अगर कभी खंभे में लीकेज आ जाए तो वो स्टेक वायर में ना आए।
@Kamalfkt
@Kamalfkt Жыл бұрын
Video achhe hain ...
@aniljain9006
@aniljain9006 5 ай бұрын
Nice video sir thanks.
@NiketShahPlus
@NiketShahPlus 5 ай бұрын
Nice.. do share this video with your friends
@techrsselectrician
@techrsselectrician Жыл бұрын
Kya baat h sir maja aa gya...
@proudindian8041
@proudindian8041 9 ай бұрын
Fantastic explanation. Can u please tell us the correct earthing wire sizes for airconditioners and other appliances like geyser, iron box etc / bulb, fan etc
@NiketShahPlus
@NiketShahPlus 9 ай бұрын
Will try to make video on this
@e.vp.v5600
@e.vp.v5600 Жыл бұрын
It should be greater than 0 but less than 6 VAC
@milindpatil5091
@milindpatil5091 Жыл бұрын
Thanks. Very well explained.
@sanjaykondekar3734
@sanjaykondekar3734 Жыл бұрын
This video clip is very nice.Ask to one question that if voltage between neutral and earth has more than 3.5 volt,Is it affecting the electrical energy bill.. If it is zero volt, is it affecting electricity bill..?
@Rajendr9651
@Rajendr9651 Жыл бұрын
Yes, affecting, but ,how much ? Twenty eight Paisa per bill.
@dineshparmar6464
@dineshparmar6464 6 ай бұрын
I have made new earthing at home because the old one is showing more than 230volt between nutral to earth at all the points. Now, the neutral to earth is between 16v to 22 volt at all points. No appliances are damaged or malfunction. How to resolve the more voltage between neutral to earth. Wiring done by builder looks poor, and almost all points were loose connections. And seems extended neutral wire from main point. Some. Do suggest the best way to solve the problem. Thanks
@NiketShahPlus
@NiketShahPlus 6 ай бұрын
First check the load on neutral.. make proper bus bar as well as if possible implement RCCB.. upto 10v is also ok between neutral and earth
@arunkhanna8530
@arunkhanna8530 Жыл бұрын
Thanks for sharing
@shanmallick9864
@shanmallick9864 Жыл бұрын
Thanks
@SreeParasharaSreedharBhattar
@SreeParasharaSreedharBhattar Жыл бұрын
Good one sir
@Toli737
@Toli737 Жыл бұрын
sir agar 2- 5 v aata h to kya mai us volt ka use kar 1.5 volt wala led 4 se 5 led series me jorkar direct jala sakte h ya nhi
@gappuhegde334
@gappuhegde334 Жыл бұрын
Sir thankyou for your information
@maheshkava8817
@maheshkava8817 Жыл бұрын
अगर trasformar से nutal से जो graunding होता हे वो लूज या तो निकल जाता हे तो भो N E पे ज्यादा वोल्ट आएंगे जो अक्सर गावो मे होता हे nutral और phese दोनों ने testar दिखाए गा
@mustafashaikh8303
@mustafashaikh8303 Жыл бұрын
The best 👍
@oasisAUH
@oasisAUH Жыл бұрын
As you told. is there cable size 3 sq mm ?
@rjsameer249
@rjsameer249 Жыл бұрын
Less than 5 V hona chahiye
@nithyanadas5220
@nithyanadas5220 Жыл бұрын
Good information sir
@axn4376
@axn4376 Жыл бұрын
Neutral say ek room por 5 point cunnection k liya ek hi Neutral say hony say kya hoga
@santoshnegi2862
@santoshnegi2862 8 ай бұрын
Good knowledge
@NiketShahPlus
@NiketShahPlus 8 ай бұрын
So nice of you do share with your friends
@SimonKarre-kw8fx
@SimonKarre-kw8fx Жыл бұрын
Nice video sir 👍
@kaushikcoolable
@kaushikcoolable Жыл бұрын
Earthing k liye kitna wire size Dena chahiye??
@BhakurTech
@BhakurTech Жыл бұрын
😊Sir aapne bahut acha bataya lekin sir ek mistake ho gay aapse 3mm ka wire nahi aata hai sir😊
@noelpeter1735
@noelpeter1735 10 ай бұрын
Very Very good sir thank you sir
@NiketShahPlus
@NiketShahPlus 10 ай бұрын
Most welcome
@surajroy1520
@surajroy1520 Жыл бұрын
Thanks dear sir
@RajvindarRaj-m7m
@RajvindarRaj-m7m Жыл бұрын
Sir mere ghar me jab mene earthing check kiya toh Phase+Nutral=228v dikha raha tha Phase+Earth=227v Aur Nutral+Earth=8v dikha raha tha Sir aap please bataiye ye neutral to earth jo 8v aaya he ye sahi he ya galat ....please bataiye aur agar galat he to ise sahi kese kiya jaye please bataiye
@NirajKumar-w1q6w
@NirajKumar-w1q6w 8 күн бұрын
Rong hai
@chandandigital9357
@chandandigital9357 Жыл бұрын
Thank you
@shivajishahapurkar1838
@shivajishahapurkar1838 Жыл бұрын
यह सही है ,neutral loop ,नही करना चाहिए।
@surendrasahu8436
@surendrasahu8436 Жыл бұрын
Super sir ji thankyou sir ji
@mahmoodmirza3301
@mahmoodmirza3301 Жыл бұрын
Zero Volt is the Best! Upto 5V Potential Difference P.D. between the Earth and Neutral is OK. The higher the poor! The electrical devices would perform poorly if this P.D. is higher.
@kochising659
@kochising659 Жыл бұрын
Thank u sair.
@DushyantSiyag
@DushyantSiyag Жыл бұрын
Hello bhai ...hamare ghr m earth ka wire connect nhi h earth se fir bhi usme 17 volt aata h earth wale wire m ... sab device check kr k dekh liya.. mil hi nhi rha h
@vp.naranga
@vp.naranga Жыл бұрын
Aap earth ka wire connect kariye sahi ho jayega q ki mere sath bhi same problem tha
@narayansahoo1660
@narayansahoo1660 Жыл бұрын
Right side thiki achhi କିମ୍ୱା ୦ voltage ହିଁ ଟିକି ଅଟେ।
@PRATIKPARDHI1504
@PRATIKPARDHI1504 Жыл бұрын
Sahi hai Boss
@ashokpawar6201
@ashokpawar6201 5 ай бұрын
धन्यवाद 🙏
@NiketShahPlus
@NiketShahPlus 5 ай бұрын
Welcome.. do share this video with others also
@sunilsahu2525
@sunilsahu2525 Жыл бұрын
Very nice sir
@YashKumar-hu1xt
@YashKumar-hu1xt Жыл бұрын
Sir from this 3 v come from between netural and earth ?
@chandumujum6904
@chandumujum6904 Жыл бұрын
Tc grpound ok hai ya kise chake Karn
Can we Connect Earthing in place of Neutral | Neutral vs Earthing | Interview Question
7:16
Electrical With Abhishek Joshi
Рет қаралды 215 М.
From Small To Giant 0%🍫 VS 100%🍫 #katebrush #shorts #gummy
00:19
Кто круче, как думаешь?
00:44
МЯТНАЯ ФАНТА
Рет қаралды 6 МЛН
How many people are in the changing room? #devil #lilith #funny #shorts
00:39
БУ, ИСПУГАЛСЯ?? #shorts
00:22
Паша Осадчий
Рет қаралды 3 МЛН
How to Reduce Earth Resistance | Earthing Resistance | Electrical Safety| Hindi
7:00
Electrical With Abhishek Joshi
Рет қаралды 43 М.
From Small To Giant 0%🍫 VS 100%🍫 #katebrush #shorts #gummy
00:19