It might help to take the answer and use it to size the OCPD and conductors at the end. I am not sure but I think the total load would be 117.66 amps; this would require a 125 amp service OCPD with copper #2 sized from T310.12(A). Do you agree with these numbers?
@Rusty-gm7gjАй бұрын
13:17 I do not understand how you got 32,800 VA as your total VA.
@jarodvelectric7431Ай бұрын
This is just an example. These are separate examples to break down each section of the calculation into separate sections. The point is to show you if you had 32,800 VA, what you would do with it in the optional method. At 15:17 there is an actual example which includes everything all at once.