Over current calculation and setting

  Рет қаралды 36,677

Electrical and Electronic tech

Electrical and Electronic tech

Күн бұрын

Over current calculation and setting

Пікірлер: 32
@Invisible_Tri
@Invisible_Tri 3 жыл бұрын
Your every videos are like Gems👍
@gopalmondal5082
@gopalmondal5082 2 жыл бұрын
Very good
@sharifhossain8830
@sharifhossain8830 Жыл бұрын
👍
@surendrakverma555
@surendrakverma555 Жыл бұрын
Very good. Thanks 🙏🙏🙏🙏🙏
@rajkumarpujari8426
@rajkumarpujari8426 9 ай бұрын
Thank you sir
@aprojmyageri5378
@aprojmyageri5378 Жыл бұрын
Plz make a video on ELR selection for factory...
@israradil3625
@israradil3625 3 жыл бұрын
Thanks
@badshahibrahim5423
@badshahibrahim5423 3 жыл бұрын
Thanks for it.
@amitkalyan5435
@amitkalyan5435 3 жыл бұрын
Make a video on alternator relay panel controlling avr close loop
@RahulKumar-sw2hk
@RahulKumar-sw2hk 9 ай бұрын
Sir please explain other protection set value
@RahulKumar-sw2hk
@RahulKumar-sw2hk 9 ай бұрын
Like E/F U/V O/V etc.
@mohammadpathan4668
@mohammadpathan4668 4 жыл бұрын
can we use LV side setting instead of HV side O/C setting in this REF 615 relay ?
@ElectricalandElectronictech
@ElectricalandElectronictech 4 жыл бұрын
Yes, you can set L. T side, but C. T input taken from L. T side
@panditvishal5451
@panditvishal5451 Жыл бұрын
Sir here in this setting whts the mean of time setting multiplayer is 1 available why it's value is 1? Please make full video so same in setting group all setting meaning can understand like operation is On out of 3 and Tsm like that..
@mshanmugapriyan
@mshanmugapriyan 3 жыл бұрын
Please put earth fault calculation like this
@ElectricalandElectronictech
@ElectricalandElectronictech 3 жыл бұрын
Thanks for your comment, I will publish shortly
@ASHOKKUMAR-xd5gu
@ASHOKKUMAR-xd5gu 2 жыл бұрын
Please provide fault current calculation for jvs relay..
@shaikkhaja2821
@shaikkhaja2821 10 ай бұрын
Sir, I>,I>> Kaisa set karsakte hy .
@poojamishra024
@poojamishra024 2 жыл бұрын
What is IN???I think you had done wrong calculation. It shoud be 0.55*IN..where IN is I nominal you can take IN 400 or 5 amp..Pls explain...
@debdattaG
@debdattaG Жыл бұрын
Yes ,he is wrong. You are absolutely right.
@orkhanmirishli1631
@orkhanmirishli1631 Жыл бұрын
In should be ct primary
@orkhanmirishli1631
@orkhanmirishli1631 Жыл бұрын
What is ln inside relay? Ct primari?
@aitazazahsanofficial
@aitazazahsanofficial 3 жыл бұрын
agAr 300/1 ki ct hai tu phr ka setting ho gi
@rahulsahane6878
@rahulsahane6878 3 жыл бұрын
Wrong calculation. If transformer full load has 220Amp. And u are setting,CT ratio-400 for primary and 5 amp for secondary. Then In-400Amp. If you are putting low stage full load overcurrent tripping setting,it should be 85% of your full load current. It simply means it should be set as a 0.85*In.
@ElectricalandElectronictech
@ElectricalandElectronictech 3 жыл бұрын
If you set 0.85.the relay trip at 340 amp(0.85 x400) But your full load current 220amp. Then how to relay protect your load
@rahulsahane6878
@rahulsahane6878 3 жыл бұрын
@@ElectricalandElectronictech sir I am justing giving example for low stage. If you FLC is 220 Amp. U can set 0.5*In. So it will trip on 200A for low stage overcurrent.
@ElectricalandElectronictech
@ElectricalandElectronictech 3 жыл бұрын
Friend ,you are right as per your Calculation ,if CT ratio 400/1 amp.you can set 0.5 for 200 amp tripping. But if CT ratio 400/5 amp you should set 2.5 for 200 amp, 2.75 for 220 amp.
@orkhanmirishli1631
@orkhanmirishli1631 Жыл бұрын
@@ElectricalandElectronictech where did you find 0,5 and 2,5 from?
@fredysaragih8537
@fredysaragih8537 3 жыл бұрын
Dear sir, can you simulate, how to set the p3 easergy relay configuration, with transformer 2000kva, 20 kv/0.4 kv, thx
@pavankumarnaik3908
@pavankumarnaik3908 3 жыл бұрын
Dear sir, can you please explain regarding rej601 relay setting ,I>,I》,I>》,I0>,I0》, SEND UR NO. sir, please sir
@ElectricalandElectronictech
@ElectricalandElectronictech 3 жыл бұрын
My number 8248719700
@TheNascentMan
@TheNascentMan 27 күн бұрын
In ka kya matlab hota hai?
Relay setting calculation|IDMT relay|Protection|Electrical Technology and Industrial Practice
8:10
ELECTRICAL TECHNOLOGY and INDUSTRIAL PRACTICE
Рет қаралды 181 М.
How I Did The SELF BENDING Spoon 😱🥄 #shorts
00:19
Wian
Рет қаралды 36 МЛН
Пройди игру и получи 5 чупа-чупсов (2024)
00:49
Екатерина Ковалева
Рет қаралды 3,2 МЛН
Gli occhiali da sole non mi hanno coperto! 😎
00:13
Senza Limiti
Рет қаралды 16 МЛН
طردت النملة من المنزل😡 ماذا فعل؟🥲
00:25
Cool Tool SHORTS Arabic
Рет қаралды 10 МЛН
Over Current Protection Setting Calculation in details | Part 2
19:24
C&S IDMT Relay setting
9:22
Kheman Verma
Рет қаралды 38 М.
ABB Make || REF615 || Over current and earth fault relay || Hindi
5:04
Protection Relay Setting Calculation for Transformer Feeder Relays
20:49
Over current relay solved numerical problem
11:03
Techspecial Information
Рет қаралды 76 М.
ABB REF615 Connection ,Testing & commissioning
8:42
Learn Tech
Рет қаралды 64 М.
Over current relay CDG 31
8:05
PRM’S Learning Hub
Рет қаралды 17 М.
How I Did The SELF BENDING Spoon 😱🥄 #shorts
00:19
Wian
Рет қаралды 36 МЛН