Polarization Index Testing (Long Version)

  Рет қаралды 23,054

Joe Istre

Joe Istre

Күн бұрын

Пікірлер: 19
@EonTide1111
@EonTide1111 10 ай бұрын
Is the polarization index table listed here in the NEC or where is that general info found
@30mAkills
@30mAkills Жыл бұрын
Per IEEE 43 - 2013 Part 12.2.2, when IR value exceeds 5 Gohms @ 1 min, PI test can have inconclusive results, and may not be a valid indication of the insulation condition. Means the calculated PI may not be meaningful. Megger may be a giant, but they won't reveal the point for their benefit. Most of their literature is based on obsolete insulating materials purposely. Something like outdated syllabus. Then what's the working voltage of that jumper? How you selected 5 KV as injected voltage? Thanks.
@douglasgimenez5480
@douglasgimenez5480 Жыл бұрын
Nice explanation, thanks a lot sir 👏🏼
@drjohn5407
@drjohn5407 4 жыл бұрын
When referring to molecules, I believe you mean atoms. Those atoms containing a balance of the nucleus of protons surrounded by the orbiting electron field - the excited (free) electrons being those which move from atom to atom - hence voltage potential and current flow.
@joeistre2717
@joeistre2717 3 жыл бұрын
In the PI art, the molecules are referring to insulator molecules - usually plastics. I would agree with you for conductors. Then again, if we are getting these minuscule current flows from plastics, I suppose we are stripping the outer electrons from the outer orbitals of the molecules with the high voltages.
@danielalvarenga3081
@danielalvarenga3081 4 жыл бұрын
Excellent explanation, thank you so much!
@bengkelS2M
@bengkelS2M 2 жыл бұрын
so easy to understand... thanks sir
@joseriggio4366
@joseriggio4366 Жыл бұрын
why you not measure betwen conductors instead,?, the way you’re testing will show insulation results only at tha point, but i you check the cord betwen conductors will give de idea how is the insulation alongside, thanks
@pedalpromise1017
@pedalpromise1017 5 жыл бұрын
the question is, why does resistance increase with time?
@andrewwong4827
@andrewwong4827 5 жыл бұрын
The tested system acts like a capacitor. The theory of a capacitor in a DC system is that during its initial stages, there are some current transfer between the two conductors. After some time, it tapers off and no current transfer occurs as it is an open circuit. So for a PI test, the first minute is like the initial stages where there are some small current transfer, hence the lower resistance due to ohms law. Around the 10 minute mark should be the point where there's no current transfer, hence the higher resistance due to ohms law.
@LIM_Khuan
@LIM_Khuan 3 жыл бұрын
great
@RizwanKhan_99
@RizwanKhan_99 6 жыл бұрын
GREAT !!!
@சக்திவிவசாயம்-ஞ1ய
@சக்திவிவசாயம்-ஞ1ய 3 жыл бұрын
Any jobs opportunity Electrical Testing Engineer
@ajaytr3344
@ajaytr3344 3 жыл бұрын
Why are we taking 10 min??
@joeistre2717
@joeistre2717 3 жыл бұрын
It is an industry standard test. PI is a 10 minute test.
@nahashamsa2791
@nahashamsa2791 2 жыл бұрын
Hi sir... which standard it is mentioned?
@OmniBaddie
@OmniBaddie 2 жыл бұрын
@@nahashamsa2791 IEEE Standard 43-2000
@30mAkills
@30mAkills Жыл бұрын
@@OmniBaddie Please read part 12.2.2. PI is not recommended if the 1 min IR value exceeds 5 Gohms.
What is Polarization Index (PI) Test and How to Perform It? |EXPLAINED
7:07
ElectricalEngineeringPlanet
Рет қаралды 6 М.
Insulation Resistance Part 1 - Why do it?
13:24
JPElectric
Рет қаралды 33 М.
Каха и дочка
00:28
К-Media
Рет қаралды 3,4 МЛН
Try this prank with your friends 😂 @karina-kola
00:18
Andrey Grechka
Рет қаралды 9 МЛН
Transformer Turns Ratio Test - Protec Equipment Resources
29:47
Protec Equipment Resources
Рет қаралды 33 М.
Insulation Resistance Test of Transformer
7:21
The Engineering Power
Рет қаралды 109 М.
Insulation Testing Fluke-1507 - Fluke Fridays - Episode 106
8:02
Fridays With Brandon
Рет қаралды 88 М.
Tan Delta (DF or PF) Testing Explained part 2 - Theory
19:29
Andrej Sepcic
Рет қаралды 35 М.
Transformer IR Test
7:22
Butch Chxa
Рет қаралды 26 М.
How to test transformers
16:22
Serge Levesque
Рет қаралды 33 М.
Sverker 900 Useful Functions (Long Version)
13:56
Joe Istre
Рет қаралды 1,3 М.
Polarization Index Testing - Motor Repair Best Practices
3:02
Electrical Equipment Company
Рет қаралды 23 М.
Каха и дочка
00:28
К-Media
Рет қаралды 3,4 МЛН