It is the ratio of reading taking after 15 or 30 seconds to reading taking after 60 seconds with same coonection as your video. Both readings are taken in one step. The purpose of this test is to ensure integrity of the winding insulation.
@nkvaishnav63953 жыл бұрын
Nice Explanation point to point...Will wait for next video.. Quality video..
@theengineeringpower42133 жыл бұрын
thanks for appreciation. More videos coming soon. Keep in touch.
@shashanksahu23262 жыл бұрын
It is really a very helpful video. It has cleared all my doubts. Thank u sir.
@theengineeringpower42132 жыл бұрын
You are welcome and thanks for ur valuable feedback.
@ziaullhaqzahid345817 күн бұрын
Helpful
@erwinreyes58884 ай бұрын
thank you so much for your helpful videos
@benjaminotettey6315 Жыл бұрын
I love the explanation
@chandanjana6964 Жыл бұрын
Informative, Thnx sir.
@jaydoctor78242 жыл бұрын
Thank you sir for your educational video.
@theengineeringpower42132 жыл бұрын
You are welcome. Keep in touch for more educational videos related to practical Electrical Engineering.
@smartengineeringeee499010 ай бұрын
Please give the reference informations in detail that where did you get it.
@judebarnes75952 жыл бұрын
Nice work - thank you for posting this video. In the calculations you compensate based on room temperature. Should you instead be compensating for transformer oil temperature.
@theengineeringpower42132 жыл бұрын
You are right. In this video, for simplification ambient temperature is used. However for accurate calculation, the transformer oil temperature must be used, Thanks for your valuable comment.
@erisherm.8451 Жыл бұрын
Very informative indeed 👍
@theengineeringpower4213 Жыл бұрын
Thanks for appreciation.
@earnmoney25052 жыл бұрын
Thank you sir🙂 ,this is very helpful .
@dengakairup2 ай бұрын
You are right 👍
@JhonTesfahun Жыл бұрын
nice work.
@rangerrojo50473 жыл бұрын
Nice work. What books do you suggest about this topic?
@theengineeringpower42133 жыл бұрын
Thanks. As someone practically associated with sub-stations and T/Lines, I would suggest to study updated articles from the internet as the testing sets are evolving with time.
@kdmq Жыл бұрын
It's OK to say that any transformer is safe to operate at 20 Celsius, but what if the manufacturing company knows that the transformer is going to be subjected to ambient temperatures much hotter than 20 Celsius? Isn't it better to apply the IR test for the maximum operating temperature. For example, if the transformer is being used in hot summer climates where the temperature regularly reaches 35 Celsius, shouldn't we apply the test for 35 Celsius to make sure there will be no arcing at all times of the year?
@kiwidevo13 жыл бұрын
What voltage are you setting the megger to for each test H-XG X-HG and HX-G ?
@theengineeringpower42133 жыл бұрын
For a High voltage i.e. 220kV or 500kV transformer, the megger testing set rating must be 5 kV. For medium voltage i.e. 11kV, megger set of 1kV rating is OK.
@TwoFaced2 Жыл бұрын
Can you please make videos on testing of power cables
@theengineeringpower4213 Жыл бұрын
Sure. I will upload soon IA.
@goodman123103 ай бұрын
is the 20 ' c the temperature of winding of the ambient temperature , another thing would this work with dry transformers ? thanks
@Kishore_.0352 жыл бұрын
What is the resistance value at a temperature of 40 degree celcius
@cedarelectric77634 ай бұрын
How do we adjust the temperature of the oil of the transformer
@cedarelectric77634 ай бұрын
How dovi test for the temperature of the transformer oil
@Wolf.88 Жыл бұрын
Thanks!
@86karna Жыл бұрын
How the input supply is injected for testing of transformer?. Input source
@theengineeringpower4213 Жыл бұрын
Input source is the megger testing set which has built-in battery (in case of electronic set). While in case of old hand operated manual megger testing set, voltage is produced by rotation of crank.
@akhtarhussainshah74352 жыл бұрын
if DAR less the 1 it is dangerous need for maintenance if ration greater then 1 and less then 1.3 the check oil BDV mositure contents and C & DF test of winding if the ratio greater then 1.3 it is good
@natural60862 жыл бұрын
why did not you use guard terminal.
@theengineeringpower42132 жыл бұрын
It's used practically in most cases. Not shown here to avoid any confusion for new learners. Guard terminal is a way to minimize the interference from unwanted circuits. So e.g. if we are measuring insulation resistance between primary and ground, we will have to guard the secondary terminal of transformer.
@hariharroy11 ай бұрын
@@theengineeringpower4213Could you please explain in more detail? What do you mean by 'to minimise interference from unwanted circuits'?
@sunildevariya79652 жыл бұрын
Tnx
@324amit77 Жыл бұрын
3:04 isn't it 500kOhm ?
@akhtarhussainshah74352 жыл бұрын
Dielectric Absorption Ratio (DAR) Test insulation test ruther then IR test
@akhtarhussainshah74352 жыл бұрын
DAR b/w HV to LV, LV to G , HV to G
@tyd34072 жыл бұрын
Major Farts 🤣
@theengineeringpower42132 жыл бұрын
Subtitles :)
@jasonchristopheraguillon4988 Жыл бұрын
Insulation Reating of Einding must be not lower Than 10Giga ohms not in mega
@theengineeringpower4213 Жыл бұрын
As per insulation resistance minimum requirements for a transformer, for each kV atleast we must have 2 Mega Ohm resistance. so based on this, you can calculate minimum insulation resistance requirements for any rating transformer. that will turn out to be in Mega ohms in most cases