Protection Relay Setting Calculation for MV Motor Feeder Relays

  Рет қаралды 9,364

Julius Salutan

Julius Salutan

Күн бұрын

Performed relay setting calculation for the following relays:
- Excessive Start Time Protection Relay (48)
- Thermal Overload Protection Relay (49)
- Negative Phase Sequence Protection Relay (46)
- Stall Detection Protection Relay (51LR)
- Phase Under Voltage Protection Relay (27)
- Phase Over Voltage Protection Relay (59)
- Phase Time Delay Overcurrent Protection Relay (51)
- Ground Time Delay Overcurrent Protection Relay (51G)
- Start Number Protection Relay (66)
- Loss of Load Protection Relay (37)
- Sonde Temperature in Windings

Пікірлер: 13
@tuna6423
@tuna6423 7 ай бұрын
Hi Julius, I am thinking that 24:15 Earth fault protection If it is set only 2 value i.e., threshold and definite time, it should be called as 50G not 51G Unless you select IDMT Characteristic e.g., NINV, VINV or EINV Normal/Very/Extremely Inverse respectively and set time multiplier this will be 51G
@Mukhaizna
@Mukhaizna Жыл бұрын
great video, thanks for sharing. might be a good idea to include the motor inertia, mechanical load details, run a simulation using Digsilent power factory , and see the performance of the protection setting under various operating scenarios.
@shihabahmedalkatrani3050
@shihabahmedalkatrani3050 Жыл бұрын
Thanks 🙏
@pinoymaster1067
@pinoymaster1067 Жыл бұрын
nice video tutorial sir
@aliamoor1541
@aliamoor1541 Жыл бұрын
Thanks a lot for this great video but how we set IDMT RELAY I mean 51relay second stage
@juliussalutan8006
@juliussalutan8006 Жыл бұрын
IDMT relay second stage is not being envisage for MV motor feeder relay
@ImranKhan-nu6xw
@ImranKhan-nu6xw 2 жыл бұрын
Thanks for sharing the valuable information Kindly prepare a vedio on radial feeder setting for distribution system of load 7000kva, full load current 400 amp ,bus voltage 11kv ,CT ratio 400/5 ,low settings,high setting i.e I>,I>>& I>>>
@juliussalutan8006
@juliussalutan8006 Жыл бұрын
I'll consider your request on my future videos, welcome
@rjleal
@rjleal 2 жыл бұрын
Hello, great video. Where did you get the settings that you show here? For example, the 80% of the short circuit current? Is there any standard for this? Thank you
@juliussalutan8006
@juliussalutan8006 Жыл бұрын
I think for the 80%, it is related to the setting of undervoltage relay. For industry practice, undervoltage relay setting is being set between 70 % to 80% of the nominal voltage
@yassineallouche9844
@yassineallouche9844 14 күн бұрын
And for Time of 70% WE Can let 3sec??​@@juliussalutan8006
@reyyanez6705
@reyyanez6705 2 жыл бұрын
Sir, yung SONDE temperature protection, Anong temperature element po gamit nun same lang po ba sa RTD Pt.?
@juliussalutan8006
@juliussalutan8006 Жыл бұрын
Yes sir, RTD PT100
Protection Relay Setting Calculation for Transformer Feeder Relays
20:49
IDMT Relay setting calculation|TIME GRADATION|RELAY CO-ORDINATION
14:05
ELECTRICAL TECHNOLOGY and INDUSTRIAL PRACTICE
Рет қаралды 38 М.
How I Did The SELF BENDING Spoon 😱🥄 #shorts
00:19
Wian
Рет қаралды 35 МЛН
Calculating Motor Overloads
7:55
schulerruler
Рет қаралды 65 М.
These Illusions Fool Almost Everyone
24:55
Veritasium
Рет қаралды 2,1 МЛН
Motor Starting and Motor Protection
10:49
Eaton
Рет қаралды 24 М.
Relay Coordination Study Using ETAP | Part 1
40:11
Julius Salutan
Рет қаралды 19 М.
HVAC vs HVDC | What is the difference | TheElectricalGuy
14:34
Gaurav J - TheElectricalGuy
Рет қаралды 39 М.
Cable Sizing Using ETAP
23:56
Julius Salutan
Рет қаралды 7 М.