This video references Machine Safety Standard EN 60204-1, which is a European Standard. There are many wiring color schemes in use around the world. The video shows one implementation (EN 60445). Whenever designing or troubleshooting inside a panel, it is imperative to review the documentation, including wiring diagrams, to identify the various circuits in the panel. In the US, NFPA (NEC) and UL508A are the corresponding standards. In those standards, using orange and white/orange is in both the NFPA 79 and UL 508A for components that remain energized when panel power is disconnected, regardless of potential.
@mwautomatic5 жыл бұрын
FYI, for anyone looking from the US, this is not a standard for controls in the US.
@insylem5 жыл бұрын
Thanks I'm in the US and I just started a new job building panels and we have different colors
@eugenecbell5 жыл бұрын
m wilson thanks, I’ve been designing, building and troubleshooting industrial control systems in the US and have never seen this standard. They had my heart racing for a minute.
@andydelle45095 жыл бұрын
Yes I was going to ask that. Just doesn't seem right based on USA electrical color codes. Also black is both AC hot and DC+? Isn't that a disaster waiting to happen?
@seminolefantodd47365 жыл бұрын
Plus, to meet arc flash requirement, the outlet and programming port(s) must be accessible without opening the cabinet's door(s). Graceport and Automation Direct offer the components necessary to meet this requirement.
@kccryptkeeper48745 жыл бұрын
In the Automotive world for years it is: Black: 480v high voltage, motor power Red: 120v control power Blue: Low voltage DC power and control (24VDC) Yellow: Interlock power from a separate panel source. Green: Ground
@colincampbell52075 жыл бұрын
Your videos are awesome, the only caution I would mention in regards to this one is that many facilities have different standards for wiring. I work in a pulp mill that is 60 years old. The mill upgraded various systems and there is still PLC 5 in over half the mill. In Canada we have to follow the Canadian Electrical Code and work within that code to create a mill standard as well.
@realpars5 жыл бұрын
Hi Colin, Thanks for sharing your feedback and knowledge with us. You are certainly right, I will forward this to our creator team, to keep in this in mind for future video courses. Thanks again for sharing!
@PowerHaus3045 жыл бұрын
As an industrial electrician who works on these panels all over the world. There is no such thing as a standard - even in Europe! For context my last company wired everything in orange I have never seen two panels the same- not even close.
@darbybrooks66094 жыл бұрын
"Standard" is of it's country of origin . As I have worked on many foreign Control Cabinets, many from Germany, I must add decals to inform other's of the Changes in Wiring because the unit is of another origin and Color Identification is not STANDARD to the USA and must follow the manufactures identification.
@jasonakery34303 жыл бұрын
This is correct. Seen engineers pick their favorite colors. What code?
@MiniPeugot5 жыл бұрын
Don't believe this is how every cabinet is wired. Always read the elementary drawings.
@practicasindustriales41685 жыл бұрын
But usually it should be like it , SHOULD BE ,any way think that every wire is energized even u had cut the energy off ,just think like that
@Manos-de-Piedra5 жыл бұрын
Exactly Justin, Just because this panel is wired like this does not mean every other one is. Very misleading video description
@MR-nl8xr5 жыл бұрын
@@practicasindustriales4168 it's your type of mentallity that cripples the industry. Turning small risks into catstrophic nightmares which creates thousands of laws and rules to detain work. Double, tripple, quadrupple check everything and then you don't need to brainwash yourself that "everything is on". A powerwand and repeated checking have saved me from danger more than your idea.
@happymark18055 жыл бұрын
I never used orange for internal lights, so this vid is a load of BS, the person who orders als can say what kind of colors he wants, usualy it is up to us who makes it but in 30+ years I NEVER used orange for internal lights
@sstorholm5 жыл бұрын
Never seen one with that colour scheme here in Finland, everything is usually wired with black conductors. :)
@messagetous5 жыл бұрын
A lot are. I had to reroute several wires in a cabinet that were run in front of the strip. When I threw the main power, I found the wires I was working with were live. It was only 24V so I black taped the tips and ran them through. Also, several contacts and other electrical/electronic, almost half the panel, were still live. I asked around and no one knew. Thanks RealPars.
@realpars5 жыл бұрын
Great to hear that our course video cleared the issue up for you, Keith! Thanks for sharing that with us. Feel free to reach out if you ever have any questions!
@finnna83525 жыл бұрын
This wiring method must be company specific or country specific. Any cabinet that has power that cant be shut off has to have labeling on the outside telling anyone that shutting off the disconnect will not kill all power in that cabinet.
@Tavle5 жыл бұрын
Finn NA are you sure the labling have to be outside or Can it be inside the panel around the supply disconnector?
@realpars5 жыл бұрын
Correct, if there is an electrical feed to a panel that cannot be disconnect at the panel, an exterior label should be provided indicating where the remote circuit is and where it can be shut off. Both NEC and IEC have guidance on how this information should be displayed.
@Tavle5 жыл бұрын
RealPars Do you have a link to that IEC guide for labling?
@jesusortiz68425 жыл бұрын
Cabinet and electrical panel are restricted, only technicians and authorized personal.
@realpars5 жыл бұрын
@@Tavle IEC 61439
@danieltracy55595 жыл бұрын
I am an industrial automation engineer and I don’t think I have ever seen this standard followed by any integrator. I wouldn’t trust it, always use a diagram if you have one, or check it out yourself.
@AJOTSHAJU5 жыл бұрын
Correct
@realpars5 жыл бұрын
As with any electrical device, disconnect, test, and verify.
@MR-nl8xr5 жыл бұрын
👍🏼
@automate71285 жыл бұрын
Rule number one as an automation engineer: don't trust anyone including yourself :)
@scrappydogfinance84345 жыл бұрын
i AGREE, WITH THE ENGINEER WHO SAID HE NEVER SEEN THIS COLOR CODING STANDARD FOLLOWED ANYWHERE... IT CHANGES FROM JOB TO JOB... (USA) HOWEVER, I HAVE SEEN TYPICALLY BLACK IS AC L1 (HOT) AND WHITE IS TYPICALLY AC NEUTRAL AND GREEN OR GREEN YELLOW IS USUALLY GROUND OR BONDING CONDUCTOR... CLEAR INSULATION USUALLY USED FOR SHIELDING. BLACK AND WHITE ARE MOST COMMON FOR 24V DC POWERED CONTROL LOOPS FOR INSTRUMENTATION AND CONTROLS. TWISTED SHIELDED PAIRS ARE USUALLY OUTER SHEATH IS BLACK AND INNER FOIL LINKING MOST COMMONLY SEEN ARE LIGHT BLUE, GOLD AND SILVER FROM MY EXPERIENCE. ORANGE ON AC PER NEC CODE IS USUALLY INDICATING THE AC 3PHASE DELTA HIGH LEG OR (STINGER) WHICH IS USUALLY HIGHER VOLTAGE IN REFERENCE TO THE NEUTRAL GROUNDED CONDUCTOR ON A DELTA 3PHASE SYSTEM, HAS TO BE DISTINGUISED FROM THE OTHER PHASES WHICH ARE ONLY 120VOLT USUALLY TO NEUTRAL. MISWIRING THE ORANGE TAPED OR ORANGE PHASE CONDUCTOR OR NOT USING ORANGE CAN CAUSE DAMAGE TO ALOT OF 120VOLT EQUIPMENT. I HAVE SEEN ORANGE USED ALOT FOR DATA CABLES AND FIBER OPTIC PATCH CABLES... RED HAS BEEN SEEN FOR EITHER L1 AC OR 24VDC POSITIVE CONDUCTOR FOR DIGITAL INPUTS AND OUTPUT FIELD WIRING, ON PLC CABINETS, USUALLY BLACK AND WHITE FOR AC HOT AND NEUTRAL ENTERING CABINET AND LOCAL CABINET MOUNTED BREAKER, BUT AFTER BREAKER, CAN BE BLACK AND WHITE OR EVEN RED AND WHITE OR RED AND BLACK. AND BLUE IS OFTEN USED FOR THE DC POSITIVE INSIDE THE CABINETS. BUT FIELD WIRES FOR DISCRETE CONTROL LOOPS can be black and white or in multiconductor cables a whole array of colors.
@davidmaes32535 жыл бұрын
The wires going in and coming out of the main switch have the same name (L1, L2, L3). This is a major error as you may touch the wrong wires elsewhere in the panel after you THINK you disconnected them from the mains. Da's kei-gevaarlijk man!!
@realpars5 жыл бұрын
The main power feeds into a panel are called L1, L2, L3 and should be called this wherever they are distributed within the panel. That way, we know that there potentially is line voltage at the point in the panel. Often, we do add a prefix at a power distribution block to identify at the block where the power is being used, such as M101-L1, M101-L2, etc. Once the power feed lands at a device that can cut off or modify the line voltage, such as a transformer, VFD, or contactor, we change the label. For a contractor the wires coming in are L1, L2, L3 and the ones going to the motor are T1, T2, T3. Panels should be designed so that when the Mains switch is de-energized, all power inside the cabinet is also removed. In cases where it is not, labeling and other means should be employed to indicate live voltages may exist inside the panel even if the Mains is disconnected. Before working on any panel circuit, verify, verify, verify!
@rogergregory59813 жыл бұрын
@@realpars the guy is correct you should have different identification cable markers on the other side of the isolator, it's a device that can be open or closed just the same as a contactor or relay you even just said so yourself ,contradicted yourself , can't even get the basics right it would be great fun on a break down on you control gear
@scrappydogfinance84345 жыл бұрын
Wire numbering and tagging and matching wiring diagrams and schematics are most useful and should have a copy inside every cabinet in my opinion. But being able tor recognize the components inside the cabinet and understanding typical power flow and distribution in these control cabinets an experienced well trained technician or automation engineer will be able to identify most components and wire functions regardless of color... Also, use a a good voltmeter and non-contact voltage detector can be very useful in verifying voltage and function of wires in a cabinet also. Good wire and terminal tagging and consistent naming conventions really helps alot and should not be understated in helping workers identify wire functions and conventions being used. Effective Tagging can help a person quickly identify function and voltage type.
@realpars5 жыл бұрын
Thank you for the excellent comments on control panel design and maintenance. These are all good points. My #1 rule for panel design and maintenance, after safety, is complete and accurate drawings and documentation.
@tiredoldmechanic17915 жыл бұрын
It's interesting how differently various manufacturers and countries use wire colors, wire numbers and set up wiring schematics. Mobile equipment can be quite different from stationary equipment. It can be quite difficult working on equipment constructed in various countries and keeping the differences in mind. In the US, we change the wire number when it connects through a device when other systems will use the same number on a wire in a circuit no matter how many devices it goes through. It's only possible to tell what part of the circuit it's in by checking terminal numbers at each end.
@realpars5 жыл бұрын
Yes, there are many wiring color schemes in use around the world. The video shows one implementation (EN 60445). Whenever designing or troubleshooting inside a panel, it is imperative to review the documentation, including wiring diagrams, to identify the various circuits in the panel.
@MrWirebrain5 жыл бұрын
I have worked in control panels of CNC machines made from all around the world for over 40 years. This is just one variant of what I have seen. it is very common to have AC in a panel live with the main disconnect in the off position to provide lighting and programming power. Usually black wires are reserved for AC power. And most often you do see white for neutrals or black with a tracer. I think this often depends on where this machine is manufactured.
@realpars5 жыл бұрын
Thanks for sharing your knowledge with us, Joe! Great to hear that.
@lewishua40642 жыл бұрын
I think you must working at North America, because NFPA 79 defines neutral conductors may colored white 😁
@sebastiannielsen2 жыл бұрын
5:50 why would you use a contactor, if the switch is three-phase 5:30 ? Normally, you would either have a three-phase switch feeding the whole load, or a single-phase switch switching a 230v (in this case it would be L2+N if L1+N is used by the maintained supply, and L3+N if L1+N and L2+N is used by some loads - to keep the phases as balanced as possible) that goes to a three-phase isolation-certified contactor with 230v coil.
@realpars2 жыл бұрын
A contactor can -provide extra protections that the switch cannot, such as thermal and overload protection. The switch provides an external means to de-energize the circuit while the contactor provides a more robust way to provide circuit protection in the cabinet. Other factors would include local code requirements and company engineering standards, both of which are not known to the viewer of the video.
@lhr17015 жыл бұрын
On all the machines I have worked on when the main panel switch is turned off the panel no longer has power period . To best of my memory I don't recall any using a for lack of a better term remote disconnect like the one shown . They all had a handle on the outside of the door that had a metal rod to engage the main disconnect when the door is closed . To open the door while the panel is energized you had to override( with a small pin ) that to release the metal rod from the disconnect .
@baconsledge5 жыл бұрын
Keep ‘em coming, RealPars!
@realpars5 жыл бұрын
Thank you, Bob!
@sinankrikor74363 жыл бұрын
I am a Control panel shop supervisor in USA the code is different , Red= 120AC Live , White = 120AC Neutral , Blue = 24VDC , 0VDC White with blue if PSU grounded and Blue with white if not grounded , Orange = 120VAC before disconnect , White with Orange = 120AC Neutral before disconnect , Blue with Orange = 24VDC before disconnect , Black=480VAC , Black with Orang=480VAC before disconnect , Green/Green with Yalow = Ground , Yalow = safety relay circuit .
@realpars3 жыл бұрын
Thanks for adding that, Sinan! Very helpful for engineers in the US.
@hobbes_is_real3 жыл бұрын
While your color code may be different, using orange and white/orange is in both the NFPA 79 and UL 508A as being for components that remain energized when panel power is disconnected, regardless of potential.
@amjadhelo35985 жыл бұрын
Every week i stay excited to the new video Thank you for yours effort Thank you realpars My best channel I hope the weekly video be long time ❤️
@realpars5 жыл бұрын
That is great to hear! Thanks for your continues support! Happy learning!
@alicheraitia51463 жыл бұрын
Love ya all ,more vids please ,we are in need ,thank you for all best.
@akylbek_berikuly_945 жыл бұрын
I love this chanel! 👍
@realpars5 жыл бұрын
We appreciate that! Thanks for your support.
@zenebehagos35375 жыл бұрын
it is very important lecture more than a physical practice, keep sharing of like these lectures,thanks a lot
@realpars5 жыл бұрын
Thanks for your support!
@Liteg03 жыл бұрын
Every cabinet from different manufactures I've come across use their own coloring code. In the cabinets I design I use orange wires for externally powered control circuits.
@jester-lester8 ай бұрын
I'm confused! @3:45 in t he diagram shown, it states that single cores should be wired in Blue for AC Neutral but the neutral to your fan is wired in ORANGE single core ...doesn't this contradict what it shows in the diagram?
@realpars8 ай бұрын
Thank you for your question, it's a great one! Depending on where you are, electrical standards can vary, so it's essential to follow your local safety codes. Typically, the ORANGE wire is considered foreign wiring in many places. It might carry power from an external or internal source unrelated to the main power switch, so it's crucial to handle it with extreme caution. Even when you switch off the main power, these wires might still carry electricity. Most industrialized countries recognize this standard. The other wire cores you mentioned are controlled by the main on/off switch. We design it this way to ensure that certain devices like fans remain operational even when the main power is off. These ORANGE wires usually have their breaker switch separate from the main one. I hope this explanation clarifies things for you! Happy learning, and if you have more questions, feel free to ask!
@БекетТаниев5 жыл бұрын
Great! Keep going. I will recomend this channel for collegues and students.
@realpars5 жыл бұрын
That is amazing! We are very happy to hear that. Thanks for sharing!
@babupolymer16494 жыл бұрын
Excellent voice n vocabulary, I am finding interesting to learn more
@realpars4 жыл бұрын
Thank you!
@dougm26815 жыл бұрын
Must be "EU" color codes
@MR-nl8xr5 жыл бұрын
I was about to say.
@Anthony-bu5ur4 жыл бұрын
doug m Nope. Not sure where they get half their info from
@10_01-l4c4 жыл бұрын
The machine safety standard EN60294-1 EN being a European standard BS being a British standard ISO being an international standard And I believe UL is the USA standard (underwriters Laboratories)
@arttu43133 жыл бұрын
@@Anthony-bu5ur it is though
@richardclark85203 жыл бұрын
Not a standard in the US. Orange is used for 24 VAC . But has been used to signify voltage from a source outside the panel not controlled by the main disconnect on the panel. Yellow is more common for this purpose . And a purple wire used as a jumper wire in a circuit that may be used as a place holder for future input devices.
@realpars3 жыл бұрын
Richard, thank you for your comment. There are a number of wiring "standards? so whenever inspecting a pane\l, it is best to refer to the lead sheets of the panel drawings to understand how the wiring colors are used.
@derina.maleek94085 жыл бұрын
First time I heard about orange wires Thanks realpars
@2312-p3b5 жыл бұрын
And you'l likely only ever see them in their panel. Seen my share of them and never came across that.
@hobbes_is_real3 жыл бұрын
@@2312-p3b Or any other panel designed using the NFPA 79 standard, since that's where this comes from.
@garbo89623 жыл бұрын
In the USA never heard of an orange wire specifying anything but the B O Y color coding of 480 volt 3 phase. B O Y = blue orange yellow. A yellow wire was also for a wire that was still energized when disconnect switch is off. Was a sparky at a large newspaper. Was told to find out where the 120 volt yellow wire that went thru 14 press units feed from. Turned off over 500 circuit breakers and a lot of 480 volt breakers over several hours but never located feed. Prayed that fuse or breaker that supplied it never blow or tripped on my shift.
@realpars3 жыл бұрын
Hi Izzy, Thanks for your comment! You are right, we have added the following disclaimer to this video: This video references Machine Safety Standard EN 60204-1, which is a European Standard. There are many wiring color schemes in use around the world. The video shows one implementation (EN 60445). Whenever designing or troubleshooting inside a panel, it is imperative to review the documentation, including wiring diagrams, to identify the various circuits in the panel. In the US, NFPA (NEC) and UL508A are the corresponding standards. In those standards, using orange and white/orange is in both the NFPA 79 and UL 508A for components that remain energized when panel power is disconnected, regardless of potential. Thanks for sharing and clarifying that as well!
@myanmar80445 жыл бұрын
Thank for your VIDEO GOD BLESSED YOU ALL
@realpars5 жыл бұрын
Happy learning!
@mnada724 жыл бұрын
Simply put, the brown wire is live even if the main switch is off , is that it ? According to 3:47 the neutral should be blue but in 4:00 I see that orange is also implemented as neutral !
@realpars4 жыл бұрын
I see two different neutral schemes as explained at 3:47; Orange and blue. At 5:12, we see orange being used for a 1-phase circuit (light in the panel) for both H and N. At 5:30, we see blue as being used for neural in the 3-phase circuit. I do not see brown wires at 4:00. Perhaps the orange wires appear brown on your computer.
@mnada724 жыл бұрын
@@realpars I am sorry I meant Orange , at 4:00 orange wire for neutral
@e.muniappanelumalai12783 жыл бұрын
Thank you very much for your Valuable information.
@realpars3 жыл бұрын
You are most welcome!
@johnlansing29025 жыл бұрын
Thank you for helping people to learn real world issues In automation control
@realpars5 жыл бұрын
You are very welcome, John! Thanks for your support.
@jayt.42835 жыл бұрын
Unfortunately this is not the color coding for panels built in the US/according to NFPA79. Useful for control cabinets brought in from elsewhere though (I just installed a few)
@fischb225 жыл бұрын
keep in mind nfpa79 is not law. but yeah none of the stuff in the video is US
@jayt.42835 жыл бұрын
@@fischb22 sure, but UL standard does share many similarities and even makes direct calls to NFPA documents, including following NFPA79
@sumilidero5 жыл бұрын
Yes it is EN(glish) standard for European Union; not for USA :p
@hobbes_is_real3 жыл бұрын
What are you talking about? This is specifically from the NFPA 79, 13.2.4.1 unless they've updated it and took that out since 2007.
@vedatatakul27503 жыл бұрын
5:24 Why is the color of the input wires of the main switch not orange?
@realpars3 жыл бұрын
The wires to and from the door switch are connected to a contactor which is used to disconnect the incoming power. Generally, the main feed to the panel will use orange wires so that it is very clear that this circuit is the incoming power feed. Subcircuits are typically color-coded based on type of voltage (AC or DC).
@erdingtown5 жыл бұрын
in europe is brown for load and blue for neutral.
@AndreasDelleske5 жыл бұрын
erdingtown Germany: Brown, grey, black for the phases L1 to L3, blue MUST be N, green yellow MUST be PE. For me, yellow or orange could be foreign potential. Red can be anything.
@philippesoares17455 жыл бұрын
@@AndreasDelleske same standards in France.
@mizz14145 жыл бұрын
@@philippesoares1745 Same in every EU Country really, because thats what Norms are for... Switzerland also has the same ones...
@erlwindegans39545 жыл бұрын
Same in the UK. Brown Black Grey for 3-phase is a standard. Never seen 3x black
@septicsid84385 жыл бұрын
@@erlwindegans3954 I Often do 3ph as black, the current one for Australia is all black
@dasy2k15 жыл бұрын
Even then the colour code is not universal. We would tend to use brown for L1 Black for L2 grey for L3 Blue for N Gn/Ye for earths Red for DC+ (annoyingly DC- is often Black same as L2! I)
@MottyGlix5 жыл бұрын
The use of brown-black-gray for phases, and blue for neutral (and green/yellow for ground) is the standard for common mains wiring. Is it the standard in control panels?
@rogergregory59813 жыл бұрын
@@MottyGlix brown black grey or all black is what I've been using since thay introduced brown black grey and I've never seen a three core +earth in orange for 415 v ...maybe orange used for high voltage
@johnclarke29975 жыл бұрын
Worked on a old 1970s built control panel this morning which had white wire only and only method of ident was the numbering at each end of the wire. Doubt it will ever get rewired - no interest or budget to do so.
@alikhanzulkashov44385 жыл бұрын
Just before watching the video, I want to give my guess very quick. I think orange wire is used for ESD, while purple one is designated for F&G system. Now it is time to find out what it really means)
@groundfaultbob5 жыл бұрын
What do you mean by a neutral wire where Europe ha a 220 volt single phase system and a 380 V 3 phase system. A thee phase Delta system would = 1/2 of 380= 190V and a 380v Y four wire=219V. Is theat what you're referring as the neutral?
@joncurtis1995 жыл бұрын
The phase to earth/neutral of a 380V 3ph system is 380/sqrt(3) = 220V. The neutral (4th wire) would go back to the start point somewhere upstream.
@groundfaultbob5 жыл бұрын
@@joncurtis199 What you mean that the system (380v) is a 4 wire Y grounded system. That's the only way to get 220 volts from the utility side of the equation.
@Tavle5 жыл бұрын
Robert Ulrich Grounding in Europe is different from US. We have TT, TN and IT-net (search for it) Normal voltage is 3x400/230VAC for TT and TN-net and it consist of 5 or 4 wires(IT are most for marine and off-shore normal without N). L1, L2, L3(phases) N(grounding point in the HV/LV transformer on the LV side star point) PE (Ground) or PEN (combined PE and N) 3x400: L1-L2=400V, L1-L3=400V, L3-L2=400V 3x230V: L1-N=230V, L2-N=230V, L3-N=230V
@realpars5 жыл бұрын
You will use a neutral in a 3-phase system only when you intend to use each phase separately for loads, like in a Y-grounded system (see Robert Ulrich's comment below). The neutral (4th wire) prevents one phase from "feeding over" to another phase.
@sabercruiser.70533 жыл бұрын
keep up the mighty work u are doing thnx.
@realpars3 жыл бұрын
Much appreciated!
@nimabakhshi82023 жыл бұрын
Hey RealPars, in this example why do you need the contactor? The entire 3-phase is switched on/off with the external disconnect. Is there any other incoming power supply you are controlling with the contactor?
@realpars3 жыл бұрын
To be honest, we could have left the contactor out of the design. The contactor allows the distribution of power to multiple subcircuits. The contactor as shown also has advanced protection features that a simple disconnect switch does not have (internal overloads, for example).
@nimabakhshi82023 жыл бұрын
@@realpars Thank you! And the contactor does not need circuit breaker protection, right? In the video I don't think it is not installed downstream of a branch circuit C.B.
@Sunpixelvideo5 жыл бұрын
Let's face it. If you don't open the mcc feeding the panel, you're gonna have live voltages somewhere in there. In the US, so many things are different from what in the panel here. We'd probably be feeding Delta instead of Star/Wye. Neutrals would be grounded at the control transformer and colored white. Blue is only DC+ and DC- is blue with white or just white or even just more blue.
@realpars5 жыл бұрын
Thank you for your comment. There are quite a few differences how panels are constructed around the world, and it is always important to understand the codes and standards for those areas. In the US, we receive many panels from Europe with machines built in Germany or Italy. While the wire colors may be different and the types of devices may not be what we are used to, the accompanying drawings, BOM's and installation manuals allow us to install and startup these panels safely. We may add lock-out points, arc flash stickers, and other items to adhere to local codes and standards.
@MR-nl8xr5 жыл бұрын
Not all panels are feed from MCCs.
@Sunpixelvideo5 жыл бұрын
Not all panels are free from an mcc, sure. If you can point that out, you know enough to understand what my point was. Turn off the power upstream of the panel. It's a KZbin comment, so not always well researched and proof read.
@tombrewsaugh13995 жыл бұрын
Never opened a control cabinet to find a blue wire used as a neutral. Exactly why would you use orange for both your hit feed and neutral at anytime? Seems to me a good way to mess things up. Once had a co worker rewire a control panel with all red wire only thing he had in his truck. Didn't even use wire markers for identification. Took 2 guys 2 days two days to correct.
@realpars5 жыл бұрын
There are many wiring color schemes in use around the world. The video shows one implementation (EN 60445). Whenever designing or troubleshooting inside a panel, it is imperative to review the documentation, including wiring diagrams, to identify the various circuits in the panel.
@normanlevasseur65655 жыл бұрын
This is European code not American standard
@kubeek5 жыл бұрын
oh really? What tipped you off?
@claudehebert31315 жыл бұрын
@@kubeek For starters the european (CEE 7/4?) power receptacle :-)
@normanlevasseur65655 жыл бұрын
Just trying to inform all the inexperienced that may watch this video. Don't be a smart ...
@kubeek5 жыл бұрын
@@normanlevasseur6565 I dont know what inexperieneced people watch this video, but when he clearly says at 1:55 that it is according to European Norm 60204-1, are you really suprisied that he is not talking about united states of america specific norms?
@normanlevasseur65655 жыл бұрын
@@kubeek no need to be so smug
@karlmorzy59593 жыл бұрын
Yellow usually indicates outside wiring from Another disconnect source If in America I’d assume Orange means high leg or hot ???
@realpars3 жыл бұрын
Hi Karl, You are right, this video references Machine Safety Standard EN 60204-1, which is a European Standard. There are many wiring color schemes in use around the world. The video shows one implementation (EN 60445). Whenever designing or troubleshooting inside a panel, it is imperative to review the documentation, including wiring diagrams, to identify the various circuits in the panel. In the US, NFPA (NEC) and UL508A are the corresponding standards. In those standards, using orange and white/orange is in both the NFPA 79 and UL 508A for components that remain energized when panel power is disconnected, regardless of potential. Thanks for mentioning that!
@kusanagiigami5 жыл бұрын
i studdied this color code bfore at university & forgot abt,tnx for rmindin & clearifyin
@travonmiller52795 жыл бұрын
You'll forget it again when you start working because in reality they use whatever color is handy to get along. I was taught to not even trust the diagram, if there's any chance the wire has a dangerous voltage, test it yourself before working period
@oldtimer21923 жыл бұрын
Doesn’t look like spelling was a big requirement at uni does it?
@georgecobena74145 жыл бұрын
What is the correct color for 0VDC?
@realpars5 жыл бұрын
In the scheme of this video, ground/earth/24VDC Common would be Yellow/Green.
@RuudKuin Жыл бұрын
@realpars Maybe a clip on explaining/comparing UL and CE certification
@ahmedessam32805 жыл бұрын
Thx 4 for efforts and plz keep going.
@realpars5 жыл бұрын
You are very welcome, Ahmed! Happy learning!
@fethilakhdari10785 жыл бұрын
Thanks for the good information, although I am a bit puzzled by this choice of colors as Black is used for both power AC phase and power DC+ and in Control both AC phase and Neutral are Red. making it "Not Very easy to tell one from the other". In my old ANSI color coding post WW2 I can easily tell AC from DC and Phase 1, 2, and 3 in three phase system. What do we gain in the new color coding? Thanks for any comment you might have to help.Best regards,
@realpars5 жыл бұрын
There are many wiring color schemes in use around the world. The video shows one implementation (EN 60445). Whenever designing or troubleshooting inside a panel, it is imperative to review the documentation, including wiring diagrams, to identify the various circuits in the panel.
@MrAzizsasuke5 жыл бұрын
Good job and thanks a lot for this video
@realpars5 жыл бұрын
You are very welcome, Aziz!
@makedapalmer75134 жыл бұрын
Great videos. Can you explain the operation of UPS. Thanks
thanks a lot, good work, question please, why you didn't give the power to the panel through the main switch directly, why you used contactor in the way ?
@realpars5 жыл бұрын
At 5:52 in the video, the main switch is shown. What is not shown is the main power feed connected to the main switch. Some designers prefer to use a contactor with overloads instead of fused main disconnect blocks for space and maintenance purposes. What I don't see is an external lock out on the main switch, but I am sure it has one, or there will be a nearby disconnect/lockout.
@MohamedAtef-wm8hu5 жыл бұрын
@@realpars thanks for the reply, but what is responsible for short circuit protection? I think the motor circuit breaker gv2 is responsible for the overload and short circuit protection
@sumilidero5 жыл бұрын
yeah thats weird, main switch should kill the incoming power directly, not via contactor
@davecc00005 жыл бұрын
As stated elsewhere in the comments, these wire colors are not standard in USA or EU. So in which country(ies) are these colors used?
@realpars5 жыл бұрын
These colors follow IEC EN 60402-1, as stated in the video. This is the Machine Safety Standard for the EU.
@hobbes_is_real3 жыл бұрын
The orange color for power coming from a different source is in NFPA 79 and UL 508A.
@Ryarios5 жыл бұрын
Due to the laws that require special clothing and have specially trained personnel work inside a live panel, most of our customers require all outside voltages over 24 VDC terminate in a separate panel from the controls. This simplifies things when electricians need to enter the cabinet to do their work. Especially when the electrician is from an outside vendor.
@stephengriffin57425 жыл бұрын
Where does the orange wires get a feed when the main supply is turned off
@Tavle5 жыл бұрын
Ryarios are you from UK?
@Ryarios5 жыл бұрын
Dan Jensen no, the US.
@Ryarios5 жыл бұрын
Stephen Griffin it’s called "foreign voltages". It can come from lots of sources including devices sending or receiving signals to/from the panel in question. It also may just be the power that feeds the panel.
@sumilidero5 жыл бұрын
So, average electrician can't work in live panel in US? little trust you have in your staff :p
@habebsabri42885 жыл бұрын
Thank you for this explanation But if you devote an episode on how to read the control diagram
@realpars5 жыл бұрын
Hey Habeb! Thanks for your comment and your suggestion. I will pass this on to our course developers! Thanks for sharing and happy learning!
@habebsabri42885 жыл бұрын
@@realpars thank you
@fernandlust5322 жыл бұрын
I always look at the first pages of the schematics. Normally the color coding is explained somewhere there. Safer than trust whatever EN- or ISO-
@ThuanAutomation4 жыл бұрын
Thank you so much. share very helpful
@realpars4 жыл бұрын
You are very welcome!
@bolaheya62205 жыл бұрын
Hey I have a question about the subscription for one month does it allow to me to watch all the library without limitation cause I have a small experience about the plcs of siemens I don't wanna start from 0 I saw some of your videos it is amazing but some they covered a lot that I am already know so can choose what i want from the library and watch it or maybe download it to see offline
@realpars5 жыл бұрын
Hi Boulayeha, Thanks for your comment! Great to hear that you are interested in joining the RealPars family! As a paid subscriber you obtain full access to our complete course library. There will surely be no limitations. Regarding your previous experience with PLC's, I would suggest having a browse around our course library to see which topics we cover at the moment. bit.ly/30ZrxWq Also, you are definitely able to download our course videos for offline use. The following link is a step to step guide on how to do so bit.ly/2OK5eiF. Hopefully, this answer your question sufficiently. If you have any other questions or would like any further assistance, feel free to reach back out or email us at hello@realpars.com Happy learning!
@bolaheya62205 жыл бұрын
@@realpars great support thank you
@Crifstar5 жыл бұрын
I'm curious as to what country this is standard cause whoever built our plant didn't follow this in the US
@generation-x4065 жыл бұрын
EU not US
@realpars5 жыл бұрын
I believe this panel was built in the EU according to IEC standards.
@mahmoudreda84815 жыл бұрын
Hello thank you for excellent explaining. i tried to enter on the courses in website but it not work, what's the problem.
@realpars5 жыл бұрын
Hi Mahmoud, Thanks for your comment! I am sorry to hear that you are experiencing issues registering for our RealPars Course Library. Have you tried signing up through this link? bit.ly/30AVJaR If these issues continue to happen, please email us at support@realpars.com with a brief description of the type of error you are receiving. Hopefully, we are able to sort this out for you quickly!
@mahmoudreda84815 жыл бұрын
Thank you I will try and send you about the result
@miladinseratlic45655 жыл бұрын
in cabinets of machines that I worked with orange was 230VAC but w/o voltage when power was cut off. Each cabinet should have it OWN elec. diagram
@clems69892 жыл бұрын
I dont know where you came up with that color coding. Because it isnt like that in the US..
@realpars2 жыл бұрын
You're correct, Clem's! We have the following RealPars comment pinned under this video where we clarify the US-EU color coding difference: "This video references Machine Safety Standard EN 60204-1, which is a European Standard. There are many wiring color schemes in use around the world. The video shows one implementation (EN 60445). Whenever designing or troubleshooting inside a panel, it is imperative to review the documentation, including wiring diagrams, to identify the various circuits in the panel. In the US, NFPA (NEC) and UL508A are the corresponding standards. In those standards, using orange and white/orange is in both the NFPA 79 and UL 508A for components that remain energized when panel power is disconnected, regardless of potential."
@Tavle5 жыл бұрын
Is it correct to mark supply terminals L1,L2,L3,N acc. To EN 60204-1?
@realpars5 жыл бұрын
Yes, but EN 60204-1 references the designations of supply terminals (L1, L2, L3, N, PE) in EN 60445.
@Tavle5 жыл бұрын
RealPars EN 60445 Annex A say that conductors are named L1,L2... But terminals are named U, V, W, N
@sumilidero5 жыл бұрын
@@Tavle UVW are motor/transformer terminals in practise
@Tavle5 жыл бұрын
sumilidero And the supply terminals for a machine acc. To EN 60204-1 and if there is more the one supply they are called U1, V1, W1,N1, U2, V2.....
@jackburnett28105 жыл бұрын
Thats just what I was missing...motiwation.
@willmitchell2553 жыл бұрын
🤣 orange vires
@azeemahammed86464 жыл бұрын
Include videos on relay connection and selection for plc
@realpars4 жыл бұрын
Hi Azeem! Thanks for your comment and your suggestion. I will pass this on to our course developers! Thanks for sharing and happy learning!
@danialanddorssa3 жыл бұрын
super informative
@realpars3 жыл бұрын
Glad you liked it!
@isonlynameleft5 жыл бұрын
Depends on the panel, NEVER trust convention!
@samisrour31294 жыл бұрын
Sure it is useful, thx lot for info
@realpars4 жыл бұрын
You are very welcome!
@abumomoh-sanni35895 жыл бұрын
If the main switch is then turned off, how and where does the "orange wire" get power?
@LL-xm4kw5 жыл бұрын
orange wire not connect to breaker or contactor
@realpars5 жыл бұрын
As indicated, but not fully explained in the video, the distribution block with the orange wires has a power source separate form the circuit controlled by the main switch.
@andyjohnson44855 жыл бұрын
Yes, very intense!
@llVIU3 жыл бұрын
I almost died watching this video, it should be marked 18+ only
@001prk5 жыл бұрын
pls make a video on Ground protection system of Local Control Panel
@realpars5 жыл бұрын
Hey Prakash! Thanks for your comment and your suggestion. I will pass this on to our course developers! Thanks for sharing and happy learning!
@KevinNguyen-tw5ml Жыл бұрын
Thank you very good !
@realpars Жыл бұрын
You're very welcome!
@johnmoses195 жыл бұрын
Please make more videos for us...thanks
@realpars4 жыл бұрын
Thanks for your support!
@shamialgawzi82775 жыл бұрын
Outstanding 👍
@realpars5 жыл бұрын
Thank you, Shami!
@aleksshutka94815 жыл бұрын
According to European standards it’s not allowed to run 3 phases to the door, isn’t it? As I know main disconnect switch should be installed on panel or cabinet internal surfaces.
@realpars5 жыл бұрын
The only requirements I am aware of are: 1) any electrical cables landing on devices in panel doors must be installed so that the cables are tension-free. 2) the panel door must be tied to ground, 3) there shall be no sharp edges on panel frames or doors, and 4) live parts must be protected against direct contact in accordance with DIN EN 50274 or VDE 0660-514.
@douggordon39063 жыл бұрын
NEMA is usually yellow. IEC is orange
@realpars3 жыл бұрын
That is correct for interlock wiring. It is always best to consult the panel drawings to determine the standard used for that panel. I have seen panels designed in the EU, built in Canada, and shipped to Japan. So what standard did the panel use? Well, you could pick one of three standards from what I told you above, like CSA or IEC, but you would be wrong. It was built to NEC standards. because the company in Japan was a US company and NEC was their international standard at all of their sites for panel construction.
@stevenmoomey21155 жыл бұрын
Like others have said, not in the United States. Something I would like to know, why didn’t you use Orange terminal blocks for your Orange wires. Yes, they are readily available.
@scottsommer78645 жыл бұрын
The video showed an example of a control panel that was ordered/purchased by a client. Orange terminal blocks are available and could have been specified for this panel, but were not in this case.
@hobbes_is_real3 жыл бұрын
If you're designing to NFPA 79, then yes this should definitely be true in the US.
@GOOGLEISVERYEVIL5 жыл бұрын
I am a control systems specialist aka automation engineer PLC/SLC programmer, certified UL panel designer and builder. I have been in the field for 15 years none of these colors they called out are correct. I follow the UL508A code. And they are very specific on color codes. And if I used blue for ac neutral I would get a big fat fine when my panel was inspected by the UL guy. Plus if you turn off the disconnect and ALL power is not removed I have to put a sticker on the outside of my enclosure next to the disconnect stating more that there is more than one source of power feeding the cabinet. Is this a different country?
@realpars5 жыл бұрын
This panel is not built to UL508A standards. It was built in the EU for an EU installation, following IEC EN 60204-1.
@GOOGLEISVERYEVIL5 жыл бұрын
@@realpars Did I miss the part where you explained this is for the EU.
@hobbes_is_real3 жыл бұрын
If you're using UL 508A and following their color code, you should be using either orange and white/orange or yellow and white/yellow for any conductors that remain energized when the main disconnect is switched off (check 66.9.1).
@legominimovieproductions5 жыл бұрын
If ac live and neutral are orange, how do i know which is which?
@tomthomasjohnpaulmooremawr30145 жыл бұрын
On french 230 Check between earth and live = 230 n'eut earth = 0v and if both you've got two phases 400v
@realpars5 жыл бұрын
There should be voltage (115 VAC, 230VAC) between the hot wire and ground. There should be zero volts between neutral and ground.
@legominimovieproductions5 жыл бұрын
Yes thats like its everywhere, but in germany we have briwn black and grey so you know which wire is the phase without testing and that you dont accidentally short live and neutral together
@zwartepanter115 жыл бұрын
@@realpars Dan denk ik dat je eens een nieuwe voltmeter moet kopen ! (morgen even de test doen, ipv draadjes volgens plan trekken in een kastje.) Tussen Fase en aarde is het altijd 230 Volt (in een 3x400 VAC-systeem), of je moet in een 3x220 VAC-systeem zitten, dat al heel oud is... Dit komt doordat de neutrale geleider aan de hoogspanningstrafo aan de aarde hangt (middenpunt van de 3 fasen). en bij een 3x220 VAC-Systeem is er geen middenpunt voor de neutrtale geleider. (of is het in Nederland dan toch weer heel anders dan in de rest van europa ?)
@tomthomasjohnpaulmooremawr30145 жыл бұрын
Understood by using Google translation. For me what you discribe is what i have but i hear thé new places have but Single phase.
@charliechimples5 жыл бұрын
Great vid. Thanks for sharing. 🐵
@realpars5 жыл бұрын
You are very welcome, Charlie!
@vitalikomissarov6154 жыл бұрын
very useful!
@realpars4 жыл бұрын
Great to hear that, Vitali!
@georgegeorge8994 жыл бұрын
In which country do you operate?
@realpars4 жыл бұрын
Hi George, Thanks for your comment! Our headquarters are based in Rotterdam, the Netherlands. But, we operate worldwide :). Happy learning!
@georgegeorge8994 жыл бұрын
@@realpars Nice! The same here in Germany. Keep up the good work ! 👍
@BrianSeklecki3 жыл бұрын
Hopefully US/CA will ditch old NEC color coding and adopt EN/EU/International standards soon.
@realpars3 жыл бұрын
It is a possibility, but there are too many organizations invested in the current standards and too many installed systems. Each standards organization has certain local power and influence, and it is unlikely that there will be a harmonious worldwide standard anytime soon.
@bharathpoojary15645 жыл бұрын
Nice video
@realpars5 жыл бұрын
Thank you!
@andrewhardcastle79825 жыл бұрын
That was very informative and useful thank you 😊
@realpars5 жыл бұрын
Great to hear that, Andrew! Thanks for sharing.
@mab93164 жыл бұрын
Thank you.
@realpars4 жыл бұрын
You're very welcome!
@septicsid84385 жыл бұрын
Realpars, where in EN60204-1 does it give a table of these colours please? I cannot find the above. All I can find is a recommendation to follow the colours from IEC60757. These colours are not required by any law and can only ever be a recommendation. In the main they are changed dependent upon customer requirements, country and/or whichever way the wind is blowing. Please backup your statements with some facts?
@realpars5 жыл бұрын
The color schema was moved to IEC/EN 60446 and then to DIN EN 60445.
@ahmadbasel55875 жыл бұрын
Thanks 👍
@realpars5 жыл бұрын
You are welcome, Ahmad!
@Cooliemasteroz5 жыл бұрын
It depends on which country you are in.
@khalidkamal29023 жыл бұрын
Could you make things more elaborated "explicit" could be benevolent.
@winner13382 жыл бұрын
Company that i work with use orange for UPS or generator.
@salemalsayed40335 жыл бұрын
Useful so much
@realpars5 жыл бұрын
Great to hear that, Salem!
@tommays565 жыл бұрын
Good as always But in buying a LOT of machines From EU county's from large builders with extensive saftey systems the orange is something not commonly done I believe it is because when the mains is locked out users want the panel in a zero voltage state
@realpars5 жыл бұрын
Thanks for sharing your thoughts and knowledge with us, Tom!
@stalinsubbiah32385 жыл бұрын
how to learn Programmable Logic Controller?
@realpars5 жыл бұрын
The best way is to subscribe to the video courses at Realpars.com. Learn the basics of PLC programming, then move on to more advanced topics, all at your own pace from your own computer.
@JoacimStenberg5 жыл бұрын
Where I live, and in my field of work, an orange wire is temporary.
@realpars5 жыл бұрын
This panel was built in the EU according to IEC standards. There are a number different standards that have been written for different situations (hazardous installations, general purpose, outdoor, etc.), different industries (mining, pharmaceutical, marine/subsea, etc.), and different geographies (US, Canada, EU, Japan, etc.)
@potssucculents3 жыл бұрын
New subscriber here
@realpars3 жыл бұрын
Glad to have you here!
@0073805 жыл бұрын
These colors on the control circuits don't follow NEC standard.
@Tavle5 жыл бұрын
Roger Smith No EN 60204-1 (Europe) and maybe IEC 60204-1 (most of the World). North America are very speciel with NEC, UL and CSA :)
@realpars5 жыл бұрын
Dan is absolutely right. The cable configurations/colors in the video are IEC standards.
@jahidmondol30725 жыл бұрын
Dear sir please make a new tutorial of hydraulic solenoid valve & type of solenoid valve
@realpars5 жыл бұрын
Hi Jahid, Thanks for your comment and your suggestion. I will pass this on to our course developers! Thanks for sharing and happy learning!
@berndeckenfels5 жыл бұрын
Those color standards are confusing as hell, why is that?
@realpars5 жыл бұрын
I once heard from a very wise engineer, who said, "the wonderful thing about standards is that there are so many to choose from." And this is a perfect case where too many standards can lead to confusion. Look at device networks: ProfiBus, Foundation Fieldbus, IOLink, Ethernet/IP, ASi, WorldFIP, BACNet, Modbus, etc. The shear number of available standards makes things confusing. This video addresses one of many, many standards for control panel wiring that pertains specifically to machine safety in the EU. Personally, I have not used this standard on a project, even with equipment supplied from EU countries. But I know it exists and understand that if I have a panel that follows it, that I will need to become familiar with the details of that standard. I do not know the history of why this color scheme was developed, but I am sure orange was used to set this standard apart from other panel standards.
@berndeckenfels5 жыл бұрын
RealPars yah ok, but why would + be black and no DC GND or -. Why not separate L and N and why have different colors based on the code types...
@garyschultz2533 жыл бұрын
Why are they screwing with the Color Code. A/C Neutral is white, DC + is Red, except when dealing with Data Centers, and Green Yellow is for Dedicated Isolated Ground in systems with high Harmonic Values.
@realpars3 жыл бұрын
Gary, the video references Machine Safety Standard EN 60204-1, which is a European Standard. In the US, NFPA (NEC) and UL508A are the standards, and in those standards, orange wires are addressed for exactly the same purpose as is shown in teeth video, except I do not see this employed in many cases. There are many wiring color schemes in use around the world. The video shows one implementation (EN 60445). Whenever designing or troubleshooting inside a panel, it is imperative to review the documentation, including wiring diagrams, to identify the various circuits in the panel.