Reducing Energy Consumption in a Large Home: A Step-by-Step Guide

  Рет қаралды 221,873

Urban Plumbers

Urban Plumbers

Күн бұрын

#vaillant #PDHW #costofliving
In this video, I show you how I convert a highly inefficient and oversized gas boiler system into what is called a weather-compensated Domestic Hot Water Priority system and save the owners of this house an absolute fortune in their heating bills.
This job involved:
- heat loss calculations (18.50kW) and new system design
- removal of one 24kW system boiler (not needed!)
- removal of one of 300L unvented cylinders (not needed, unless there is 15 of you!)
- rewiring of the system
- supply and installation of weather compensated controls - Vaillant Senso Comfort
- integration of existing controls (12 zones) into Vaillant Senso Comfort set up
- removal of low loss header and system pump (not needed!)
- improvements to hot water performance
All those changes should save this family up to 40% on their energy use.

Пікірлер: 446
@andrewmillwardwatford9410
@andrewmillwardwatford9410 Жыл бұрын
You have no hydraulic seperation for a system with ufh and radiators on low temperature controls. This will cause underflow in the ufh circuits when in operation. The llh needs to be refitted and a separate pump used for the radiator circuit from the distribution header. This is standard Vailant and Viessmann design. Hydraulic seperation has rules for when and when not it is required. This design you have done is subject of many of my design videos and causes regular winter call outs for me. It's very easy to rectify the issue. Ask Vilizar at Vailant to do a system schematic for you. This is as much of a hydronic no no as ccts at the ufh manifold.
@UrbanPlumbers
@UrbanPlumbers Жыл бұрын
Well, we do disagree here. I’d rather have CCT on manifolds than LLH here. If I have made a mistake I want to learn from it and go back and rectify. I appreciate your experience but I would like to test it myself and go back if needed. I have seen the discussion with you and Adam re CCT and I am aware of it. I will report back
@andrewmillwardwatford9410
@andrewmillwardwatford9410 Жыл бұрын
@@UrbanPlumbers it can all be proved mathematically with what you have learned from the heat geek course. I worry about credible sources giving out ideas with mistaken design principles. This leaves installers and customers vulnerable to system issues. Happy to discuss the issues with you.
@UrbanPlumbers
@UrbanPlumbers Жыл бұрын
@@andrewmillwardwatford9410 sure! I would love to meet and have it all explained!
@UrbanPlumbers
@UrbanPlumbers Жыл бұрын
How do I find your number mate?
@andrewmillwardwatford9410
@andrewmillwardwatford9410 Жыл бұрын
@@UrbanPlumbers I message you on messenger before
@avivscrewvalla
@avivscrewvalla Жыл бұрын
What is truly amazing is that Urban Plumbers took on such a massive job and did not force the client to buy a whole bunch of new equipment to solve their issue. Instead, he deleted inefficient kit, redesigned and rewired the system and invested only time. Syzmon is the highest caliber of professional! Well done!
@TheWebstaff
@TheWebstaff Жыл бұрын
I can't wait to see the update and note from Andrew. It was a bit of an experiment and lessons might have to be learnt. It's good to see people's working out though!
@ogi22
@ogi22 Жыл бұрын
Well, i have to agree that this is amazing and a great show of high class specialist. However if they had double what they needed, i would just leave those redundant parts as a spare. Such heater is not worth a couple pennies... I have a similar sityation at my home - exchanging coal heating for gas. And i still want to leave old stove just in case, work on it a little and have an emergency heat source able to use coal, wood, chips, pellet... Hard times are coming and relying only on one source of energy is very risky.
@edc1569
@edc1569 Жыл бұрын
Breath of fresh air, so tiring seeing trades just scrap perfectly serviceable equipment, incredibly wasteful.
@chriswev
@chriswev Жыл бұрын
Never met a plumber/ heating guy with half the knowledge, and ability of this guy, unreal 👍
@microcolonel
@microcolonel Жыл бұрын
Finally a heating plumber who puts into his job more thought than I put into my hobbies.
@billmarsh1971
@billmarsh1971 Жыл бұрын
With these levels of competency and professionalism you should be running the entire country. Absolutely fantastic Mr Urban
@UrbanPlumbers
@UrbanPlumbers Жыл бұрын
naaah - the current lot are doing great, aren't they? 😄
@nigelsears7191
@nigelsears7191 Жыл бұрын
raw talent and whats even better is you do really go above and beyond to try to make your customers systems as efficient as possible , well done Simon
@smithleon
@smithleon Жыл бұрын
Wow, what a difference. Plumbing and heating genius. As a DIY'er i'm in complete awe :)
@silvervanmanfly
@silvervanmanfly Жыл бұрын
As a plumber myself I am also in awe. A credit to the profession.
@Umski
@Umski Жыл бұрын
I would happily endorse your ability as a real engineer unlike many of the so-called gas/boiler fitters that like to think they are! Well done on a) taking on the job, b) being tenacious and knowledgeable enough to fault find it and c) resolve it without resorting to a ‘rip it out and start from scratch’ attitude 👍
@Umski
@Umski Жыл бұрын
@James Clerk Maxwell I have a Blue Peter badge 🤪
@billmarsh1971
@billmarsh1971 Жыл бұрын
@@Umski this is by far the most magnificent comeback I've ever seen on the internet, very well played!
@burropoco
@burropoco Жыл бұрын
Hopefully young apprentices are watching this channel and seeing a great example of what professionalism and skill looks like. It will certainly help them in their future careers.
@tonyb3629
@tonyb3629 Жыл бұрын
It seems you have to be as much an electrician, plumber and boiler engineer - all at the same time. This is a huge, complex job that could completely fry your brain. Hat's off to you.
@boomish69
@boomish69 Жыл бұрын
Love to see the original plumbers face who obviously thinks he’s the bees knees over designing such a complex system. Awesome job!
@fredflintstone1428
@fredflintstone1428 Жыл бұрын
I love your channel. Your style of presenting is really natural as opposed to some on KZbin. Your knowledge is excellent and your problem solving skills really creative. Well done.
@theamanbaby82
@theamanbaby82 Жыл бұрын
Brilliant video as always. As a heating engineer myself, I can appreciate what an amazing standard you work to 👌 Keep up the good work & keep the awesome vids coming 👍
@Flashg19811
@Flashg19811 Жыл бұрын
You are a master of your craft and I’m addicted to watching vids now about plumbing and heating…😂😂
@UrbanPlumbers
@UrbanPlumbers Жыл бұрын
👍
@Brian77766
@Brian77766 Жыл бұрын
You are a heating genius that can simplify overcomplex systems and remove all that's not needed leaving the heating system more efficient and the customer very pleased.
@justjacqueline2004
@justjacqueline2004 Жыл бұрын
I have not a clue but am fascinated by the skill of Mr Urban and his unique approach to home heating that really effects us now.
@gheorghiuvasile266
@gheorghiuvasile266 Жыл бұрын
We can summarize that in order to save a fortune on heating costs we should call a competent and knowledgeable plumber :D very good video I quite enjoyed it, thanks for sharing!
@davidbrotherson933
@davidbrotherson933 Жыл бұрын
Another great video of your work.. your depth of knowledge is incredible. I don't know how you learned all that but your customers are lucky to have such a top professional on the job.
@delilahlynch324
@delilahlynch324 Жыл бұрын
He's done the heat geek training course, best resource in the country
@otw5974
@otw5974 Жыл бұрын
Your work ethic is fantastic, as others have commented. Fine tuning and efficiency - simplifying and optimising powered by thought, not excess and compensation powered by laziness and incompetence. Re the softened water thing - base exchange softened water does indeed dissolve scale deposits, you're right. However when this occurs on a large build-up, sludge can form in lower-flowing areas, or restrictions, such as strainers, filters, and aerator fittings at the end of taps, so something to look out for in a situation like this. It can also dissolve 'cleanly' over time though and eventually pass through to drain without much issue.
@michaelhales501
@michaelhales501 Жыл бұрын
Your knowledge is incredible. You were certainly born to do this job!
@TomNook.
@TomNook. Жыл бұрын
You are an artist and this heating system is a work of art
@petehefferon8192
@petehefferon8192 Жыл бұрын
It’s mental how much knowledge you keep stored in your brain. Incredible
@xbullshet
@xbullshet Жыл бұрын
No idea or understanding , but it is amazing to see someone so professional and easy to understand, that he knows what he is doing and also, takes some risks to test himself. Thanks for your knowledge!
@wilteduk007
@wilteduk007 Жыл бұрын
It's a rarity to find someone so knowledgeable.
@willmorgan6867
@willmorgan6867 Жыл бұрын
Big respect, I'm a techie not a plumber but appreciated the erasure of stuff that wasn't adding anything valuable to the system. Goes to show that there's plenty of scope to reduce energy usage and waste. Please keep making more of these, and hope you aren't kidnapped :)
@wakayama1991
@wakayama1991 Жыл бұрын
really excellent video! Everything explained so a layperson like me can understand, delivered with humility and a sense of humour too! You sound like a true professional, not some blagging shyster (can you tell I've had a couple of those in the past?) Your customers are lucky to have you. Subscribed, and please keep the videos coming!
@MichaelPickles
@MichaelPickles Жыл бұрын
You should open that bottle of champagne to celebrate a job well done
@careykaeding4542
@careykaeding4542 Жыл бұрын
They hired you for a reason. Tons of houses out there like this. Keep up the good work
@UrbanPlumbers
@UrbanPlumbers Жыл бұрын
Thanks 👍
@john-qq4ym
@john-qq4ym Жыл бұрын
You're amazing, managing to sort out all that wiring. I was impressed with the condition of the hot water cylinders, no limescale at all. After seeing that I went and bought an industrial water softener to fill my 4,000 litre buffer tank. I'm planning on linking an annexe and have some insulated underground water pipe, it's 32mm so I'm going to thread 16mm through to get my flow rate correct. It's only a 10 mtr. run so I think it should be fine. I'm leaving the hot water on Economy 7 as long as my contract allows. I find with a properly insulated large tank there's very little loss over the day. Some people complain about heat loss from a store but what I've found is you have to make sure there's no parasitic convection going on. Another thing I don't think people realise is that their heat store isn't fully up to temperature to start with. I can see heat stores will be very useful when smart grid pricing comes along. John.
@johnsmith-ik8il
@johnsmith-ik8il Жыл бұрын
I watch these videos even though I have no idea what he's talking about. What a guy.
@stephengreen6338
@stephengreen6338 Жыл бұрын
And to think I had trouble wiring a Y plan, with cylinder, and room stat, you my friend are on a higher plain, enjoy the content, well done Simone
@Colin82ish
@Colin82ish Жыл бұрын
Wow, so many wiring centres, my mind is blown. What a superb job you've done there, most impressive!
@richardhalliday6469
@richardhalliday6469 Жыл бұрын
Chanced upon one of your videos, I was impressed by the content, presentation and professionalism - now a subscriber - excellent job my friend.
@kenbone4535
@kenbone4535 Жыл бұрын
I love wiring heating controls, looking to be working with you soon.
@Chris-js4yq
@Chris-js4yq Жыл бұрын
Fantastic really enjoyed this as a gas engineer thank you
@UrbanPlumbers
@UrbanPlumbers Жыл бұрын
Glad you enjoyed it
@asmerom3025
@asmerom3025 Жыл бұрын
Brilliant ! Mesmerising watching a true professional at work..
@ashplumb1
@ashplumb1 Жыл бұрын
You pal are a very clever chap. Mind is blown again
@thomassheridan4252
@thomassheridan4252 Жыл бұрын
Excellent video, don't think most electricians could have worked that out.
@spikespike9430
@spikespike9430 Жыл бұрын
Just found your channel and really impressed. You may still have a bit to learn but could be the time to ease of on the tools and make your fortune in consulting. ie How to do a proper job or correct what 'heating engineers ' have botched up and over charged on. ( only applies to some, you know who you are ) Your knowledge for your age far exceeds what an average guy knows and your videos and knowledge is truly inspirational. Well done and keep the videos coming.
@adobo6905
@adobo6905 Жыл бұрын
You are doing an excellent explanation with the limited time and complex installation that you have. You did not tell us if the boilers were set up to fire properly to maintain the needed space and hot water temp. You stated that energy consumption was high with not enough heating but you did not share your findings as to what caused the situation of the high energy bill. Good luck.
@MrMattlock
@MrMattlock Жыл бұрын
You didn't explain what you had to do to that wiring centre, but my head had exploded already by then! Why do installers make things so unnecessarily complicated? It's a lovely big house, but I've worked in 50 room hotels with simpler control systems! Well done for improving things so much for the client with minimum outlay.
@makgou9148
@makgou9148 Жыл бұрын
Simon strikes again. As always covers every detail as it should have been in the first place.
@lincslegend6936
@lincslegend6936 Жыл бұрын
Knowledge and skill off the scale. 👏
@SuperMcgenius
@SuperMcgenius Жыл бұрын
I like that you tried without knowing it would work. Glad it did, smart work.
@davejohnston5158
@davejohnston5158 Жыл бұрын
I have always thought commercial heating engineers have been lured by over complexity for technical one-upmanship. It appears that the clients budget usually determines the system size. In a house of this size I would expect a second boiler to be in position just to prevent inconvenient heat failure. I am amazed that all those zones work on one built-in boiler pump.
@Lee.Willcox
@Lee.Willcox Жыл бұрын
I love their choice in the heating system, I love how you have rationalised it all (BRILLIANT) and I really love their choice in paint 🤭 Farrow & Ball, they are superior producers of paint with a wonderful palette of rich colours (no I don't work for them). Such an daunting job you have taken on and you achieved it 😎
@stephen3654
@stephen3654 Жыл бұрын
They're not short, they can even afford Andrex.
@Lee.Willcox
@Lee.Willcox Жыл бұрын
​@@stephen3654 😄😆😅🤣I shop at LIDL and their bog roll chafes 😩 If only I could afford ALDI or ASDA bog paper, let alone Waitrose 😤😥
@stephen3654
@stephen3654 Жыл бұрын
@@Lee.Willcox I use my hand and rinse it in the flush
@dglcomputers1498
@dglcomputers1498 Жыл бұрын
I will say the Vailant/Gloworm ebus stuff is quite handy, we had a new glowworm compact fitted at the place we are renting and no controller or even a room thermostat was fitted (the previous boiler being an ultracom with the built in programmer). Absolute pain to turn the heating on/off so ended up getting a ClimaPro2. Installed in seconds using the plug under the boiler and so much easier than having to take the front cover off to wire something internally.
@k20aa
@k20aa Жыл бұрын
I love it when a plan comes together 👍👍👍
@schrodingerscat1863
@schrodingerscat1863 Жыл бұрын
Guarantee the original installer looked at the house and thought, they have plenty of money, then over-specified the original system massively to make it a much bigger job than actually needed. You could run the place as a hotel on that original system, 50kW, total overkill.
@waqasahmed939
@waqasahmed939 Жыл бұрын
I've got a 29KwH boiled when realistically, I need half that. My house theoretically uses 10,000 KwH of gas a year
@Bertie_Ahern
@Bertie_Ahern Жыл бұрын
Of course. Sad but true, it's only about money for most plumbers.
@samposton9101
@samposton9101 Жыл бұрын
Lovely work mate. What a massive difference that will make to their gas bills this year!
@UrbanPlumbers
@UrbanPlumbers Жыл бұрын
There is more to it than I was able to show on the video. They had 600L of stored water and never enough hot water - 2nd circulation was constantly depleting the cylinders with 2 x boilers constantly trying to recharge them! This should make a massive improvement to energy consumption
@samposton9101
@samposton9101 Жыл бұрын
@@UrbanPlumbers crazy!! I suppose that’s why the secondary return should be lagged so well to stop that. At the new gas price that’s over 2.5k per year in saving!!
@UrbanPlumbers
@UrbanPlumbers Жыл бұрын
@@samposton9101 yes, you can easily cost you that much with insane 600L and 50kW of boilers cycling all day
@singlendhot8628
@singlendhot8628 Жыл бұрын
@@UrbanPlumbers Reminds me of that mixing episode you did earlier in the year. Well done!
@psi10001
@psi10001 Жыл бұрын
I can't wait to see the results in a year!
@UrbanPlumbers
@UrbanPlumbers Жыл бұрын
I think I will go back in Jan 2023 once we have data for at least 2-3 colder months.
@VietecHeating
@VietecHeating Жыл бұрын
Not sure I agree with removing the LLH for such a system, however, real world testing is the best way to find out if it works, we can have all the theories we want and all the mathematical equations and all the manufacturers test rigs in test conditions, but these do not prove real working of an actual system, it’s great that you have a client willing to undergo a trial for a different approach and it will be very interesting to see how it turns out, I look forward to the follow up video with interest, it could prove a lot of theories wrong
@UrbanPlumbers
@UrbanPlumbers Жыл бұрын
yes, it would be nice to keep it in, but that would require re-piping of hot water and radiator circuits so that the take-off for DHW is before the header, additional 2 pumps - one for CH rads and one for DHW plus replacement of mixing valves on 2 manifolds. It may still happen. We will know soon.
@NickLaslett
@NickLaslett Жыл бұрын
Great explanation of the system and the changes you made.
@fastestmilkman3840
@fastestmilkman3840 Жыл бұрын
Amazing work, loved how you have worked everything out first and problem-solve - wish you are closer to us in (Bath) as it is a pain to find a good plumber to install a new boiler for us at the moment!
@andyhodchild8
@andyhodchild8 Жыл бұрын
Very good video, for 30 years I fit weather compensator, the old honeywell AQ6000 was a fab weather compensator controller with optimum on and optimum off. If HMG wanted to improve efficiency they could get rid of bimetallic stats, thermistors are so much better.
@pradhpatle
@pradhpatle Жыл бұрын
It will succeed 👍. Have no doubt about it. I hate low loss headers when they are not needed. If in doubt I would put small buffer with buffer sensors wired to vr 71 instead.
@mikeh6206
@mikeh6206 Жыл бұрын
I'm a Viessmann guy and have often used the boiler pump to handle full radiator loads but only when the pump is operating within its curve. The DHW 3 way valve is handled internally in the boiler so there is no question of having the wrong temp going to the tank. I can understand why the LLH is in place and if the DHW was sent to the tank bypassing the LLH, you would still have the benefit of the LLH for flow control through the secondary circuits.
@plumbertime
@plumbertime Жыл бұрын
Very nice job. Sadly too many surveyors only look at what you already have and quote rather than asking what you need and would like to achieve and then quote. Sadly too many unskilled people don’t know how to work out what’s required so so just do a like for like swap. There’s plenty of big well named companies fitting systems like it’s the 90’s! And sadly customers love it because the rads get hot.
@hogey74
@hogey74 Жыл бұрын
Great video thanks and salient in late 2022 in Europe. Also good seeing you discussing theory and practice in the comments.
@andyleggatt1846
@andyleggatt1846 Жыл бұрын
maybe you could see if vaillant will sponsor an Arotherm addition for the property next year! ;) would have been interesting to know more about the wiring, though I appreciate the brain frying nature of boiler wiring!
@steveeggleton876
@steveeggleton876 Жыл бұрын
Yes a softener will slowly remove existing scale build up in any water using system or appliance
@UrbanPlumbers
@UrbanPlumbers Жыл бұрын
I heard that before, but this is the first time I was actually able to confrim it!
@hansv.d.p.8679
@hansv.d.p.8679 Жыл бұрын
Well..Simon..you have nailed it... bravo and keep on going...greetings from Rotterdam ..thanks for sharing .
@gino2465
@gino2465 Жыл бұрын
Now that's a real nice home
@serraios1989
@serraios1989 Жыл бұрын
Well done for taking on the challenge!!! Could you not have salvaged the second water cylinder with an endoscope camera? Remove the heating element and stick the scope in. Less time and effort consuming. Still many thanks for the video
@andynicolson1057
@andynicolson1057 Жыл бұрын
Awesome, you're clearly the Davie504 of the plumbing world....Epic.....Slap!
@UrbanPlumbers
@UrbanPlumbers Жыл бұрын
Slappers !
@valentinmirauta7059
@valentinmirauta7059 Жыл бұрын
Knowledgeable at its best, very good video for who is in the game and not only. Thanks
@richardharries5551
@richardharries5551 Жыл бұрын
But of a misleading clickbait, no normal family lives like this. The owner was oversold heating cap acity and equipment. I am impressed with both your enthusiasm and knowledge as I am a retired Marine Engineer and used to large systems. Hopefully the owner gave you that bottle of champagne in appreciation.
@UrbanPlumbers
@UrbanPlumbers Жыл бұрын
come on - it KZbin - it has to be a bit of a clickbait 😉 Thanks for the comment.
@jeanjacques9980
@jeanjacques9980 Жыл бұрын
Fascinating video, bit mind blowing for a domestic installation, imagine a hospital!
@Fractal227
@Fractal227 Жыл бұрын
I need this dude to come and look at my house, if just i was not so far away xD
@scott19087
@scott19087 Жыл бұрын
I always take my time to write numbers and rooms on the corresponding wires, plus I write it on a piece of paper and leave that on the boiler/heat pump. Sometimes it feels useless but seeing how much time it takes you figuring out, I’ll continue doing it lol
@UrbanPlumbers
@UrbanPlumbers Жыл бұрын
I take pictures of the notes and file them under the project in Evernote. I do that for all jobs Justin case I have to trouble shoot it in the future
@ReferenceFidelityComponents
@ReferenceFidelityComponents Жыл бұрын
Decent looking boilers those. They look similar to the range topping Ideal Vogue or System boilers inside and out. Not cheap!
@GSXRRizla
@GSXRRizla Жыл бұрын
I wish you were closer to Shropshire. I'd happily have you review and upgrade my system. If you have any recommendations for like minded installers, please share. Keep up the great work...
@ItsFriscoBaby
@ItsFriscoBaby Жыл бұрын
Base exchange water softeners (salt) both stop the buildup of limescale and strip the existing scale from the pipework and cylinders. It takes months or years depending on the level of existing buildup but what you had here is no surprise.
@DJ-uk5mm
@DJ-uk5mm Жыл бұрын
Blimey this guy is a plumbing genius we’ll done
@deanchapple1
@deanchapple1 Жыл бұрын
Thanks for taking the time!!
@user-te1le7ck6b
@user-te1le7ck6b Жыл бұрын
Mate I’m a computer science teacher and even I struggled to keep up with your Boolean logic , your simply one of a kind , I had a similar issue and still do , 38kw boiler when all I needed was 24kw at most , took years for me to be told and modulation set as best as it could , even now it’s not great but seems better. Anything else I can do bar swap the boiler ? Congrats I hope to use you when I’m back in the UK 👍👍👍
@RayMondElec
@RayMondElec Жыл бұрын
Hi G please explain modulation set as best as it could. . Thanks
@user-te1le7ck6b
@user-te1le7ck6b Жыл бұрын
@@RayMondElec engineer set the boiler to modulate down quicker so it uses less power as it doesn’t need it
@RayMondElec
@RayMondElec Жыл бұрын
@@user-te1le7ck6b thank you. I think that means your boiler was range rated. I may be wrong. I think the boiler in the video is a vallient 837. Mine is a vallient 937 ( in built storage tanks) . Valliant service the boiler. My total rads KW is 18. So I set it to 18kw. Valliant engineer said it is best to leave it on auto mode and switched it back🙄. He also said to leave the pump speed in Auto. Set my flow to 55C and hot water to 50C. So much conflicting info online one never really knows what to set in order to save gas and run an efficient system. 🤔
@user-te1le7ck6b
@user-te1le7ck6b Жыл бұрын
@@RayMondElec mine is 38kw so needed to set it down to help as best as it could
@dontuno
@dontuno Жыл бұрын
I'm always fascinated by your videos and despite what is being said by some, your knowledge way surpasses any plumber I have ever met! I'm particularly interested to note that a 24 kw boiler can provide all the heat on a 4000 square foot property given that my 1800 ish property with 11 trv'd rads and 1 hw tank struggles on a 18kw boiler even when 4 rads are isolated and the respective room doors are closed. The only suggestion I have had from a plumber is to increase the boiler to 24 kw. BTW, double glazed and copious roof insulation.
@UrbanPlumbers
@UrbanPlumbers Жыл бұрын
you probably only need 10kW then. Google 'heat geek map' and hire a heat geek elite member - bigger chance to get someone who will be actually able to help you
@dontuno
@dontuno Жыл бұрын
@@UrbanPlumbers Many thanks and I will give that a go.
@richwaight
@richwaight Жыл бұрын
Brilliant work! Super interesting and well explained 🙌
@ram64man
@ram64man Жыл бұрын
The owner of the property, please post if you now have a full working 300 litre hot water tank providing all your needs or if you still experience an issue of lack enough hot water
@AidanSkoyles
@AidanSkoyles Жыл бұрын
cool; makes me appreciate simple American plumbing systems.
@henrybartlett1986
@henrybartlett1986 Жыл бұрын
Well done. These are great to watch.
@Matt.ffgmatHexPulseChain
@Matt.ffgmatHexPulseChain Жыл бұрын
Brilliant job!!! 👍👍👍👍
@SJR275
@SJR275 Жыл бұрын
Amazing work as always. Wish you were up in the North East so that I could get you to fix this little bungalow haha.
@davidfellowes1628
@davidfellowes1628 Жыл бұрын
The overall complexity of this system and the various parts raises a question in my mind. Hotels don’t create these inter related and inter dependent systems. They work much more on a room by room basis for all variable services. Why wouldn’t something similar work better and cost less here as well, because large parts of that house aren’t used every day. Individual room or area type systems can be activated when in use and only public areas on permanently. Also the thermal envelope of this property can’t be very efficient either based on your energy consumption stats.
@loving-plumbing
@loving-plumbing Жыл бұрын
Another well explained interesting video. Great stuff
@Skeletoncrew46and2
@Skeletoncrew46and2 Жыл бұрын
Head acratcher, pulled it off, by the looks of it. Just shows again how oversized our heating system are. Perfect example of over engineering. Nice work!
@UrbanPlumbers
@UrbanPlumbers Жыл бұрын
my head still hurts from tracing all those wires!
@Skeletoncrew46and2
@Skeletoncrew46and2 Жыл бұрын
@@UrbanPlumbers oh man that's a massive detective job. Well done.
@SisterAbdullahX
@SisterAbdullahX Жыл бұрын
Awesome job as ever. Got to be honest, I wouldn’t have tackled that job, far too much thinking for my brain to deal with! Have you done any formal electrical training or did you just learn as you went along?
@UrbanPlumbers
@UrbanPlumbers Жыл бұрын
I only had basic electrical training
@krissybufton
@krissybufton Жыл бұрын
I absolutely love your videos man!! I keep watching with a view of trying to work out why my heating system is so inefficient ! I live down near Portsmouth, would you travel this far to try and help me make my system work better ? I have a highly disabled daughter who requires constant temperature consistency and I struggle to keep everything working nicely for her! I have a Worcester Bosch life system boiler with an unvented 250l cylinder and underfloor heating in areas throughout the downstairs with a scope of extending this underfloor heating when works are done. I’m constantly wrestling with it to try and keep my bills down!!
@UrbanPlumbers
@UrbanPlumbers Жыл бұрын
Google ‘heat geek map’ for a better chance of finding an engineer who understands efficient heating systems
@krissybufton
@krissybufton Жыл бұрын
@@UrbanPlumbers oooh I’ll look into it ! Thanks
@MrSunnyBhoy
@MrSunnyBhoy Жыл бұрын
You should be teaching at a university mate. You are that good.
@chrispychan4547
@chrispychan4547 Жыл бұрын
Awesome plumbing man. Would love to understand the electronics side to your level one day.
@nedloh17
@nedloh17 Жыл бұрын
A heating engineer Wizard !!
@johndevlin980
@johndevlin980 Жыл бұрын
That’s amazing mate, good work 👍
@deanchapple1
@deanchapple1 Жыл бұрын
Well done! Phenomenal knowledge and courage to take on such a can of worms!! Elite engineer!! 💪🏼😊👍🏼 Although I think Andrew Millward may have a point and his words may come to haunt you?….. 👍🏼
@euroasiabtlimited3208
@euroasiabtlimited3208 Жыл бұрын
Great work . Thanks for sharing all that valuable information .
@hansgroenewegen6910
@hansgroenewegen6910 Жыл бұрын
You.are.a.good.plummer! Very good video. Thank you!
@chrisillingworth7967
@chrisillingworth7967 Жыл бұрын
Fantastic and informative video. Ain’t the main reason for a llh where there is multiple pumps with ufh? To stop them influencing flow rates outside of the international pump flow? Hydronic separation, Not just for when you have two boilers together.
@UrbanPlumbers
@UrbanPlumbers Жыл бұрын
Yes that is correct. However even with LLH in you still have a system pump influencing 2 manifolds pumps. I had a 2 hour discussion on how to address this with Andrew Millward today. I would just use CCT on manifolds as per Adam from HeatvGeek but Andrew is set against it and says it is as bad as no separation. I think I may put LLH back but without the system pump and just add 1 pump for rad circuit. I think this was a consensus we reached with Andrew. There is going to be a follow up on this soon. Another solution would be to use one boiler for rads and cylinders and separate the system with 2nd boiler just doing UFH on low temp. Unfortunately all those option add a cost to the install
@LocostR1
@LocostR1 Жыл бұрын
@@UrbanPlumbers Andrew's solution for my Vaillant install would probably work well, using electronic mixing valves or mixing groups controlled by the VR71 to supply WC controlled heat curves to each emitter type kzbin.info/www/bejne/bYmYhYWVmpV9gK8
@johnmit
@johnmit Жыл бұрын
It's a fantastic example that complexity does not automatically give you better efficiency, control or cost savings - and it can do the very opposite. I wonder how much all those extra thermostats (and the perceived extra control) actually saves them when compared to a simpler well balanced system. My guess is not as much as they think. And also why use underfloor heating manifolds with cheaper actuators when you can make you own out of hundreds of tees and individual zone valves... The labour time alone on all that soldering....
@jackman19911
@jackman19911 Жыл бұрын
Just taking that cylinder out is going to save a lot of money. Issue I find in installations with llh is how the circuits are run, dhw should be before the header/heat ex on priority so then all heating circuits can freely modulate
@UrbanPlumbers
@UrbanPlumbers Жыл бұрын
Exactly! Thank you.
@Thedar561
@Thedar561 Жыл бұрын
Is running a 2000 LTR buffer tank with an UFH system a good idea in relation to efficiency ??
@stigkrakpants3052
@stigkrakpants3052 Жыл бұрын
Does this video and his amazing work fill me with confidence that there are good tradesmen out there - who are honest and demand the best for client; or does this video worry the hell out of me that i will only find a poor or below par tradesman, who will rip me off and leave me with a crappy short lived system...?
@offgridwanabe
@offgridwanabe Жыл бұрын
Brilliant the outdoor sensor is the weak point imho at least if your weather changes fast.
How To Get Most From Your Vaillant Boiler.
16:53
Urban Plumbers
Рет қаралды 43 М.
Heat Geek Mini Store: Is It a Good Fit For Your Home?
16:31
Urban Plumbers
Рет қаралды 32 М.
小丑把天使丢游泳池里#short #angel #clown
00:15
Super Beauty team
Рет қаралды 47 МЛН
How many boilers does this house really need?
16:52
Urban Plumbers
Рет қаралды 55 М.
Learn How to Lower Gas Bills and Improve System Performance
13:10
Urban Plumbers
Рет қаралды 57 М.
Micro-bore Pipework & Heat Pumps: How To Make It Work.
11:04
Urban Plumbers
Рет қаралды 27 М.
Is a Geothermal Heat Pump Worth It? My Net Zero Home
14:43
Undecided with Matt Ferrell
Рет қаралды 1,1 МЛН
How Developers Are Ruining The Heat Pump Market
20:28
Urban Plumbers
Рет қаралды 110 М.
Heat Geek Super Cylinder Tested: The Most Efficient Hot Water Ever?
15:30