Good explanation of concept. Very few videos are available on youTube with such high quality knowledge. Thanks for sharing
@parishithjayan Жыл бұрын
Thank you for recognising
@chetantagade232 Жыл бұрын
Thank you for your bracing details guidance
@ShrikantKharatmol02085 ай бұрын
Ohh man 😮 i found gold on KZbin. V.informative video
@parishithjayan5 ай бұрын
Thanks..
@Er.Praveenraj Жыл бұрын
Your videos are good. The way you Present is really Good. Wish you all the best for more videos 🎉🙌
@parishithjayan Жыл бұрын
Thanks a lot
@mohammedobaidullah1613 ай бұрын
Please also explain about seismic & deflection..
@parishithjayan3 ай бұрын
Will do...
@sandybabya Жыл бұрын
Really nice content, keep it up
@parishithjayan Жыл бұрын
Thanks will do
@ganeshpaudel29729 ай бұрын
Thanks for this amazing video. I had a question - What happens if we do not provide the connecting member at the ridge line in this case, how does the bracings behave? What if we do not provide gable end column, Are roof bracings needed for no gable column case?
@parishithjayan4 ай бұрын
Obviously we are going to provide purlins above the rafters and near ridge there will be two purlins closer to the ridge, they try to transfer the force.. And incase if there is no wind column and the building is kind of open, we provide bracings on roof for the stability of the frame along the longitudinal direction.. There won't be much of a calculation subjected to calculating the force.. But there has to be minimum bracings provided on the roof to attain stability..
@Sarathk460 Жыл бұрын
For earth quake load. How bracing will behave ??? Bcoz of load reversal
@parishithjayan Жыл бұрын
When the load reversal occurs, the other pair of bracing would become active.
@kalyanikaremore5286 ай бұрын
How bracing behaves at expansion joint location?
@parishithjayan4 ай бұрын
The basic assumption is that, the force won't transfer from one side of the expansion to the other.. All the forces which arises from one end gable should be carried and transferred within the bracings provided before the expansion joint itself..
@omarshahid544 ай бұрын
Impressive Video But One Qs U said that if we have 80m span we need 3 braced bays - Maximum allowed is 50m so Can u tell me how 3 braced bays ... PLease
@parishithjayan4 ай бұрын
Considering ur building length wise split up is 10x 8m bays.. And m assuming that u r going to brace penultimate bay (last before bay) on each side.. which means the center to center distance of bracing will be 80m - 24m = 56m. Which exceeds 50m, so we need to have 3 braced bays in the building..
@aakashmistry422211 ай бұрын
Very good explanation about bracing system and it's important but if bracing have reversal stress like sometime compression or tension so what is it slenderness limit we need to consider ?
@parishithjayan11 ай бұрын
Just follow code. As per IS 800, for the strut or bracing member subjected to wind or seismic loads where there is a possibility for the reversal of stresses, need to check the tensile slenderness ratio for 350
@aakashmistry422211 ай бұрын
@@parishithjayan thank you !!
@magaj5665 Жыл бұрын
Thanks a lot for bringing the video
@parishithjayan Жыл бұрын
My pleasure..
@ashishsojrani1496 Жыл бұрын
What will happen if I provide bracing in second last bay
@parishithjayan Жыл бұрын
Nothing will happen.. You need to pass the force through strut tube until it reaches the braced bay properly..
@nageshghadge664 Жыл бұрын
Superb 🙌
@parishithjayan Жыл бұрын
Thank you
@MohammadGhouseShaikAnchala11 ай бұрын
Dear Sir your explanation was awesome. But I have one doubt, how do the first 2 rods will inactive, why don't they take the bracing force and gets buckle (fail's in buckling). And also what about wall bracing, which rods will take the force and which are inactive. Please clarify my doubts..... Thank U Sir.....
@parishithjayan11 ай бұрын
Basically, the rods are slender members which are not intended to take any compression force. Once the bracing force reaches those points, they try to push the rod and since they are slender, they can't withstand this force or they can't transfer this force, so they buckle away means losing its capacity to transfer the bracing force through compression. Then the force tries to find the new path to reach bottom. So it travels along the line of action, and once it reaches the second rafter, the alternate pair of brace rods gets activated and resist the load through tension. The same for wall bracings as well.. go through the video once again and try to make a simple bracing model in STAAD and study the behaviour to understand the concept.
@MohammadGhouseShaikAnchala11 ай бұрын
@@parishithjayan Thank U soo much Sir for your kind reply...