Always crack open the steam (top) gauge glass stop (with drain open) first if the boiler is hot. This warms the glass gently. Then open the bottom one, allowing a little water to flush out any small shards of glass, rust, debris from previous broken sightglass, etc.
@tenjhotenge6 жыл бұрын
awesome video thanks for this! Makes more sense now than reading it from a textbook.
@wareboilers6 жыл бұрын
Thanks for the comment! Sometimes seeing it is just a better way to understand a concept. Thanks for watching
@Arcturian11112 жыл бұрын
Can u clean the original tube. If so what do you use?
@alexanderadvincula92765 жыл бұрын
Great video!!!! Ritchie. quick question How to replace a tricocks on a steam boiler. thanks
@maavmaav61115 жыл бұрын
Can I replace the sight glass when the boiler still operating? If so, the boiler water still hot, which valve open first to put water back in the sight glass?
@josephrodriguez15403 жыл бұрын
Yes, you can.
@frustr8ted782 жыл бұрын
I close steam first.. Then water.. And after replacement... Water then steam...
@dalton59295 жыл бұрын
Great video very informative. Any tips on proper heating of the new glass though and avoiding skin contact?
@wareboilers5 жыл бұрын
Just introduce the heat slowly will really be the best bet to not cause shock. Wearing gloves is the best and safest way to do this procedure. Hopefully that help and thanks for watching.
@dalton59295 жыл бұрын
@@wareboilers that's what I was thinking thanks
@SushilKumar-hq4zv4 жыл бұрын
Great Video
@Citizen4354 жыл бұрын
Thankyou. Please show the video descaling for portable steam generator
@nyaikanelson66117 жыл бұрын
I would love some one to particularly hint on replacing the gauge glass when the boiler is actually running, since their is always limited time to stop production . which valve should be opened first? often the glass explodes when opening those valves.
@egold10066 жыл бұрын
Nyaika Nelson Always wait till the boiler cools down. Make sure the site glass is high pressure rated. I use Duran glass like the one used in this video.
@santoshchaglani78806 жыл бұрын
Santosh chaglani
@strobe96 жыл бұрын
For the home, what does it mean when the gauge glass is full to the point where you can't see the water line and it doesn't drain even when draining the main valve until the low cutoff light comes on?
@wareboilers6 жыл бұрын
It sounds like something is going wrong for sure. The boiler might be incredibly flooded or there could be something wrong with the gauge glass. Recommend getting that checked out from a professional in your area. Good luck and thanks for watching!
@jameswoltal20304 жыл бұрын
After replacing the glass & reinstalling the rods, you should not open both valves at the same time. If the bottom nut/washer leaks you will see water dripping. You have no way of knowing if the top nut is going to leak except when the boiler is making steam. Open the bottom valve 1st. If the water level rises in the glass the top washer is not seated properly. If the water does not rise the the washer/nut is good. Science - 2 things cannot occupy the same space at the same time.
@wareboilers4 жыл бұрын
kzbin.info/www/bejne/r6aVomSrmNyhmbs here is another video on this that we did on a working boiler. Take a look at that one
@SushilKumar-hq4zv4 жыл бұрын
Can someone send the video link in which i can see the cleaning or adjusting the igniter of boiler . Thanx
@wareboilers4 жыл бұрын
We actually do not have have a video that covers this but we will take a look and see if we can! Thanks for watching
@vieuxacadian94553 жыл бұрын
Don't forget to mention internal sight glass erosion !