I've been using a Short Pro Tool ever sense they came out and I don't know why more people are not using them.Good tool
@TPINSC8 ай бұрын
Me too
@KenMagee8 ай бұрын
After watching you cut those connectors I started doing the same thing and it works great. So much better than trying to deal with any stranded wire.
@bobgardner55808 ай бұрын
Retired now from 45 years as HVAC Tech. When I had a short like that in the outdoor unit the first thing I checked was for a small burn mark on the units cover where the control wires come in to the unit. The wires would be up against the door and would vibrate thru the insulation after a few years of running and finally short and leave a small burn mafk on the door. When you were putting the door back on it looked like a burn mark on door on the lable. Love your videos and love the way you troubleshoot. Your expertise shows.
@Chevroldsmobuiac8 ай бұрын
Great example of tracking an electrical fault, thanks!
@oliverstreet77045 ай бұрын
You turn a lot of screws by hand every day. Your hands will eventually tell you they've got too many miles on them. Get a lightweight electric screwdriver and use it so you don't put miles on your hands spinning screws you don't need to spin by hand. One other thing, cutting the ring off the terminal and leaving the ferrule isn't an approved use of the wiring device because it's too hard. A terminal block is a pressure terminal that is worked out for the screw to press soft copper wire to make enough contact area to the tongue. The hard ferrule doesn't create as much area. The screw side mashes better but its electrically worthless, screw threads have only a tiny contact area. What you're doing usually works initially and many will work indefinitely or at least longer than the contactor, but eventually some will show the current crowding as hot spotting, it will look like localized corrosion. Eventually the terminal overheats and the contactor will fail. You do a good job of tightening the lug to try to compensate, but working up enough torque is likely to break the contactor case before you get enough area. Get an automatic wire stripper you like enough to use or a buy a bottle of quick connect screw terminals so you can leave the ring on.
@user-hj5le6lo9w7 ай бұрын
Interesting way you landed the incoming power wires to the contactor. Makes sense. Better contact with wires. I’m gonna use that. Thanks!
@stevencossaboon32378 ай бұрын
Nice troubleshooting and work Ted.
@peterhodgkins69858 ай бұрын
Good work and nice demo of the Short Pro Tool! Thanks!
@RayRay-nb7tn8 ай бұрын
1 ton for that Bonus room seems alot, no? They be changing filters with the construction going on. I like that short probe tool, gotta look in on getting one. Nice explanation of what, how, and to find a short. Nice job Ted.
@JazawaToad8 ай бұрын
This was only a simple fix because of your experience and knowledge. I dont think a youngin' would have figured it out quite that easily.
@fredsmith12408 ай бұрын
Gonna start calling you the one handed film bandit. Great vids man!
@DonMoran-l9h8 ай бұрын
I am getting one of those short pro tools. Great video as usual.
@spitzer11138 ай бұрын
Great diagnosis and working the issue quickly and efficiently!
@Eddy638 ай бұрын
Nice looking install ... Love these chasing shorts vids that uses good troubleshooting like you did ... Thx
@Garth20118 ай бұрын
Nice job...Nice house too. Plenty of HVAC...all 2 stories should 2 or 3 units for full control and options. A few smaller units tend to work best.
@FPHA6978 ай бұрын
Great job Ted I have tool need to break it out and use more !
@mauichaui6416 ай бұрын
You could OHM out your contactor from furnace or thermostat.
@Sunrise_HVAC8 ай бұрын
Love that tool. Better than the little popper.
@williamserver43328 ай бұрын
Great video. Very informative. Finding low voltage shorts always gives me problems.
@carbine858 ай бұрын
I do the same thing with contactor lugs. Never had a problem.
@dimbag18 ай бұрын
Videos on back to back days . YES !
@watermanone75678 ай бұрын
Great little tool, Where did you purchase it? Thanks for the video.
@lee-johnson8 ай бұрын
I leave the short pro connected while testing outside. Finds the problem quick.
@Paul-IE-Repairs8 ай бұрын
Those lugs are not rated for a finely stranded wire, thus requiring a ferrule to crimp to so that the wires do no break under the set screw. So you are correct in the way you are installing wires into the device
@robalexander73488 ай бұрын
A nice check over job Ted 👍 Au
@seadeas8 ай бұрын
This is one of the better videos I’ve watched, of yours 👍
@James_Bowie8 ай бұрын
Using those old connectors as ferrules is perfectly OK. Much better than bare wires. 👍
@rj.parker8 ай бұрын
“Short Pro Tool” with current limiting and auto reset for the win. Beats the heck out of a Little Popper.
@jeffreywhitlatch14098 ай бұрын
I think contactor coils are failing way more than they used to these days. Even though my last short was a bad tstat wire beween the A-H and tstat, on a 6yr old metal stud condo with a Carrier. I was using my lil popper. And I do compressor wires the same way in lugs.😶
@zachary29998 ай бұрын
Awesome tool. Does it matter putting 5amp fuse on board that says 3amp fuse on it? And if you take screws out of back of the contactor the black plastic on side, slides out and you can see the coil.
@Hvac-dude8 ай бұрын
Holy cow I haven't seen a dico thermostat in a while basically white rodgers 😊
@carlosrodas11698 ай бұрын
one of the best video. I stared to wach all your videos. can you tell me where can I buy the screw driver that one you use in the video
@boeing757pilot8 ай бұрын
That's a Klein, not sure model.
@uxwbill8 ай бұрын
I've yet to see my Short Pro light up. Somehow I had imagined it would light up orange.
@NerdyBoyEden3 ай бұрын
what screw driver is that you use??
@padricfleming8 ай бұрын
How many ohms are you looking for when you ohm out the contactor?
@sknight03918 ай бұрын
Ted is The Man! 😎👍 🚨🚨🚨
@natepeterson71458 ай бұрын
IMO that's a more secure way to secure those wires on the contactor. I wish they were all like that.
@The1JBanks8 ай бұрын
Nice. Good find Ted.
@davidsanders69578 ай бұрын
Check the muffler bearings
@TedCookHVAC8 ай бұрын
Yes, and the blinker fluid.
@woodystokes15438 ай бұрын
Nice work 😊
@dealdoe53694 ай бұрын
Filter drier in the attic space is crazy lol
@wurthmannd0248 ай бұрын
1.5 pole contactors should always read
@petergarofolo93858 ай бұрын
Excellent video 👍 👍
@RogerGregory-vl4kb8 ай бұрын
Thats a nice pen you have their Ted.
@jhatfield27558 ай бұрын
I ohm y and commong inside and itll lead u to contactor straight off bat sometimes
@TedCookHVAC8 ай бұрын
Smart !!
@chesstime3568 ай бұрын
As always very nice video
@stephenpeele33098 ай бұрын
What tool is that you are using
@duramusmosley55308 ай бұрын
Short pro tool
@brandonneims93978 ай бұрын
Are you sponsored by the short pro tool can I use something to get a discount on it
@daviddoyle32464 ай бұрын
By doing what you did I'd think you'd get alot better contact instead of just putting bare wire in the contactor
@seadeas8 ай бұрын
It certainly isn’t…, such good English!!! 👍
@jasonrtfm34718 ай бұрын
Ah, the famous Carrier run cap that you'll be back for soon.
@davidlundy50078 ай бұрын
How many times have you forgot to mark the box and it wound up in your parts bin ? Lol
@Honestandtruth0078 ай бұрын
This is Not Simple.....a lot of experiences going into troubleshooting to pinpoint the Problem 👍
@tbone63548 ай бұрын
A good idea is to add 50ml of sulphuric acid to the compressor before regassing
@Zee-hl5iu8 ай бұрын
Tool link?
@scotts41258 ай бұрын
If it's Dico it must be the best.
@Mac4Willy8 ай бұрын
Great troubleshooting my man!
@Sunrise_HVAC8 ай бұрын
You could have left that short pro connected then when you connected the contactor it would have engaged. I do it a lot but like you said, just another way to skin that damn cat. 😊
@kevincampbell72768 ай бұрын
I have been cutting them ends off for years
@DonMoran-l9h8 ай бұрын
I can not get the fan speed turned up on Pepe's (Your old neighbor.) Trane. On fan only it blows on the lowest speed. It will not let me change taps. What am I missing?? PLEASE HEP a brother out!!!! I will be calling you about this soon.. : )
@TedCookHVAC8 ай бұрын
Call me up man …. I can tell you how.
@Doughboy18248 ай бұрын
Big house!!!
@daddygc58148 ай бұрын
And beautiful, like so many of the homes he works in
@tomcarroll37718 ай бұрын
I believe the contactor is called a double pole single throw contact
@bobb.63933 ай бұрын
Cool
@nomusicrc8 ай бұрын
Last Nice job
@briancarlisi22248 ай бұрын
Sell them some new modern T-stats when you return with filters. Those old, mismatched ones look hideous.
@kevincampbell72768 ай бұрын
Someone had red on common is supposed to be blue
@gerardomireles1228 ай бұрын
Helicopter 🚁
@gvnumber32008 ай бұрын
Ted Cook is workin’ again, Y’all !
@AdamDeal-KF0PRI8 ай бұрын
very n8ce trouble shooting! china keeps you in business thats for sure!
@yamohvac31818 ай бұрын
Ted
@davidsanders69578 ай бұрын
Glad I'm not the customer of yours. Because yes, there is a need to put gauge on it. Regardless of how you feel me as a customer is what I am paying for. Being a SERVICE PROVIDER is just that !! Provide FULL SERVICE, to the "best of your ability " I guess. Your now un-employed
@TedCookHVAC8 ай бұрын
First of all the customer was only billed for the low-voltage diagnostic, and the contactor replacement. So you’re mistaken, the customer did not pay for anything that I neglected to do. The general maintenance is done by a different tech at a different time of year, and is not combined with a repair situation, therefore, full service to the air conditioner or furnace was not performed nor was the customer billed for it. Second of all, it is up to me and my experience as to whether I see a need to connect gauges and affect a port that can easily create a leak for no reason. If you think you know better than the service tech, then you may as well service your own unit. And lastly, I agree with you, I am very glad that you’re not my customer either. If you don’t trust a professional, you should not hire them. And if you do hire a professional, you should trust them. You do not know more than me about Hvac. You have made that obvious. I just don’t throw gauges uselessly on every machine I walk up to. We take temperature readings, line temp readings, Delta T readings, etc. and there are many things we can do without disturbing the refrigeration system whatsoever. I hope your defensive posture pays off for you and other situations of life, but in this particular instance, it only makes you appear to be difficult to get along with.
@cmgngmc8 ай бұрын
NO LIGHT IN A ATTIC WITH MECHANICALS IN IT IS SO C H E A P DID I SAY C H E A P