Trane package unit no AC

  Рет қаралды 15,083

Curious HVAC Guy

Curious HVAC Guy

Күн бұрын

Пікірлер: 52
@jfrancis98
@jfrancis98 5 жыл бұрын
Nice to see I'm not the only one who educates themselves instead of ASSUMING. Thank you for being human
@curioushvacguy6876
@curioushvacguy6876 5 жыл бұрын
gotta stay humble to learn ya know- im a student everyday, just wish I had more time to study and do experiments, lol
@SqueakyHinge
@SqueakyHinge 5 жыл бұрын
Enthalpy economizers take into consideration "total heat" of the air based on a sliding scale computation internal to the manufactures design. They are designed to allow the air with the least amount of heat to make contact with the evaporator coil as the evaporator is designed to remove two types of heat. One is sensible heat with the other latent heat. Both represent "total heat". By using enthalpy the system uses less power because it's removing less heat so it doesn't have to work as hard. However, at an outdoor air temperature of 92 even in a dry climate the enthalpy control should have automatically removed itself from the control circuit & switched over to mechanical refrigeration.
@domenicpurgatori7068
@domenicpurgatori7068 Жыл бұрын
This helped me with the unit I'm working on right this minute, appreciate it sir.
@justincanterbury2561
@justincanterbury2561 4 жыл бұрын
Good job bro. I see a lot of guys that just don’t understand economizers and try to just bypass them all together and only use compressors. Good work getting them that free cooling!!
@theairconditioningguy
@theairconditioningguy 5 жыл бұрын
I love how you took us through your thinking process. Great! Video
@eggman9713
@eggman9713 5 жыл бұрын
I live in a dry climate, so we always set up economizers for dry-bulb only. But in areas of the northwest that are more humid, we sometimes use enthalpy. However, every economizer I have seen will have a maximum dry-bulb that will override the humidity sensor, so the situation in this video cannot happen. The logic looks something like "OK to economize if enthalpy
@actechformallyyomama746
@actechformallyyomama746 5 жыл бұрын
Thank you for that. I learned a lot there. It’s rare when we have a dry enough day here in Houston for that to be a problem but good to know. Thanks again.
@CHOMAHOMA
@CHOMAHOMA 2 жыл бұрын
Thank you for making this video. I am trying to understand those types of controls (economizers) a bit better in order to troubleshoot when I find them in the field. Good 👍 job.
@LeoS41280
@LeoS41280 4 жыл бұрын
I have some units like that on a building I take care of. I m going to check and see how their economicizers are set up. Thanks for the video.
@markcaldwell1245
@markcaldwell1245 4 жыл бұрын
Excellent job. Economizers are mostly a joke here in Oklahoma with the humidity on average and get bypassed a lot. This is good to know about straight temp readings and bypassing all the humidity elements that are typically the problem. That and gears jamming from dust and dirt. Economizers made me a true believer in MAU’s, something that is made for the job versus something added on.
@dumptrks
@dumptrks 5 жыл бұрын
Thanks man great informational video..I'll keep that in mind but haven't worked on a Trane one yet
@hrdworkin7633
@hrdworkin7633 5 жыл бұрын
Now THAT was interesting. I hope reliatel and Trane was listening. Great videos!
@goonzsquad1
@goonzsquad1 3 жыл бұрын
Great content loving the free infro
@sergiodjf
@sergiodjf 4 жыл бұрын
Unfortunately not everyone checks the economizer settings. One time I ran into a rooftop unit that had the economizer still collapsed inside as shipped from the factory. Very funny to find things like that.
@curioushvacguy6876
@curioushvacguy6876 4 жыл бұрын
Wow- lol I havent found that before-- just a few units that had duct work ran to the unit but no actual hole in the ductwork for it to bring in air, lol
@jphvac5725
@jphvac5725 5 жыл бұрын
Great information!! Some of these economizers are made too complicated for no good reason!!
@sparkytech8787
@sparkytech8787 5 жыл бұрын
Great Job your a great teacher, and humble thanks.
@jonathanschulz5841
@jonathanschulz5841 5 жыл бұрын
I don’t think they only look at humidity, they look at enthalpy (btu content in the air), which is a combination of temp and humidity. The controller is trying to determine if it is easier to cool dry, hot OA or more wet, but cooler return air. It is almost always cheaper to mechanically cool dry air. Regardless of the set up, it still should have turned on mechanical cooling if it was not able to meet setpoint. My money is you have a bad sensor and a bad board. But if it works with dry bulb, and the customer doesn’t care, all good 👍 sweet vid.
@curioushvacguy6876
@curioushvacguy6876 5 жыл бұрын
You make a good point Johnathan- I'll be going back soon for there spring pm so I'll get to revisit this case and see how it's been running. Thanks for watching
@jonathanschulz5841
@jonathanschulz5841 5 жыл бұрын
Curious HVAC Guy Did the unit have a 2 stage stat?
@djastram
@djastram 4 жыл бұрын
It compares ra enthalpy against oa enthalpy. If the math works out in the enthalpy calculations, it can cool with the oa, and it's lower enthalpy. The enthalpy math at 93 degrees and low humidity, should have calculated out to DX only. Those humidity sensors are not very reliable. I have 'fixed' many trane units the same way you did. There may be a day where it is just cool enough, and dry enough to free cool, and dry bulb only might miss that. Improved reliability is what I would shoot for also. Google enthalpy calculator, and fiddle with the inputs. Good video!
@CameronKettner
@CameronKettner Жыл бұрын
@@jonathanschulz5841 I see this overlooked all the time, the installers think because its a single stage unit, that they can use a single stage stat and not wire stage two. If there is no call on y2 then the economizer will never energize the first stage compressor while it thinks its suitable to economize even if economizing alone is not enough to satisfy the setpoint. At a minimum y2 needs to be jumped to y1 or better yet use a two stage stat.
@Randylazz
@Randylazz 5 жыл бұрын
Ya learn something new everyday Some good info right there.............
@yamohvac3181
@yamohvac3181 5 жыл бұрын
Great Job i learn something new today Buen trabajo aprendí algo nuevo hoy
@sergiomansilla
@sergiomansilla 5 жыл бұрын
Yo también !!! Saludos
@bryantylerservices
@bryantylerservices 5 жыл бұрын
Very good information! Humidity sensing... Ive only ran into ambient outside type.. So thank you ,i learned something new today.. Thanks for the great information. Bryan tyler refrigeration
@curioushvacguy6876
@curioushvacguy6876 5 жыл бұрын
Thanks for the support Joseph
@KG-yn9qi
@KG-yn9qi 4 жыл бұрын
Good work as always! (get knowed up! Ha ha) hey know its a pain and time consuming. Could possible to use a Shop Vac etc., to clean the inside area? Know all before the filter. But the build up can fall into ducting below, and grow icky stuff that filter will not remove. Use long wand with a brush head. Also see you and others on the coil side not clean up the build up! Why?
@daryllneuburger4946
@daryllneuburger4946 5 жыл бұрын
Cool great video 👍
@curioushvacguy6876
@curioushvacguy6876 5 жыл бұрын
Thanks
@jrsmyth9761
@jrsmyth9761 5 жыл бұрын
Is there a MAT setpoint Trane is going for, like Carrier has?
@Rodzilla408
@Rodzilla408 5 жыл бұрын
Thanks for the video I'm sure it will help me out one day.
@Grinderluke
@Grinderluke 5 жыл бұрын
Have you worked on the new carrier units with a vane axial motors
@curioushvacguy6876
@curioushvacguy6876 5 жыл бұрын
Hey Luke- I have not worked on those yet, but I have seen a few pictures of them. Have you gotten to work on them?
@prettycureforever7102
@prettycureforever7102 5 жыл бұрын
Did you change the filters ? They look dirty itll be really great if u did
@KG-yn9qi
@KG-yn9qi 5 жыл бұрын
Sir, as a new sub. I do watch others. But like watching you mire than Ted Cook of anti Diy fame.
@curioushvacguy6876
@curioushvacguy6876 5 жыл бұрын
I appreciate the support- thanks for watching
@jacobcolby1423
@jacobcolby1423 5 жыл бұрын
Great vid!
@kings92071
@kings92071 5 жыл бұрын
Did it have a 2 stage thermostat? If y2 is energized and it is ok to economize, the unit will economize and run the compressor. Every economizer should have a 2 stage stat. We run into this a lot in freezer farms.
@kings92071
@kings92071 5 жыл бұрын
Curious HVAC guy basically a freezer farm is a big room where they have a bunch of -80c freezers for storing test samples. Generates a lot of heat 24/7. The economizers really work over night bringing in the “free cooling”. Another interesting thing I learned with high heat load conditions with economizers is that y3 on a jade controller is actually a timer setting. The default is 2 hours. That is definitely a must change setting for something like a freezer farm.The company I work for does mostly pharmaceutical and clean rooms in Southern California.
@jwchicano
@jwchicano 5 жыл бұрын
Serious question. If the economizer is set for free cooling at 55°F what's the need for mechanical? I just got chewed out because I noted on two new rtu installs that these units with economizers need 2 stage stats for mechanical and free cooling to maintain a mixed air temp of 55°F. So instead of getting bitched at for trying to do what I thought was right I'm setting the enthalpy sensors for 55°F hoping that anything above that (given that the enthalpy sensors are working properly) it'll just drive the outside air dampers closed, open up the return damper and just bring on mechanical.
@jonathanschulz5841
@jonathanschulz5841 5 жыл бұрын
4!RF0RC3 JU4N should not have gotten bitched at. That’s dumb logic. When the economizer, sensor, damper, etc go bad a two stage stat will turn on the mechanical cooling if the economizer doesn’t keep up (probably because it’s broken). Or what if you have a high heat load like a server or elevator room? For those rooms I typically set the Econ for 60-65deg with mechanical cooling as. Back up. Easier to cool 65deg air vs 78deg (most cases).
@jonnymac31
@jonnymac31 5 жыл бұрын
If you want the service literature for the units with the reliatel and also the older units with the UCP controls let me know. I can send you digital copies. Nice video man.
@HVACRVIDEOS
@HVACRVIDEOS 5 жыл бұрын
John I'd love to get a copy of anything your willing to share. Hvacrvideos@gmail.com
@jonnymac31
@jonnymac31 5 жыл бұрын
@@HVACRVIDEOS I'll send it your way
@jonnymac31
@jonnymac31 5 жыл бұрын
@@HVACRVIDEOS I'll send it your way.
@jonnymac31
@jonnymac31 5 жыл бұрын
@@curioushvacguy6876 sweet man. I'm happy to share it.
@lee-johnson
@lee-johnson 5 жыл бұрын
Would be nice if they would put that trick in the manual.
@fredflintstone8048
@fredflintstone8048 4 жыл бұрын
I have to be smarter than what I'm working on in order to be effective. Most sophisticated economizers operate proportionally. As the outside air dampers open, the return air closes. This is to keep an air volume balance and to try and maintain a temperature setpoint. Some will use enthalpy setpoint control. This should be understood already, but I'll say it anyway.. The goal is to use the air source that will require the least amount of energy to cool and when the OSAT is low enough, require nothing more than fan power turning off the refrigeration section. I mean no offense to any hvac techs, but I find that economizers often get turned off because most HVAC techs don't understand them nor are they interested in taking the time to learn how they work. BTW, enthalpy is a value that's a combination of humidity and temperature, not humidity alone. Not to get overly technical here, but the value measures the number of water molecules and their temperature . The energy of cooling that must be applied to the coil to meet setpoint is dependant on the number of water molicules and how much the temperature needs to be changed.. The return air enthalpy is compared to the ouside air enthalpy and the lowest of the two is the best choice. modulating of the economizer on the other hand is generally done based on maintaining a temperature. Humidity is also a concern because of the energy wasted in the coil to dehumidify.
@russell4309
@russell4309 5 жыл бұрын
👍
@tomdolan8811
@tomdolan8811 5 жыл бұрын
From Trane’s own recommendations, to disconnect the humidity sensors, tells me their engineering design is flawed. In my view, external temperature sensors should be the primary control of the economizers. External humidity sensors should override the economizer’s function only when outdoor relative humidity is too high for indoor comfort even though the outside temperature is, say around 50°. Cool humid air being pumped indoors WILL bring complaints❗️Thanks for your coverage of this topic❗️
Carrier package unit not cooling: Part 2
20:43
Curious HVAC Guy
Рет қаралды 12 М.
HVAC TROUBLESHOOTING
23:18
D2D NY Real World HVAC Simplified
Рет қаралды 14 М.
Don’t Choose The Wrong Box 😱
00:41
Topper Guild
Рет қаралды 62 МЛН
Гениальное изобретение из обычного стаканчика!
00:31
Лютая физика | Олимпиадная физика
Рет қаралды 4,8 МЛН
Quick emergency calls
22:53
Curious HVAC Guy
Рет қаралды 9 М.
Carrier package unit No AC
18:01
Curious HVAC Guy
Рет қаралды 36 М.
Heat Pump package changed over to Trane Gas Packaged unit
8:14
Anti DIY HVAC
Рет қаралды 28 М.
LENNOX Multiple offender pt 1
13:05
Curious HVAC Guy
Рет қаралды 11 М.
Great HVAC Unit For The MONEY!! | RunTru By Trane
10:48
Quality HVACR
Рет қаралды 106 М.
Reliatel Training
7:25
Mr. Mechanical BAS
Рет қаралды 25 М.
Trane & Carrier Package Units Not Cooling
15:17
HVACR Survival
Рет қаралды 22 М.
Lennox package unit no AC/loss of comm with EMS
18:07
Curious HVAC Guy
Рет қаралды 17 М.
Don’t Choose The Wrong Box 😱
00:41
Topper Guild
Рет қаралды 62 МЛН