York Ymc2 Chillers Shutdown Shortly After Scheduled Start Time… Tripped Main.. No Display VFD

  Рет қаралды 16,155

Subcool HVAC

Subcool HVAC

3 ай бұрын

Was contacted early in the morning prior to shift start by a coworker that the chillers abruptly stopped after starting, no pumps or chillers running, no display on vfd’s and a main breaker tripped…Priority work order generated and Here’s how we responded #chiller #york #hvac

Пікірлер: 60
@ericbaker5619
@ericbaker5619 3 ай бұрын
Crazy that motor didn't show short when you two tested at the disconnect at the motor. Thanks for the video.
@subcoolHVAC
@subcoolHVAC 3 ай бұрын
I know, I was expecting to find one grounded. Better the pump motor than a tower motor 🫡
@Byron88
@Byron88 3 ай бұрын
It's surprisingly common, after it blows the arc usually breaks the short, but its so close to being grounded as soon as you apply voltage again it arcs again, as you saw after the megger showed 0Mohm at almost 0 volts, the fault would have showed up right away with a megger vs a standard ohmmeter
@craiglewis8272
@craiglewis8272 2 ай бұрын
@@Byron88yeah. That’s why I don’t like using a standard meter when checking for grounded motor
@ShaunPuzon
@ShaunPuzon 3 ай бұрын
Your editing work is on point, sir! Yet another great video!
@subcoolHVAC
@subcoolHVAC 3 ай бұрын
Thanks Shaun 👊
@mxslick50
@mxslick50 3 ай бұрын
You should probably replace the contacts in that starter, closing into a short (and it opening on the original fault) would have pitted the contacts pretty bad. At the least, do a voltage drop measurement across all three contacts when you get the new motor running. Any voltage greater than about 2v across those contacts means they are bad.
@subcoolHVAC
@subcoolHVAC 3 ай бұрын
Definitely 👍
@dgapp76
@dgapp76 3 ай бұрын
Agreed
@SupraTompan
@SupraTompan 2 ай бұрын
You simply measure voltage before and after contacts? I would not have thought about this.
@subcoolHVAC
@subcoolHVAC 2 ай бұрын
Measure volt across contacts while energized, Thermal camera will also help determine if excessive heat is being generated in any contacts. 0 drop is 👍
@littleprincess4417
@littleprincess4417 3 ай бұрын
We once had a wire on a 277 volt 20 amp lighting circuit bypass not only the 20 amp breaker, but also the 225 amp breaker in the distribution panel and go back and get a 800 amp breaker in the MDP.
@subcoolHVAC
@subcoolHVAC 3 ай бұрын
That’s a strong willed wire 😃 Thanks for sharing
@dgapp76
@dgapp76 3 ай бұрын
I was told by an old AC duffer years ago to make sure you keep the smoke in. 😅
@subcoolHVAC
@subcoolHVAC 3 ай бұрын
Yep, I heard that too 😃
@TheChillerGuys
@TheChillerGuys 3 ай бұрын
It’s so hard to put it back in after you let it out too… 😅
@subcoolHVAC
@subcoolHVAC 2 ай бұрын
Expensive too
@ayoutubewatcher7009
@ayoutubewatcher7009 2 ай бұрын
I miss working on the larger tonnage equipment, but not really.
@subcoolHVAC
@subcoolHVAC 2 ай бұрын
I hear you 👍 Thanks for watching!
@jasonjohnsonHVAC
@jasonjohnsonHVAC 3 ай бұрын
Yeah buddy....she gave up the ghost in style. Let the magic smike out....kinda lost opportunity for your helper to have gathered it back up in a bucket...😂😂😂😂....that smoke is valuable.....im just playing around. Great video as always
@subcoolHVAC
@subcoolHVAC 3 ай бұрын
Oh yeah, nothing like some bbq first thing in the morning. At least the apprentice got to see his first motor smoke release 😁Thanks Jason 👍
@plushdragon
@plushdragon 3 ай бұрын
where someone with a paper bag to go boom when you reset the mains
@subcoolHVAC
@subcoolHVAC 3 ай бұрын
😃
@LilyRoseElectric
@LilyRoseElectric 3 ай бұрын
Great job 👏
@subcoolHVAC
@subcoolHVAC 3 ай бұрын
Thanks 👍
@TheChillerGuys
@TheChillerGuys 3 ай бұрын
Awesome stuff man!
@subcoolHVAC
@subcoolHVAC 3 ай бұрын
Appreciate it!
@MariMuthu-ck5ih
@MariMuthu-ck5ih 3 ай бұрын
Good job 👍👍
@subcoolHVAC
@subcoolHVAC 3 ай бұрын
Thanks 👍
@fellpower
@fellpower 2 ай бұрын
For a fast check, u can measure the resistance of the motors, but if u want to make it right, u should measure with an insulation tester, because it can be moisture on a broken cable / motor or something like that. with an insulation tester - u can find that
@subcoolHVAC
@subcoolHVAC 2 ай бұрын
Thanks for Watching!
@stevencossaboon3237
@stevencossaboon3237 3 ай бұрын
Nice work Subcool.
@subcoolHVAC
@subcoolHVAC 3 ай бұрын
Thanks!
@JW-qp5uf
@JW-qp5uf 2 ай бұрын
Why are the chillers run in series? Are the temps higher on chiller 1 going into 2? Thanks for the video.
@subcoolHVAC
@subcoolHVAC 2 ай бұрын
There’s only 1 chilled water pump on this chiller plant, yes chiller 1 receives the warmer return water from the loop then passes through chiller 2 . Thanks for the question 👍
@guygfm4243
@guygfm4243 2 ай бұрын
Thanks for sharing
@subcoolHVAC
@subcoolHVAC 2 ай бұрын
Thanks for watching!
@djcode4714
@djcode4714 3 ай бұрын
yay. another one bites them dust!
@subcoolHVAC
@subcoolHVAC 3 ай бұрын
😎
@zekenzy6486
@zekenzy6486 2 ай бұрын
Great Video. Good Job and Nice Work. Thank you for sharing. Is that motor pump short to ground is that why's chillers was tripped Main breaker ? Please. Could we have part 2 replace motor pump ^_^
@subcoolHVAC
@subcoolHVAC 2 ай бұрын
Yes, motor shorted to ground. Thanks for the question. Part 2 is possible 👍
@BOBKB3NZX
@BOBKB3NZX 3 ай бұрын
I've noticed on higher current application that breakers meant to trip before a main will get stuck and not trip when they're supposed to. Maybe a quarterly exercise of them may alleviate that
@subcoolHVAC
@subcoolHVAC 3 ай бұрын
Thanks for the suggestion 👍
@ickipoo
@ickipoo 3 ай бұрын
I think the issue is simply the peak fault current, which every breaker in series will see simultaneously. A sudden hard fault will have a high enough current to trip upstream breakers. In some applications, some series resistance or inductance is required to limit fault currents to manageable levels - breakers are only rated to break a certain fault current.
@mrfrenzy.
@mrfrenzy. 2 ай бұрын
The main breaker should be programmed to prevent this, I would have a good electrician check the calculations and programming.
@rock7282
@rock7282 2 ай бұрын
Time to go with a new generation Baldor motor
@subcoolHVAC
@subcoolHVAC 2 ай бұрын
👍
@anthonybush3134
@anthonybush3134 2 ай бұрын
What are you going to do with that impeller from the old pump?
@subcoolHVAC
@subcoolHVAC 2 ай бұрын
The pump was removed to replace bearings and seals
@brent562
@brent562 3 ай бұрын
How much a motor like that cost?
@subcoolHVAC
@subcoolHVAC 3 ай бұрын
Somewhere between $4k-$5k depending on availability , I don’t do the purchasing though. Thanks 👍
@user-ge5le4ku6j
@user-ge5le4ku6j 2 ай бұрын
why no disconnect at the motor?
@subcoolHVAC
@subcoolHVAC 2 ай бұрын
There are disconnects 👍
@mxslick50
@mxslick50 2 ай бұрын
Try watching the whole video.....
@Cinncinnatus
@Cinncinnatus 2 ай бұрын
if you check to ground you should first check from ground to ground to make sure you actually getting a proper probe contact. 3:45 Not saying something done totally wrong either just as you shown in the video earlier probe contact isnt always perfect so should be teaching them to get into the habit of making sure the ground is being read properly first.
@subcoolHVAC
@subcoolHVAC 2 ай бұрын
It’s more likely the initial short to ground cleared and when power applied it arced to ground again. Thanks for commenting
@Cinncinnatus
@Cinncinnatus 2 ай бұрын
@@subcoolHVAC oh I wasn't referring to the cause nor am I implying it was overlooked/missed. Just saying you skip teaching a crucial step when checking for shorts to ground. Should always test first from ground to ground then test your lines/loads. If you just take your probe to a ground then use the other and start looking for shorts you assume to know that your grounded probe has proper contact.
@subcoolHVAC
@subcoolHVAC 2 ай бұрын
Thanks for watching
@lilpbass
@lilpbass 3 ай бұрын
I got some magic smoke I can sell you 😂
@subcoolHVAC
@subcoolHVAC 3 ай бұрын
Sold 👍🤣
York Chilled Water Air Handler Too Cold …… Rooms Are Freezing
20:28
ЧУТЬ НЕ УТОНУЛ #shorts
00:27
Паша Осадчий
Рет қаралды 6 МЛН
Looks realistic #tiktok
00:22
Анастасия Тарасова
Рет қаралды 104 МЛН
Mom's Unique Approach to Teaching Kids Hygiene #shorts
00:16
Fabiosa Stories
Рет қаралды 10 МЛН
Your church organ needs a huge infra-subwoofer.
6:26
ALPHA SOUND
Рет қаралды 114 М.
How a Supermarket Refrigeration System Works
8:45
HVACR Career Connect NY
Рет қаралды 59 М.
All About Telephone Power Plants
30:32
Connections Museum
Рет қаралды 55 М.
Commercial RTU HVAC Service Call
10:12
HughesMan HVAC
Рет қаралды 19 М.
Quantas vezes os ratinhos caíram?
0:18
F L U S C O M A N I A
Рет қаралды 40 МЛН
казахи сделали мустанг🤯❗️
0:26
Профессор ПельменАрти💀
Рет қаралды 3,4 МЛН
Очень ждал свою маму 💔
0:56
Awesome Cuts
Рет қаралды 7 МЛН
tractor rear light project #project
0:40
SB Skill
Рет қаралды 12 МЛН
Mobile phone 📱✋🚫😰
1:00
Okanutie
Рет қаралды 9 МЛН
Gym belt !! 😂😂  @kauermtt
0:10
Tibo InShape
Рет қаралды 5 МЛН