Transformer Circuit breaker and Fuse size Calculation

  Рет қаралды 11,501

Rashid iqubal

Rashid iqubal

Күн бұрын

Пікірлер: 42
@ShahulHameed-ic7tn
@ShahulHameed-ic7tn Ай бұрын
very useful info regarding electrical field.
@Rashid-iqubal
@Rashid-iqubal Ай бұрын
Thanks and keep watching
@nazmulkabir2481
@nazmulkabir2481 10 ай бұрын
Very Very Informative and helpful
@Rashid-iqubal
@Rashid-iqubal 10 ай бұрын
Thanks for watching
@mohammedirzath2788
@mohammedirzath2788 2 ай бұрын
can you tell me why your following NEC for breaker calc
@vipinsoni8437
@vipinsoni8437 18 күн бұрын
Please make a video for calculation of breaker making & breaking current.
@deepakmuyal4096
@deepakmuyal4096 8 ай бұрын
Kindly upload substation design videos
@Rashid-iqubal
@Rashid-iqubal 8 ай бұрын
Will upload soon
@vinodkumarprajapati5182
@vinodkumarprajapati5182 4 ай бұрын
Very good
@Rashid-iqubal
@Rashid-iqubal 4 ай бұрын
Thanks 🙏🏽
@manzoorkhan5246
@manzoorkhan5246 6 ай бұрын
For sizing breaker, contactor and cables which standard you normally use?
@Rashid-iqubal
@Rashid-iqubal 6 ай бұрын
@@manzoorkhan5246 NEC
@manzoorkhan5246
@manzoorkhan5246 6 ай бұрын
@@Rashid-iqubal please explain it further or mention any specific code like 23567
@seanakiiki7670
@seanakiiki7670 4 ай бұрын
Great, thxu
@Rashid-iqubal
@Rashid-iqubal 4 ай бұрын
Thanks for watching...
@maikanataucoko5888
@maikanataucoko5888 2 ай бұрын
For the 2nd example, is there a reason why you used P= 1600KVA for the secondary current? or was that a mistake?
@Rashid-iqubal
@Rashid-iqubal 2 ай бұрын
It should be 1500 kva, typo error
@NomanQudrat-u2p
@NomanQudrat-u2p 4 ай бұрын
Brother very nice
@Rashid-iqubal
@Rashid-iqubal 4 ай бұрын
Thanks 🙏🏽
@kaleemahmad6573
@kaleemahmad6573 10 ай бұрын
Why you did not consider the fault current of primary side of HT 33 KV brraker rating will come above 800 amp if you will see the fault current
@Rashid-iqubal
@Rashid-iqubal 10 ай бұрын
Actually In this video I explained CB current rating as per load.. For fault current calculation we should divide full load current (Is) / impedance. Short circuit current always higher than normal current rating of breaker. Every circuit breaker has two types of rating that is current rating and short circuit rating (ka) As per my first example we have selected 630amp circuit breaker and its short circuit current would be 52.49/4.71% =1.1Ka I will make another video which cover all safety protection. Thanks for watching
@brajeshtripathy7599
@brajeshtripathy7599 7 ай бұрын
Please make a video on Transformer, DG sets, UPS selection in details.
@Rashid-iqubal
@Rashid-iqubal 7 ай бұрын
Sure my next video will be on Generator and transformer. Thanks for your suggestion
@noelfaithfulkari2857
@noelfaithfulkari2857 6 ай бұрын
thank you sir for your amazing explanations. any video on transformer sizing??
@Rashid-iqubal
@Rashid-iqubal 6 ай бұрын
@@noelfaithfulkari2857 thanks for watching, my next video will be on transformer size calculation method.
@souravhajra1645
@souravhajra1645 10 ай бұрын
What do we use to select a circuit breaker, full load current value or short circuit current value? Please clarify, i am so confused..
@Rashid-iqubal
@Rashid-iqubal 10 ай бұрын
For circuit breaker calculation you need both full load current and short circuit current. Through full load current you can find out the rating of breaker. If current exceed then full load current in any circumstances like over load or short circuit, breaker will be trip. While short circuit current work when huge amount of current flow like 100 or thousand times more then full load current then breaker trip immediately in few mili second. It will protect system from fire as well as breaker it self. So if you purchase circuit breaker you need both rating. Eg 1000A ACB with 50KA short circuit current in 1sec. Or 36KA in 3sec. Thats mean circuit breaker can tolerate 50Ka current upto 1 second. Hope you understand.
@souravhajra1645
@souravhajra1645 10 ай бұрын
Thanks alot, understood completely sir..
@nategreene45
@nategreene45 10 ай бұрын
What if it is a step-up transformer? 480v, 3ph to 4,160v, 3ph. Say impedance is 5%. Am I using 600% factor from the table to size the circuit breaker on the primary (480v) side?
@narayanmanna6532
@narayanmanna6532 Ай бұрын
Please make a video on LT panel incomer, bus coupler & outgoing feeder ACB , MCB & MCCB size selection in details please.
@Rashid-iqubal
@Rashid-iqubal Ай бұрын
Sure, i will cover all these topic
@AfrozAlam975
@AfrozAlam975 Жыл бұрын
U explained very well and your voice is so energetic and crystal clear. May i request to please earthing wire and pit calculation pe ek video banayen. Like high rise sky scrappers, hospital and residential building me earthing and selection of bare copper wire clams and pit etc
@Rashid-iqubal
@Rashid-iqubal Жыл бұрын
Thanks, sure i will upload soon..
@salmananwar8370
@salmananwar8370 3 ай бұрын
dear i follow NEC calculation, but not in all cases , you have given exp of 1000 kva which has currnt capacity 1440 amps and we can consider 1600 amps which is already at next size then why we go on 2000 amps 2 times higher than trafo size. we know when we on transformer , inrush current happens but if we size the breaker as per curve characterstic then we don need to go on higher size which is technically and economically not good.
@Rashid-iqubal
@Rashid-iqubal 3 ай бұрын
Brother i request you to please watch this video carefully, for 1000KVA full load current is 1391.24 amp and as per NEC standard we must consider 125% (125% of FLC to ensure it can handle both the regular operating current and the inrush current) then it become 1739amp and the next available size of breaker will be 2000 amp.
@salmananwar8370
@salmananwar8370 3 ай бұрын
@@Rashid-iqubal dear I appreciate your effort but adding 125 percent on line current secondary getting oversize more than transformer is unnecessary requirement. 1000 kva line current is 1440 amps available size z 1600 amps ACB in which breaker curve can bear the inrush current , that's m not talking in the Air that is my practical exposure I have done projects and proposed 1600 amps ACB that's under operational , running smoothly without any tripping. I follow nec alot but I have concerned on NEC 450.3A . Cause your design standard not only based on NEC practical exposure also does matter , when 1600 amps ACB characteristics curve offers over current protection then why do I go on 2009 amps.
@salmananwar8370
@salmananwar8370 3 ай бұрын
@@Rashid-iqubal recent I have completed data center project in ryadh in which all trafo's are dry type as per specs dry type generate huge inrush current, I installed 4 trafo's of 3150 where I proposed 5000 amps ACB accordingly all substation are operational and working smoothly.
@Rashid-iqubal
@Rashid-iqubal 3 ай бұрын
@@salmananwar8370based on your country standard or design it may happen.. i also worked in saudi and Qatar, depends on requirements and project budget we can negotiate. However for 1000 kva transformer i always used 2000amp ACB and very rarely i see 1600amp ACB. I am not saying that 1600amp is not correct. Moreover you worked in Saudi, in middle east they never compromise with safety and standards. And my calculation is totally based on NEC standard.. hope you understand dear..
@manmohandhir9117
@manmohandhir9117 9 ай бұрын
In India we follow iec rules and not nec rules.You can consult any state electricity authority and you will discover that proper fuse size for this transformer will be 80 A.CB rating for secondary will of course be 1.25 times secondary current.
@Ab_multimedia24
@Ab_multimedia24 Ай бұрын
Formula wrong kva how to write
@Rashid-iqubal
@Rashid-iqubal Ай бұрын
@@Ab_multimedia24 what wrong ???
Cable Selection Method | Cable size calculation
13:08
Rashid iqubal
Рет қаралды 12 М.
UPS and Battery size calculation | UPS Redundancy
15:01
Rashid iqubal
Рет қаралды 10 М.
She made herself an ear of corn from his marmalade candies🌽🌽🌽
00:38
Valja & Maxim Family
Рет қаралды 18 МЛН
Calculating Fault Current using transformer impedance
17:22
INW Industrial Training
Рет қаралды 11 М.
Capacitor Bank and its Circuit Breaker size calculation
10:43
Rashid iqubal
Рет қаралды 1,9 М.
Does Current Flow on the Neutral?
23:03
Electrician U
Рет қаралды 1,1 МЛН
Busbar sizing
9:27
stephen brooks
Рет қаралды 137 М.
How do you size a transformer?
22:14
Electrical Concept
Рет қаралды 6 М.
BREAKER AND CABLE SIZES FOR ELECTRICAL CIRCUITS.
11:39
LEARN ELECTRICS
Рет қаралды 182 М.