Troubleshooting AC Servo Drives

  Рет қаралды 124,451

Precision Zone, Inc.

Precision Zone, Inc.

7 жыл бұрын

This video describes troubleshooting for AC servo drives. This is a general purpose video for all types of servo drives. This video goes through visual checks and static checks on the AC servo units.
Visually, it is important to make sure nothing is burnt or broken. Smell is also important. If anything smells burnt but cannot be visually seen to be burnt, take caution! There may be burnt components in the power section or base of the drive that is hard to see without full disassembly of the drive.
Static checking should be performed with caution, as it requires using a multimeter to check the different components inside the drive. In this video, Rob explains the exact procedure step-by-step for statically checking the diodes and transistors. Make sure that before performing any static checks that the power has been removed from the drive and the unit has been properly discharged.
For any questions regarding the information presented here, or any other servo or spindle issues, please visit us at www.precisionzone.net

Пікірлер: 42
@aiasmarques1319
@aiasmarques1319 6 жыл бұрын
Very nice video!
@MarineTechHub
@MarineTechHub 6 жыл бұрын
Very Good explanation and excellent
@sudigujjar
@sudigujjar 7 жыл бұрын
Nice video
@Yorumcu63
@Yorumcu63 9 ай бұрын
Thank you for video
@akhussain182
@akhussain182 6 жыл бұрын
Excellent explanation. Do you tell us about vfd drives parameter setting according to the motor rating.
@ritikaanmol9653
@ritikaanmol9653 5 жыл бұрын
Thanks for good explanation, can you please give me an favour about BAUMMULER BUS6 , ERROR CODING MEANING.
@Entertainmentcorner12
@Entertainmentcorner12 5 жыл бұрын
I have a sanyodenki Sanmotion servo drive. it gives AL-22 overcurrent 1 alarm right after turning on power. If there is any solution do let me know
@yahaiya7400
@yahaiya7400 3 жыл бұрын
Thanks for this wonderful video I want ask you something I have servo Driver and I have errors I did not find it in the manual it appeared "(error 45 ) " Do you know what does it mean
@ShimulSiddiqui
@ShimulSiddiqui 7 жыл бұрын
Please make a BOSCH SM series servo drive resting system (with encoder) video
@ATBPRODUCTION17
@ATBPRODUCTION17 Жыл бұрын
I have a servo amplifier a20b-2101-039 malfunction appears alarm 03 . Guess what part is the damage?
@pradyumnapatra3192
@pradyumnapatra3192 3 жыл бұрын
During checking of igbt, why it shows 0.3 to 0.7 voltage and what is it ?
@michealvino6355
@michealvino6355 3 жыл бұрын
How to Identify DB Relay in a Fanuc Servo Drive ? Can you suggest... Thanks in Advance...
@MrJzplastic
@MrJzplastic 4 жыл бұрын
Do you prefer Hioki over Fluke? and why?
@truekev1
@truekev1 6 жыл бұрын
whats this used for?
@sharifhossain8830
@sharifhossain8830 2 жыл бұрын
What's servo inverter? Which are used to control ac induction motor, such as Lenze 9300, 8400 etc Please answer....
@phongcodienliendoanh6770
@phongcodienliendoanh6770 2 жыл бұрын
my driver servo MR-J3 10a cannot save any setting parameters and a blinker dot behind fourth degit. how can i fit it ?
@elevatorsasansorler
@elevatorsasansorler 5 жыл бұрын
Good
@night_grinder1378
@night_grinder1378 Жыл бұрын
is that a IGBT TEST?
@khetikimaza7000
@khetikimaza7000 Жыл бұрын
Hello sir, how to check servo drive and servo motor are faulty or not ..share me procedure for check servo drive and motor
@lighthouse6208
@lighthouse6208 6 жыл бұрын
I have a servo amp fanuc A06B-6096-H116 now 8. alarm sometime display. Please guide for me check it. Thank you verry much
@shivanagaral8059
@shivanagaral8059 6 жыл бұрын
Light House Please check with its power module and motor insulation If both are ok it can be sent to repair
@rojherlaguna3729
@rojherlaguna3729 5 жыл бұрын
Regards I need to control 5 servo motors and drivers from my computer, what motion controller card recommends me to retrofit my vertical milling machine to a CNC machine and with what software does it work? 1. AC SERVO MOTOR HF-SP102 MITSUBISHI (01) Axis X INPUT 3AC 125V 5.3 A OUTPUT 1 Kw - 2.000 rpm SERVODRIVER - MITSUBISHI MODEL: MR-J3-100A (Analog) POWER: 1KW INPUT: 5.0 A 3PH+1PH200-230V 50/60 Hz OUTPUT: 170 V 0-360Hz 6.0 A 2. AC SERVO MOTOR HF-SP152 MITSUBISHI (01) Axis Y INPUT 3AC 126V 8.0 A OUTPUT 1.5 Kw - 2.000 rpm SERVODRIVER - MITSUBISHI MODEL: MR-J3-200A (Analaog) POWER: 2KW INPUT: 10.5 A 3PH+1PH200-230V 50/60 Hz OUTPUT: 170 V 0-360Hz 11.0A 3. AC SERVO MOTOR HC-SF202 MITSUBISHI (01) Axis Z INPUT 3AC 138 V 11A OUTPUT 2.0 Kw - 2.000 rpm SERVODRIVER - MITSUBISHI MODEL: MR-H200TN POWER: 2.0 KW INPUT: AC200V - 230 V 50/60Hz OUTPUT: 10A Thank you -- Ing. Rojher Laguna rojher.laguna@gmail.com
@gordonburnett9672
@gordonburnett9672 Жыл бұрын
Mesa cards and Linuxcnc
@abuhanifazadazad2142
@abuhanifazadazad2142 2 жыл бұрын
How to find out inside circuit or short
@emmersonclaveria8203
@emmersonclaveria8203 3 жыл бұрын
Our machine encountered unusual sound after we replaced servo pack driver the unusual sound gone. What is the possible trouble of servo pack driver? thanks!
@laboratoriocotear1949
@laboratoriocotear1949 2 жыл бұрын
What kind of sound?
@manjunathkaradi2488
@manjunathkaradi2488 2 жыл бұрын
Thanks sir for explanation Please our problem solve Mustibushi Mr j2s 40 a servo drive continues alarm comming AL 25
@duynguyenkhuong2864
@duynguyenkhuong2864 6 жыл бұрын
thanks your video
@sonyalindy362
@sonyalindy362 3 жыл бұрын
4:44 what do you mean by "inputs and outputs are shorted to ground"? Why do you want that?
@yacinedali2756
@yacinedali2756 3 жыл бұрын
it means that there is no short circuit between them and ground, as far as i know
@nabilmarsel8792
@nabilmarsel8792 2 жыл бұрын
@@yacinedali2756 hello, please what the purpose of the last checking when he switch between the probs (positive to negative of DC, and negative to positive DC.)
@mauriciojimenez1505
@mauriciojimenez1505 4 жыл бұрын
Las reparaciones son costosas con los proveedores Aveces si hay manera de ver estos tutoriales te ahorras costos de reparaciones solo de refacciones
@losmasbusk2nc
@losmasbusk2nc 3 жыл бұрын
Casi la mayoría de los proveedores en México se quieren hacer ricos con las reparaciones, te sacan un ojo, existe esta empresa en Monterrey, el mismo dueño repara, y da precios muy accesibles la verdad, www.mvelectronics.mx te los recomiendo trabajan muy bien
@lighthouse6208
@lighthouse6208 6 жыл бұрын
Hi ad Please help me
@industriasmurcia44
@industriasmurcia44 6 жыл бұрын
When i start my machine indicate failure 11 and check it out like the video, all the values indicate is ok. But this failure is Causes: High power impedance, PCB or transistor module are defective. Solution: Check AC power, replace damaged Fanuc part. You can repair correct?
@Promilus1984
@Promilus1984 5 жыл бұрын
That's just simple method to verify if there's no shorted semiconductor. But sometimes (mosfet and igbt) are degraded in that way they won't show up S/C with low voltage probe of DMM. But if you apply high CE voltage (e.g. megger) it might show up a lot lower resistance than fully functional (so current "leaking out" despite transistor being turned off). During inverter operation it might lead to invalid motor rotation, eventual short circuit in output stage, blown off igbt, fuses, tracks, caps etc. or just desaturation error (and immediate stop) if drive is smart enough. Some drives use controlled rectifier at inputs so it can regulate charging of DC bus caps (no big inrush current at startup) without using NTC+resistor+relay and similar. Usually SCRs brake down to S/C state but sometimes it is open circuit. If that's the case drive might see it takes too long time to charge up caps (so it lost 1 phase). Or if there are indeed series pre-charge resistors they might be damaged and have too much resistance to charge up caps.
@alfonsoalvarez5044
@alfonsoalvarez5044 2 ай бұрын
Hola, el video parece bueno, pero sería mucho mejor si lo traduce al español o castellano, llegaría a ser más interesante
@user-xk2er3ly4j
@user-xk2er3ly4j 4 жыл бұрын
FANUC system 700 error
@BeautyBattleZone
@BeautyBattleZone 8 ай бұрын
Alarm 101 atinya apa
@barbarossa7872
@barbarossa7872 6 жыл бұрын
in chat a la
@oleguretiy3221
@oleguretiy3221 2 жыл бұрын
Bad company
@manjunathkaradi2488
@manjunathkaradi2488 2 жыл бұрын
Thanks sir for explanation Please our problem solve Mustibushi Mr j2s 40 a servo drive continues alarm comming AL 25
CNC Electric Motor Bearing Housing Repair
2:03
Precision Zone, Inc.
Рет қаралды 5 М.
Procedure for Checking  Servo Motors and Cables at a Machine
7:35
Precision Zone, Inc.
Рет қаралды 22 М.
Мы никогда не были так напуганы!
00:15
Аришнев
Рет қаралды 6 МЛН
Final muy increíble 😱
00:46
Juan De Dios Pantoja 2
Рет қаралды 53 МЛН
Everything You Need To Know About Fanuc In 20 Minutes - Global Electronic Services
20:19
Global Electronic Services
Рет қаралды 332 М.
Introduction to Servo Motors and Motion Controllers
10:32
Tim Wilborne
Рет қаралды 74 М.
How To: Troubleshoot VFDs
11:30
Radwell International
Рет қаралды 28 М.
Servo Motor Repair & Rebuild Instructions - Testing and Alignment
12:49
Global Electronic Services
Рет қаралды 124 М.
Troubleshooting a PLC Output
7:25
KletteTech
Рет қаралды 34 М.
Control Panel Testing - Tips and Tricks
5:09
RSP Supply
Рет қаралды 181 М.
VRDY Off Alarm Fanuc Servo Amplifier A06B-6090-H006
30:37
Peepaw McDonald
Рет қаралды 45 М.
Troubleshooting AC Servo Motors
4:26
Precision Zone, Inc.
Рет қаралды 39 М.
What is an AC Servo Motor? Motion Control From AutomationDirect
10:27
AutomationDirect.com
Рет қаралды 39 М.
Опыт использования Мини ПК от TECNO
1:00
Андронет
Рет қаралды 756 М.
1$ vs 500$ ВИРТУАЛЬНАЯ РЕАЛЬНОСТЬ !
23:20
GoldenBurst
Рет қаралды 1,6 МЛН
Choose a phone for your mom
0:20
ChooseGift
Рет қаралды 6 МЛН
НЕ ПОКУПАЙ СМАРТФОН, ПОКА НЕ УЗНАЕШЬ ЭТО! Не ошибись с выбором…
15:23