Nice touch with the M6 brass nuts and bolts, many a time seen M6 roofers used and then they corrode like he'll. Lovely video and showing sparkies do know how to use a brush 😂
@bristolsparky6 ай бұрын
🤙🏻🤙🏻cheers
@John_Faultless6 ай бұрын
I'm the same. I see I big chunk of metal and think: "I gotta bond that bad boi!" 😂 Nice one showing insulation resistance to see if it needs bonding 👌
@bristolsparky6 ай бұрын
✌🏻yeah man, it was nice to show the lads what you can do to prove it
@FFT_Electrical6 ай бұрын
Advice I got for doing a single container office (NAPIT Tech Support) was divorce the PME earth and TT it, I intended to do a supplemental rod but they said no to that, expect the next guy got a different answer. Nice tidy job though
@bristolsparky6 ай бұрын
That's the issue, sometimes it depends on the assessor 🙃🙃
@kennethbooth72006 ай бұрын
Is the supply PME, if so should the containers be treated the same as a caravan,i.e TT'd with earth rods. Is there any other metalwork in close vicinity either above ground or below ground.Need to assess the risk of touching the container and true earth in the event of a lost neutral. Whats your thoughts?
@bristolsparky6 ай бұрын
I have loads of thoughts, all day, all the time
@oliverbarlow6 ай бұрын
I agree. Id be treating these the same as caravans and making them TT. 🤷 Interesting real world video.
@m4sh6666 ай бұрын
I wouldn’t bond them if it’s on a PME earthing arrangement. If you lose the supply neutral the containers could become live. TT the containers in my opinion 👍 (not saying I’m correct but that’s my opinion 😁)
@bristolsparky6 ай бұрын
Appreciate your comment ✌🏻
@TheYohtube6 ай бұрын
I did a similar job and I installed a supplementary earth rod to each metal structure with an Ra of less than 20 ohms and they were all bonded to the MET. I wzs mostly concerned about the consequences of loosing the PEN. There had been thefts of earthibg conductors at transformer lications in the area too accordeing to UKPN. Anyhow NICEIC engineer was happy with it.
@bristolsparky6 ай бұрын
👍🏻
@Badgerooni906 ай бұрын
Can you test the containers to see what zs reading you get that will determine if they’re extraneous or not ?. Most likely a tt so you don’t have to worry about pen faults.
@bristolsparky6 ай бұрын
How could you test the Zs when there is no electrics inside them?
@Badgerooni906 ай бұрын
@@bristolsparky when there’s power in them. I don’t know the arrangement but if they each have a small cu you could do it then and make the decision.
@bristolsparky6 ай бұрын
@@Badgerooni90 but i can perform a test to verify before installing any electrical equipment
@Badgerooni906 ай бұрын
@@bristolsparky r2 wander lead test ? That’s probably a better shout.
@darrenhemming24276 ай бұрын
Weather make a difference Try it after the British weather and see what the reading says (great video ) gets people talking
@bristolsparky6 ай бұрын
I did on my instagram stories but didn't put it in, don't know why, think it just made the video waaaaay to long
@whatthedeuse6 ай бұрын
Surprised they didn’t go with SPDs in the units. You’ll have some lovely low readings with that tray across all the containers 🤟
@bristolsparky6 ай бұрын
The containers that didn't have the tray obviously had higher readings, but still bonded them as it was still below 30,000 ohms
@bristolsparky6 ай бұрын
There is an SPD at the source
@whatthedeuse6 ай бұрын
@@bristolsparky meant your ZDB readings will be low with that parallel paths created joining all the containers with the tray 👍
@bristolsparky6 ай бұрын
@@whatthedeuse disconnect the main earth when doing the Ze of that board but reconnected when doing Zs of the upstream circuit supply
@danj11uk6 ай бұрын
Totally agree with how you wire the emergencies, I’m the same, why wire it so you have to do the three hour test out of hours because all the office staff are sat in the dark???
@bristolsparky6 ай бұрын
Exactly mate🫡🫡
@tonywatson14126 ай бұрын
Was wondering , is there a hard and fast , right way....or a better way . Or indeed several ways .hmm./ u r van LHD ?
@bristolsparky6 ай бұрын
RHD
@neil64386 ай бұрын
I would of thought these need to be isolated from a PME system.
@bristolsparky6 ай бұрын
Me too
@paul_my_plumbs_uk6 ай бұрын
Is this a containment job?? 😂😂😂
@bristolsparky6 ай бұрын
Not sure
@paul_my_plumbs_uk6 ай бұрын
@@bristolsparky container ment😜😜
@Ibrahim-vt2tz3 ай бұрын
Just advice Moving camera all the time Is make it stressful to watch your videos I know we all have different personality I know you are happy happy guy Which is nice But Is too much on video Is too much movement of camera From side to side It is not relaxing Rather become stressful to follow Thanks ❤