Working on a CHILLER I have NEVER seen before...HVAC Life

  Рет қаралды 10,617

Quality HVACR

Quality HVACR

Күн бұрын

Пікірлер: 60
@davidoneal4100
@davidoneal4100 9 ай бұрын
Really refreshing to hear the honesty from a technician
@realmadrid5981
@realmadrid5981 9 ай бұрын
I admire and appreciate your honesty. I was told by my instructor and leads that it’s okay to not know something
@topher8634
@topher8634 9 ай бұрын
Most chillers don't turn off. They "unload". Check your low water probe on the next visit. they have a tendency to becoming scaled up and stop sensing water.
@joefrance6599
@joefrance6599 9 ай бұрын
Yep! They will "unload" constantly under light load. That is what the bypass is for.
@nathanhurst5155
@nathanhurst5155 9 ай бұрын
Man I absolutely love watching videos of people working on things they’ve never ran across before. Awesome video dude 👍
@brianjones7983
@brianjones7983 9 ай бұрын
Always remember the basics of refrigeration, break it down and figure out why and what each component is doing. You have the skills to troubleshoot it . Good job for going outside your comfort zone.
@EverythingHVACR
@EverythingHVACR 9 ай бұрын
That alarm looks to be a water issue. That brazed plate heat exchanger has an air vent on top. You need water flow like you need air flow, start with the basics and they'll lead you to the problem most of the time. I like a good process chiller.
@c_young-hvac4586
@c_young-hvac4586 9 ай бұрын
I remember the first one of those I ever worked on . I stepped back and said th3 same thing you did . And the rest was history work on quite a few of them now mostly budzar
@NROhvac
@NROhvac 9 ай бұрын
Chillers are very basic once people see it that way. The problem could be a logic control problem, I’ve had it where the parameters on the controller were not synced with real time parameters, and was off by a good amount. Logic controller had a “freeze logic stat” and put a “low water” alarm out because of the improper parameters
@EverythingHVACR
@EverythingHVACR 9 ай бұрын
@@NROhvac logic is only as good as the information you provide it.
@NROhvac
@NROhvac 9 ай бұрын
@@EverythingHVACR yes indeed! lol
@EverythingHVACR
@EverythingHVACR 9 ай бұрын
@-QualityHVACR Anytime, I'm not hard to find, and I'm happy to chat.
@FrenchBeefCDN
@FrenchBeefCDN 8 ай бұрын
Hey, a Technotrans! I am the designated Technotrans repair guy for our company since everyone thinks theyre impossible to work on (theyre not.) The one big issue is the copper is metric sizes which our local supply stores dont carry. 3/8" copper is very close to 10mm which is what they use for liquid lines. I show up and Technotrans has already shipped the parts they think it needs (Solenoid Kits, TXV, Compressor etc.) When we get a call I am just the technician who can safely recover, cut out, braze in, evacuate and charge. Cool to see.
@thesilentonevictor
@thesilentonevictor 9 ай бұрын
Good to work outside the box Zack it's a learning curve
@pedrojuarez5834
@pedrojuarez5834 9 ай бұрын
it's always exciting to see your HVAC art
@davidturney2975
@davidturney2975 3 ай бұрын
One issue I ran into recently on a Daiken chiller was a EXV that would stick closed and cause a low evap pressure fault. I chased water to confirm it was getting enough water and almost everything else before setting on the EXV
@NROhvac
@NROhvac 9 ай бұрын
Sounds like evaporator isn’t getting enough water, I would check to see for restrictions. Anything that could disrupt that chilled water supply and return will cause evaporator temp to drop, that’s what’s causing that alarm. Once you confirm everything on that side is good and it’s still being a problem, check the unit with your gauges and dive deeper from there but it should only be a water problem. I love your humility it is very inspiring keep up the good work 👊
@NROhvac
@NROhvac 7 ай бұрын
@QualityHAVCR scammer
@BoilerMaker56
@BoilerMaker56 9 ай бұрын
I would’ve done exactly the same thing. Love getting my hands into something I’ve never done before and of course, getting a hold of the manufacturer will be a big help for you. Nice job.
@UncleEarlHeatingAirCondition
@UncleEarlHeatingAirCondition 9 ай бұрын
Thanks for sharing the experience..
@richardthomas1743
@richardthomas1743 9 ай бұрын
HEY! Good morning Zach!! And thumbs UP!!
@Brad1237202
@Brad1237202 9 ай бұрын
Love your channel. Getting an education from every video. "Every day is a school day" in the HVAC trade.
@zeph352
@zeph352 9 ай бұрын
I like what you do. I always emphasize to my students that they should never throw away the manuals, before proceeding with a repair or change, they should read the manufacturer's information, it is likely that something about that model and series has changed. We should never believe that we already know enough, every day there is something new to learn. I miss the days of repairing units of those capacities: commercial and industrial. excellent video.
@jarredallen
@jarredallen 2 ай бұрын
the loading, unloading heating and cooling is controlled by the leaving and entering chilled water. if either sensor is out of range or faulty it will load and unload compressor outside of its operating range or set point.
@abhijeetchandra4657
@abhijeetchandra4657 8 ай бұрын
To simplify a chiller instead of maintaining air temp it’s water that’s the only difference 🙌🏼
@andyberreondo5007
@andyberreondo5007 9 ай бұрын
Was there a strainer? Check your water side of things
@elheffe7316
@elheffe7316 9 ай бұрын
Hey Zack, will you make a video on which shoes\boots you've used in the past and present when working in the field and why you chose them. thanks brother.
@dgapp76
@dgapp76 9 ай бұрын
Like any other equipment, they require regular maintenance. Like it was said before, check for scale as it can cause problems on the water side. It looked like your sight glass was clear and uncontaminated so I'd start by checking sensor resistance values and go from there.
@monstahtron
@monstahtron 6 ай бұрын
I service these all the time every time I go to a new one its always a challenge figuring them out and of coure half the documentation is usually in German
@dylanwood7810
@dylanwood7810 9 ай бұрын
I just started working on centrifugal chillers, damn things are massive
@joshuatriplett8726
@joshuatriplett8726 9 ай бұрын
You may have already done this but there should be a chilled water strainer in there. More than likely on the entering chilled water side of the heat exchanger. If you valve the water off and take it out you may find it dirty. Might have ink in it i have found that before. Hope you’re able to get it figured out 👍🏼
@nhfdtb
@nhfdtb 9 ай бұрын
Those chillers are pretty simple to work on. I have several printing facilities I take care of. If the condenser is inside and the hot gas is cutting on and off it probably low in refrigerant. Is it bubbling in the sight glass? It is just like working on any other chiller.
@Duey_diditGarage
@Duey_diditGarage 9 ай бұрын
Awsome vid I stick to my level 2 boilers and chiller are like a foreign language to me just never had to deal with them
@aaronburke2469
@aaronburke2469 9 ай бұрын
Props to you for posting a video working on something you're not knowledgeable about yet.
@zekenzy6486
@zekenzy6486 9 ай бұрын
Great Video. Thank you for sharing
@per995
@per995 9 ай бұрын
The manual should mention how to add water/glykol somewhere. I suppose this one has a reservoir on the higher side of the compartment with an access to refill water. It will always happen a little evaporation so may be that simple that it happened over time or even a small leak. The oil based circulators are another story without need for a refill. As you mentioned, those units mostly use a bypass valve and an all time running compressor.
@per995
@per995 9 ай бұрын
@-QualityHVACR I should have mentioned that I always look forward to your videos. You are more calm than me, a good behavior😊Always nice and clean work from you! I worked with all kind of projects over many years and quite some chillers and heat systems. Mostly worked on cascade low temperature units of different types.
@robalexander7348
@robalexander7348 9 ай бұрын
You done well Zac, may be another try with a Longer Manual Reset ? 👍 Au
@CM-ou4zr
@CM-ou4zr 9 ай бұрын
Replace the water with air it will help you remember your basics. Low water=low airflow which could cause low evap temperature etc etc you know the drill
@FranciscoHernandez-gt8ne
@FranciscoHernandez-gt8ne 9 ай бұрын
2:47 Dude! I fel that😂
@TravisGrantland
@TravisGrantland 4 ай бұрын
In my experience with those systems, it’s the incoming water. Is it a pass through or recirc?
@jarodreebel6686
@jarodreebel6686 9 ай бұрын
I love this video!
@frankgall6
@frankgall6 9 ай бұрын
I’ve worked on those. Pain in the ass
@TheCurlyKid214
@TheCurlyKid214 9 ай бұрын
Could it be the sensor that is needing replacement for this particular error? Since it isn't a constant problem.
@vasiliy0704
@vasiliy0704 9 ай бұрын
надо проверить расход воды, проверить фильтр грязевик. посмотреть давление
@maness2112
@maness2112 9 ай бұрын
Check that water/glycol loop. Could be low.
@warenmann1042
@warenmann1042 9 ай бұрын
Time to check/change the water filter...
@1380Dane
@1380Dane 9 ай бұрын
Thats a baby one we have some massive technotrans units ove here in uk horrible to work on
@CommercialGasEngineerVideos
@CommercialGasEngineerVideos 9 ай бұрын
Good job considering that you've never worked on them b4
@jacobscyphers3630
@jacobscyphers3630 9 ай бұрын
They're so cute at that age
@cwevo316
@cwevo316 9 ай бұрын
intermittent pump issues?
@Lilflue.
@Lilflue. 8 ай бұрын
Them press chillers always need to be pm every month and and it was low on coolant
@Lilflue.
@Lilflue. 7 ай бұрын
@QualityHAVCR got any questions just ask
@asianking2240
@asianking2240 9 ай бұрын
Hi bro ! Може9по подробнее показать какими инструментами пользуешься
@everlastingdane
@everlastingdane 9 ай бұрын
Probably the reservoir water pump is failing
@brianbrannanHVACTech
@brianbrannanHVACTech 6 ай бұрын
Stick to heat pumps and promoting fieldpiece tools dawg and leave the chillers for the real techs 😂
@familyofthenorth7593
@familyofthenorth7593 9 ай бұрын
Slow time of year to be working on something like that. Risky
What YOU Need To Know BEFORE Getting In The HVAC Trade!!
15:35
Quality HVACR
Рет қаралды 125 М.
This Was a TERRIBLE Install….Until Now
16:29
Quality HVACR
Рет қаралды 35 М.
Hoodie gets wicked makeover! 😲
00:47
Justin Flom
Рет қаралды 127 МЛН
Haunted House 😰😨 LeoNata family #shorts
00:37
LeoNata Family
Рет қаралды 15 МЛН
I Almost CLOSED My HVAC Company After 10 Years | Here's Why...
19:12
How to repair aluminum evap coils
15:05
Cars n HVAC
Рет қаралды 24 М.
Scroll Compressor Exposed: Understanding Its Mechanical Magic
14:39
The Engineering Mindset
Рет қаралды 266 М.
THEY SAID PLEASE HURRY THE AC'S ARE NOT WORKING
45:53
HVACR VIDEOS
Рет қаралды 313 М.
Customer Fired Other Company! Can I Figure This No Cooling Out?
18:25
Jeff’s HVAC Adventures
Рет қаралды 591 М.
Horrible HVAC Design & How I FIXED it!!
21:10
Quality HVACR
Рет қаралды 39 М.
Typical HVAC unit LEAKING refrigerant & How I Fixed it.
17:37
Quality HVACR
Рет қаралды 49 М.