200 AMP Mast Service Upgrade | Surge Protection & Generator Wiring

  Рет қаралды 47,757

Electrician Ron

Electrician Ron

2 жыл бұрын

In this video you’ll see how an existing electrical service is upgraded from 100 amps to 200 amps and gets an updated grounding system and whole-house surge protection. Home portable generator interlock and transfer switch installation too!
Permits and Inspections are required for this work. Check with your local building department and utility company before doing anything you see in this video. Electrical work is not a hobby.
200 AMP Mast Service Upgrade Materials List:
Arlington MK200WH 2” Mast Kit
Reliance PB30 Power Inlet Box
Champion 125/ 250 VOLT L14-30 Locking Generator Cord
Eaton Cutler-Hammer BR 200 Main Breaker Plug-On Neutral 40/ 80 circuit panel
Eaton Generator Interlock Kit BRMIKCSR 150A-200A Indoor
2” x 4” Galvanized Nipple
JCPL 200 amp OH meter enclosure
2” Bonding Bushing
2” Locknuts & Plastic Bushings
2” x 10’ Threaded Galvanized Electrical Conduit
Water Ground Clamps
Galvanized 5/8” x 8’ Ground Rods plus clamps
15 amp single pole circuit breakers
20 amp single pole circuit breakers
30 amp double pole circuit breaker
60 amp double pole circuit breaker
Eaton Plug-On Whole House Surge Protective Device
4/0 Aluminum Conductor
#2 AWG Aluminum Conductor
#6 AWG Copper Conductor
Arlington Bonding Bridge
4/- AL butt splices
2” Rubber Splicing Tape
1” Black Vinyl Tape
1” White Vinyl Tape
Classic Electric, LLC
Point Pleasant, NJ 098742
(732) 770 1437
Wire and Above Ground Storable Swimming Pool WATCH HERE: • Wire a Storable Swimmi...
Classic Electric uses mostly Milwaukee cordless tools, Klein tools, some Dewalt, and some Makita!
Camera: Go Pro 10
Editing software: Apple iMovie
Animation software: Apple Keynote
All videos property of Ron Pecina Jr.

Пікірлер: 167
@Gruntled2001
@Gruntled2001 Жыл бұрын
Ron, thank you for another awesome video 💪🏼👍🏼
@victorcastro8815
@victorcastro8815 2 жыл бұрын
Great video!!! Keep them coming!!
@nmeart2068
@nmeart2068 Жыл бұрын
Another fine installation Ron.
@michaelmorgan7893
@michaelmorgan7893 4 ай бұрын
A few years ago, i was called in by a buddy to help him rewire a brand new house from which all the wire had been cut and stolen by tweakers who broke in. To steal less than $100 worth of copper scrap value, they did over $2000 in damage. We also had to cut above the service panel to re- feed the new romex into the box, because the bums didnt leave enough at the top of the wall to connect to. (And it wouldnt have been code anyway, as each circuit has to be a contiguous run)
@MrKen59
@MrKen59 Жыл бұрын
I actually put ground jumpers across any shark bite valves as well. This is very informative - wow!!!
@dominicparson5270
@dominicparson5270 2 жыл бұрын
Love the videos man keep up the good work
@foggiapainting
@foggiapainting Жыл бұрын
You are the best. Thank you for your awesome videos. San Diego, CA.
@electricalron
@electricalron Жыл бұрын
Thank you for your kind words. I love San Diego! I did Navy bootcamp there in 1990 before it got shutdown a few years later.
@jasonscoggins01
@jasonscoggins01 Жыл бұрын
Thank you Sir you Rock. Keep up the Awesome work. Form one Navy Veteran to Another. Jason
@BradAskegaard
@BradAskegaard 9 ай бұрын
Thank you both for your service!!!!!
@vincenthyland8048
@vincenthyland8048 4 ай бұрын
Very conscientious work that you do 👍🏻 the industry needs more like you . Thanks for the video
@electricalron
@electricalron 4 ай бұрын
Thats very nice of you to say. Thank you!
@rodolfovesga979
@rodolfovesga979 Жыл бұрын
Cool video Ron keep them videos coming back lol 😊 Like the work ! Another job well done❤
@electricalron
@electricalron Жыл бұрын
Thanks 👍
@luis_ayala_134
@luis_ayala_134 Жыл бұрын
I recently found your channel and became a subscriber. I love the content you post. Its very informative. Keep posting more great content.
@electricalron
@electricalron Жыл бұрын
Thank you very much!
@nayivisdenis1401
@nayivisdenis1401 Жыл бұрын
hi,ron you did great job ,profesional!!!.casanova electric contractor miami
@localone1597
@localone1597 6 ай бұрын
Great video. I definitely learned a few things.
@user-le1kj1mq4b
@user-le1kj1mq4b 9 ай бұрын
Another professional, clean install.
@electricalron
@electricalron 9 ай бұрын
Thank you!
@CryptoiNNERG
@CryptoiNNERG 2 жыл бұрын
Great job brother
@ProTecElectric
@ProTecElectric 2 жыл бұрын
Great detailed video 👍
@BestKaylee
@BestKaylee 9 ай бұрын
Thank you very much. Great information and presentation.
@waynergarcia5254
@waynergarcia5254 Жыл бұрын
I loved this video!❤
@ed6837
@ed6837 2 ай бұрын
Replaced a mast riser that had been bent by a truck hitting the service drop where they crossed the driveway. We were 100 feet from the pole which is about max around here. Tied the drop off to the chimney which wasn't in line with the pole so had another rope tied off to a car for a little sideways pull. Worked out fine. Had the keys for the car in my pocket LOL. Raised the mast higher and added guy wires to it.
@DBR00
@DBR00 7 ай бұрын
Merry Christmas Electrician Ron… Sending regards from Las Vegas, NV.
@electricalron
@electricalron 7 ай бұрын
Thank you! Raiders looking good today!
@DBR00
@DBR00 7 ай бұрын
@@electricalron ironically I'm a Jets fan! I used to live in Staten Island. 😂
@electricalron
@electricalron 7 ай бұрын
@@DBR00 sweet. I was at the game yesterday.
@desertcamel3573
@desertcamel3573 Жыл бұрын
great video!
@R900DZ
@R900DZ Жыл бұрын
Awesome, thanks 👍🏻
@doc13067
@doc13067 Жыл бұрын
I love how you put the main breaker at the bottom. I don’t see this enough. Too many guys run those giant 4/0 wires from bottom to top and waste all that gutter space just to make the main at the top, even when it throws side to side.
@doc13067
@doc13067 8 ай бұрын
Stop hating. This is how it’s done in our area. We often don’t use meter mains and sometimes it’s a pain to and always it’s more expensive Would you cover the additional cost yourself if the client did not want to pay for a meter/main combo? Also, 2 ground rods are required even with a cold water ground (250.53 (a)(2) ) unless you get one ground rod certified 25 ohms or less. Too many young sparkies on the internet look to call out others’ work and mostly they’re uninformed. Great work Classic Electric!
@doc13067
@doc13067 8 ай бұрын
I stand corrected that you didn’t know about the 25 ohms John Davies because I saw it in your other comment. Apologies. But for this same reason you still need 2 with the water ground. And the meter only with main breaker is how we all do it in jersey and PA
@gfysyoutube
@gfysyoutube Жыл бұрын
Nice work!
@FHES2005
@FHES2005 2 жыл бұрын
Nice veto work bag I own the TP XXL and love it
@electricalron
@electricalron 2 жыл бұрын
Hi Fred, I have a video on the TP XXL! Check it out!
@LincolnSP150
@LincolnSP150 Жыл бұрын
Great Video ....
@SoupTheChemist
@SoupTheChemist 7 ай бұрын
Good video brother 👍🏿
@linehandibew6205
@linehandibew6205 Жыл бұрын
Great job brother. I was an electrician for 8 years and then got into the outside lineman union on Long Island. FYI that loop is a preform on the neutral from the utility drop. If you cut back the tape on your hot legs they can be unwrapped a bit and you can u do one side of that preform. Start at the span side of it and get it started with a flathead screwdriver. Once started it’ll easily come undone. Only have to open the one side of that loop and you can pass it through the lollipop (porcelain point of attachment. Then re do it. Easy peasy. If the drop is too heavy uses a wrote tie a clove hits back a bit and tie the drop off to your pipe so you free up your hands. Great work brother be safe. Just subscribed
@jamesstiltner8885
@jamesstiltner8885 Жыл бұрын
Nice job interesting about generator wish I would have did. A hookup on one
@samuelreyes2124
@samuelreyes2124 Жыл бұрын
very good work
@electricalron
@electricalron Жыл бұрын
Thank you! Cheers!
@michaelmorgan7893
@michaelmorgan7893 4 ай бұрын
That piece to anchor the wire to is an insulator. All service drops here in California require an insulator (or wireholder) of some shape or form, to attach the incoming line to a structure. Nowadays, we're starting to see less porcelain or other glassware being used for insulators, as polymers and nylon materials are being made for that purpose.
@Dezeberbro
@Dezeberbro Жыл бұрын
Good work
@electricalron
@electricalron 11 ай бұрын
Thank you so much 😀
@jimharris1590
@jimharris1590 4 ай бұрын
good job as usual---thanks Jim... I wish you would wear safety glasses!
@arnieselectric007
@arnieselectric007 Жыл бұрын
another great video, I'm glad this one came up so I could see that, I never did one before, did you use a rubber pad on the roof to kneel and stand on..?
@mrkoshe
@mrkoshe 4 ай бұрын
ta pesao el viejon! 🫡
@seanleyden7971
@seanleyden7971 3 ай бұрын
Great vid. I'm just wondering if you're alowed to use insulated lugs for the service connection instead of rubber tape & electrical tape ?
@vince6829
@vince6829 Жыл бұрын
Thank you for sharing your knowledge. Impressive how you attached those two hot wires to the service mast without gloves. I imagine that the service drop wires were live, correct? I know that technically, you are OK as long as the hot wires don’t touch each other or the neutral, and as long as you are not grounded yourself.
@linehandibew6205
@linehandibew6205 Жыл бұрын
Bird on a wire bud
@slappadabass3290
@slappadabass3290 Жыл бұрын
He also kept his hands insulated the entire time. Only touching the jacket of the wire or the handle of the T allen
@garycunningham8478
@garycunningham8478 6 ай бұрын
What was the other water ground for? Thought the ground rods needed to be continuous from panel to media bond the to both ground rods.
@derekmitt23
@derekmitt23 4 ай бұрын
Here in Michigan, we have a homeowners exemption where we can get approved to do our own electrical work. I have an associates degree in electrical engineering, so I have knowledge and experience with this kind of trade. My question is, where and what brand do you buy for the butt joint when connecting the utility back up. I also have 2 meters/service with 4 hot conductors and 2 grounded conductors that are spliced to the 3 cable utility cables. How and what connectors would you recommend. Thanks 👍
@emilyyang7087
@emilyyang7087 6 ай бұрын
This is the most educational video of showing 200 AMP Mast Service Upgrade! Great work Ron! After you connect the new wire to utility wire, will utility company do anything? It seems you've done everything.
@electricalron
@electricalron 6 ай бұрын
Around here we always disconnect/ reconnect ourselves unless it’s an underground service entrance.
@theseattlegreen1871
@theseattlegreen1871 Жыл бұрын
Hi Ron great job. A customer of mine needs a 200-amp service upgrade. The only available meter/disconnect combo was the one that had eight spaces for circuit breakers. I didn't want this I just simply wanted a combination meter/disconnect but they don't have that back ordered for a year "supposedly" My question is I need to install a 200-amp panel in their house can I tap off of this meter/disconnect 8 circuit panel combo to feed the indoor sub panel 200 amp? I'm just concerned about this 8-circuit space that I'm not even going to be using Outdoors Thanks
@stillthakoolest
@stillthakoolest Жыл бұрын
Yes essentially all of these meter main combos have feed thru lugs for an inside panel. I like them myself, nice if you decide to add ckts to a garage or hot tub etc later
@alexiscordero5639
@alexiscordero5639 Жыл бұрын
Question what kind of sealtite is it UL rated? weather resistant dose it have greenfield coted over with sealtite?
@virulentKissesXOXO
@virulentKissesXOXO Жыл бұрын
Hi trying to figure out how to strap the mast to the house, I dont see that in this video
@aerofart
@aerofart Жыл бұрын
Great info and work. Would it be a good idea to trace out and identify (label) all your branch circuits before connecting the lines to the breakers?
@joshuaarellano6600
@joshuaarellano6600 Жыл бұрын
It's usually easier to do that after the power is on. That was you can turn on the lights and use a plug tester as well.
@Bruhsidon
@Bruhsidon 3 ай бұрын
Great video. I do have one question though. The wire you had to feed the generator outlet, do you need a conduit sleeve through the penetration of the house to connect it to the box? I will be subscribing, you were very informative, keep up the great work!
@swervomatic
@swervomatic 11 ай бұрын
Your not worried about getting zapped when stripping that service drop line from the utility with your metal razor knife? Just make sure your not touching anything grounded?
@--JohnDoe
@--JohnDoe Жыл бұрын
What about disconnecting the neutral?
@Xxpoo
@Xxpoo 2 жыл бұрын
Very informative video, thanks. I do have a question, after the upgrade does the electric company have to run thicker wire to the mast to match the new wirw you just installed? I live in Ohio.
@electricalron
@electricalron 2 жыл бұрын
That's up to the utility company. The vast difference between utility wiring and customer wiring is that the utility wiring is mostly in "open air." The ampacity ratings are completely different than when the conductors are in a conduit.
@Xxpoo
@Xxpoo 7 ай бұрын
So, in other words, “knob and tube” (in open air) has a different ampacity than Romex?
@MrKen59
@MrKen59 Жыл бұрын
When running a long ground wire across the house, does it introduce an addition voltage drop across the cable due to line resistance? Seems it could create a different potential. I love watching your workmanship. Thank you for adding references.
@electricalron
@electricalron Жыл бұрын
Any conductor has resistance no matter how big or how far. The National Electrical Code has a chart for sizing the GROUNDING ELECTRODE CONDUCTOR and it is based upon the size of the service entrance conductors. NEC 250.66
@MrKen59
@MrKen59 Жыл бұрын
@@electricalron sorry for the dumb question.
@arnieselectric007
@arnieselectric007 Жыл бұрын
@@MrKen59 There is no such thing as a dumb question...especially if you don't know or have been trained where to look...
@jaandel1
@jaandel1 Жыл бұрын
@@electricalron are those wires power the one you attached on the roof
@doc13067
@doc13067 8 ай бұрын
Yes! This is correct.
@LearnHowToWipeYaArse
@LearnHowToWipeYaArse 8 ай бұрын
Hey ron how do you say coffee? CAW FEE? this video helped me understand alot of whats going on and needs to be done on my home. Thanks .
@rosaniabrian5960
@rosaniabrian5960 Жыл бұрын
Hey Ron, great video! I found the PDF file reference with First Energy allowing Licensed Electricians to disconnect/Reconnect at the service drop. Is their a PDF file reference with PSEG allowing this?
@electricalron
@electricalron Жыл бұрын
I’m sure it’s on their website as well but I haven’t looked for it in quite awhile.
@yourfast07
@yourfast07 Жыл бұрын
Can you explain why porcelain bracket is used when ground is connected to meter and fuse box ? My house doesn’t have porcelain only metal bracket holding on to metal conduit.
@linehandibew6205
@linehandibew6205 Жыл бұрын
Every utility is different may be an old service drop as well
@joshuaarellano6600
@joshuaarellano6600 Жыл бұрын
The porcelain part on the riser is called the point of attachment
@owenjennings8575
@owenjennings8575 6 ай бұрын
Hi Ron - Very informative video as usual. For wires that might be too short inside the main electrical panel, have you ever used the Wago Inline Splice Connector to extend the wires (not sure if they are NEC approved). I find that the regular wire nuts make the panel look very busy and not the best looking.
@electricalron
@electricalron 6 ай бұрын
Yes, Wago's are an approved wiring method inside a panel. However, they're a bit more expensive than wire nuts so I only use them where wire nuts aren't practical.
@mcarroll598
@mcarroll598 2 жыл бұрын
With all the services you do, you should think about getting a Milwaukee cordless H-crimper for the services. The mechanicals work but take longer. Crimper is So much easier and faster.
@electricalron
@electricalron 2 жыл бұрын
I have thought about it. For the amount of time I'd use it I just couldn't justify the cost.
@mcarroll598
@mcarroll598 2 жыл бұрын
@@electricalron understandable. They also have the cutter head that interchanges with it too. Anyways, nice install man! Can’t believe you do this all yourself. I always have a another guy with me, when doing a service like this. It’s a lot of work!! Hopefully the home owner knows to shut off that hot tub breaker, if they go to start and run that generator.
@electricalron
@electricalron 2 жыл бұрын
@@mcarroll598 I still have to label the panel here and I put a red label on the circuits that cannot be used with the port gen. Thanks for the inquiry.
@nayivisdenis1401
@nayivisdenis1401 Жыл бұрын
HI RON .THIS IS ABEL FROM MIAMI WHERE DID YOU BUY THAT PANEL??//IS SUPER USEFULL!!!
@chadpharris
@chadpharris 11 ай бұрын
Man.. you're a blessing to us common folk haha. Do you have to run an uninterrupted/unbroken line to the water meter or can you just jump it like you did the water heater then pick it back up on the other side of the houses cold water line (assuming unbroken copper throughout). Or maybe thats the point, to alleviate any unknown breaks in copper water continuity to where you might pick it up again.
@electricalron
@electricalron 11 ай бұрын
Direct line from the main disconnect. Jump it out at the meter and also hot to cold jumper at the water heater.
@doc13067
@doc13067 8 ай бұрын
I’ve got some c crimp connectors great for irreversible splices on the GEC that work great in a pinch.
@billlaporte8255
@billlaporte8255 Жыл бұрын
for all al wire should there be dielectrode grease used to prevent oxidation?
@doc13067
@doc13067 Жыл бұрын
Dialectic grease? No. Noalox maybe, but any aluminum from AA-8,000 or newer is said to not corrode.
@jragadio
@jragadio 2 жыл бұрын
On the 2017 NEC that you are on in your AHJ, AFCI protection is not required when changing out a panel board?
@electricalron
@electricalron 2 жыл бұрын
Nope! We don’t even use an AHJ! New Jersey has adopted the Uniform Construction Code which allows them to amend certain sections of the NEC. We also have an entirely different sub code called the NJ Rehab code.
@jragadio
@jragadio 2 жыл бұрын
@@electricalron Awesome. Thanks, Ron. Love your channel. Keep up the great work to spread the love for the trades!
@Rysdad1
@Rysdad1 6 ай бұрын
Is there a way to change just the meter box without having to disconnect the line in up by the mast? I need to upgrade my meter box but if it IS possible id really like to not have to cut or mess with the upper line in. Can/how could you disconnect the line in at the meter box safely and keep it from arcing whole you pull the box, change it to a new meter box, then reconnect it to the box?
@electricalron
@electricalron 6 ай бұрын
Yes, call the utility for a disconnect.
@ernestochavez1968
@ernestochavez1968 Жыл бұрын
Hello. How did you or how do you support the mast to the roof. Braced not guyed. Thank you.
@electricalron
@electricalron Жыл бұрын
There’s a minimum height where bracing is not required. Check with your utility company for specific requirements on support for a mast service.
@tootasmoviecorner
@tootasmoviecorner Жыл бұрын
Love the videos. Can I come buy all your scrap? We are Monmouth county. I'll come pick it up where ever you want. We have portable scales.
@electricalron
@electricalron Жыл бұрын
I do my own scrapping and bring it John Blewitt’s in Howell.
@mikeelu6503
@mikeelu6503 Жыл бұрын
So I’m getting a 200 amp upgrade I currently don’t have a ground to my waterline just one ground rod. When the electrician came to give the estimate he said he would only have to add another ground rod and not ground to the waterline. So I would imagine that the electrical code doesn’t differ between states or maybe it does. And the work is going to be inspected so if they do it wrong it will fail so the question is waterline ground or not?
@electricalron
@electricalron Жыл бұрын
Maybe you have PVC water main.
@nayivisdenis1401
@nayivisdenis1401 Жыл бұрын
hi.ron.in florida some inspector requirement service disconect combo whith meter ,in case fire!!!!thank you
@electricalron
@electricalron Жыл бұрын
Maybe you’re on the NEC 2020 or the distribution panel is some place other than the closest point of entrance.
@nayivisdenis1401
@nayivisdenis1401 Жыл бұрын
yes you right!!1
@DavidKingmasterWV
@DavidKingmasterWV 8 күн бұрын
What do you do with all the pex now for your primary ground's is there enough room on the meter to clamp onto?
@electricalron
@electricalron 8 күн бұрын
@@DavidKingmasterWV there’s no need to ground the pex because it’s a non-conductive material.
@TomsLife9
@TomsLife9 9 ай бұрын
what's that orange wire for the generator? 6/3 romex? is that acceptable for an outside junction box? what if that junction box needed to be a few feet away and conduit was required - could normal romex still be used?
@electricalron
@electricalron 9 ай бұрын
Can’t use NM cable in a wet location. The orange cable is specific cable for Generac generator wiring and is rated for outdoors and for direct burial. About $6 per foot.
@TomsLife9
@TomsLife9 9 ай бұрын
awesome thank you. I'm piecing together the materials to tackle all of this@@electricalron
@TomsLife9
@TomsLife9 9 ай бұрын
would that be a UF-B variety?@@electricalron
@danielwarfield1027
@danielwarfield1027 Жыл бұрын
Just curious, does the NEC allow to use a 225 amp main breaker panel with a 200 amp meter?
@joshuaarellano6600
@joshuaarellano6600 Жыл бұрын
As long as the main breaker to that panel is sized down to a 200 or less. Otherwise you'd have to upgrade your meter (and probably the wires feeding it)
@andrewhylton4780
@andrewhylton4780 Жыл бұрын
Hey Ron I like your videos very informative. Could you not satisfy the code by using the rods only?Do you have to use the rods and the water line as part of your grounding system?
@electricalron
@electricalron Жыл бұрын
Yes, the ground rods supplement that copper water main pipe to complete the grounding electrode system.
@davidmarquardt9034
@davidmarquardt9034 Жыл бұрын
@@electricalron A little history, our old house with 60 amp service only had a water line ground. I was looking at some older NEC books once and the article regarding grounding was rewritten to include the 2 8 foot ground rods in the mid 70's, I guess they determined the water pipe was insufficient. I was told many years ago that the water meter was not considered a reliable conductor, because the nuts on the connecting nipples have rubber washers and the new ones they are putting in are plastic. So the jumper was to maintain ground continuity. What I don't understand is why you only have to use a 6 AWG jumper. It seems common sense to me that if your putting in 200 amp service, you should have to put in a jumper that can handle a full 200 amp fault to ground.
@bradrock7731
@bradrock7731 Жыл бұрын
@@davidmarquardt9034 PVC not a great conductor.
@davidmarquardt9034
@davidmarquardt9034 Жыл бұрын
@@bradrock7731 True, but in our town we have heavy type K copper laterals running 75 to 100 feet out to the water main in the street. The only break is the outside shutoff between the curb and sidewalk, and this connection is hard silver braised. So that is a huge amount of surface contact.
@Chris-zn5is
@Chris-zn5is Жыл бұрын
What type of wire is ran thru the mast, I know it's 4/0 aluminum. But what type
@Chris-zn5is
@Chris-zn5is 8 ай бұрын
@johndavies2949 99% off the houses in the territories I've worked ar aluminum. All the over head services and 99% urd are aluminum
@ans1020
@ans1020 Жыл бұрын
Hey Ron, at the end when your hooking up the service, was it live? If so, you don’t wear gloves?
@electricalron
@electricalron Жыл бұрын
100% live
@user-le1kj1mq4b
@user-le1kj1mq4b 9 ай бұрын
Ron, Is there a max length for the ground wire?
@electricalron
@electricalron 8 ай бұрын
No, but the less bends in the conductor the better.
@86aoshi
@86aoshi 7 ай бұрын
Ron what makes a mast service required vs just a normal one?
@electricalron
@electricalron 7 ай бұрын
The height of the service conductors.
@cameroncrider6970
@cameroncrider6970 2 жыл бұрын
What tool are you using to drive the ground rods?
@electricalron
@electricalron 2 жыл бұрын
M18 SDS Plus w/ ground rod driver attachment.
@arnieselectric007
@arnieselectric007 Жыл бұрын
@@electricalron that's what I use as well...what a great tool for that too...
@traviselectricalservices4532
@traviselectricalservices4532 4 ай бұрын
Did you change that panel, meter, and riser by yourself in 1 day ?
@electricalron
@electricalron 4 ай бұрын
Sure did! But I do the grounding usually ahead of the upgrade.
@robertt9342
@robertt9342 Жыл бұрын
What happens if the front panel is removed, then interlock can then be bypassed.
@electricalron
@electricalron Жыл бұрын
Captain obvious.
@robertt9342
@robertt9342 Жыл бұрын
@@electricalron . Sir, I like your snark.
@price9195
@price9195 7 ай бұрын
you test for an arc to make sure you're not grounded?
@electricalron
@electricalron 7 ай бұрын
No.
@user-yv4np4ur3q
@user-yv4np4ur3q 4 ай бұрын
What type tool are you using for your ground rods
@electricalron
@electricalron 4 ай бұрын
SDS Max by Milwaukee.
@Ojeramup12
@Ojeramup12 6 ай бұрын
Is that a Nic/cut on the white feeder wire on 21:48. ?
@electricalron
@electricalron 6 ай бұрын
There’s no nicks on any of the conductors. There’s a bonding bushing present to specifically prevent that from happening.
@Ojeramup12
@Ojeramup12 6 ай бұрын
K, my mistake.
@zabizeyaee8002
@zabizeyaee8002 Жыл бұрын
That part is called a mast insulator. utility company ties the neutral conductor to it
@FHES2005
@FHES2005 2 жыл бұрын
Just wondering in your jurisdiction is it code to where you have to use rigid conduit or can you schedule 80 PVC electrical conduit
@electricalron
@electricalron 2 жыл бұрын
Normally, it's up to the utility company. If my mast were any taller than in the video the rigid conduit would have to be 2 1/2"
@balrog006
@balrog006 Жыл бұрын
PVC, even SCH 80 is not load bearing-it couldn’t be used for a mast like this.
@Kevin-wj4ed
@Kevin-wj4ed 11 ай бұрын
We're is the 400 amp meter base?
@electricalron
@electricalron 11 ай бұрын
At the supply house I imagine.
@seanstrickley3992
@seanstrickley3992 Ай бұрын
How long this job take you sir
@electricalron
@electricalron Ай бұрын
2 days labor by myself. First day grounding, seconds day service equipment.
@loganxmen3114
@loganxmen3114 3 ай бұрын
🤘🍿🍷👍👍👍👍
@samfish6938
@samfish6938 Жыл бұрын
you should use crimp lugs
@electricalron
@electricalron Жыл бұрын
Why is that?
@raymondcasso7966
@raymondcasso7966 Жыл бұрын
I actually thought they were hot, but it truns out the company pull the fuse on the transformer.
@electricalron
@electricalron Жыл бұрын
False.
@raymondcasso7966
@raymondcasso7966 Жыл бұрын
@@electricalron 😅 lol company puts on 10kv gloves just to replace a meter...
@brucerauch8024
@brucerauch8024 Жыл бұрын
I use my teeth to start my 33+ tape just as you do😂
@electricalron
@electricalron Жыл бұрын
I hope my dentist doesn't follow this channel LOL!
@robertschneider3887
@robertschneider3887 9 ай бұрын
Ik I’m a year late but did we all see the wasp nest come out of the pipe😂
@nickk05281982
@nickk05281982 Жыл бұрын
what happens when the city upgrades the water service to plastic and the customer doesnt realize that its bonded?
@electricalron
@electricalron Жыл бұрын
It’ll no longer be considered an electrode. This is why we drive supplemental ground rods.
@R900DZ
@R900DZ Жыл бұрын
His connections will still protect personnel in the case where the Copper pipe gets energized, the breaker will clear the fault.
@cavy95
@cavy95 2 жыл бұрын
200 amp, needed for EV charging overnight.
@davidhill3724
@davidhill3724 Жыл бұрын
if you think it will take 4 hrs tell your customer 6 and no matter what be done by 6 hrs
@livewire575
@livewire575 Жыл бұрын
Panel is mounted upside down
@electricalron
@electricalron Жыл бұрын
Ok, I'll go back and flip it.
Power for the Future: A new 200 AMP Electrical Service Upgrade
30:18
Electrician Ron
Рет қаралды 29 М.
FULL 200 AMP SERVICE UPGRADE | CLARK, NJ
51:14
Electrician Ron
Рет қаралды 119 М.
Sigma Kid Hair #funny #sigma #comedy
00:33
CRAZY GREAPA
Рет қаралды 37 МЛН
Double Stacked Pizza @Lionfield @ChefRush
00:33
albert_cancook
Рет қаралды 97 МЛН
Mama vs Son vs Daddy 😭🤣
00:13
DADDYSON SHOW
Рет қаралды 43 МЛН
Rewiring A 100 Year Old Garage | Removing Knob & Tube Wiring
25:05
Electrician Ron
Рет қаралды 28 М.
Overhead & Underground Electrical Utility Service
15:52
Electric Pro Academy
Рет қаралды 57 М.
Sub Panels Explained - Why are neutral and ground separated?
16:22
The Engineering Mindset
Рет қаралды 1,2 МЛН
Residential Service Entrance Nightmare DIY Electrical Repair!
11:08
electronicsNmore
Рет қаралды 21 М.
100 AMP TO 200 AMP PANEL UPGRADE | Sunny Side Linden, NJ.
20:26
Electrician Ron
Рет қаралды 52 М.
Why Do We Bond at the Service Panel and Not a Subpanel?
19:46
Electrician U
Рет қаралды 1,1 МЛН
Cheap & Easy Way to Connect a Generator to Your House - Legal Too!
8:19
Bringing Back Bella 🐶
0:16
watchmylegos
Рет қаралды 7 МЛН
Don´t WASTE FOOD pt.3
0:20
LosWagners ENG
Рет қаралды 12 МЛН
WOW! SMART idea and very USEFUL 👓 👁 p5 #camping #survival #bushcraft #outdoors
0:17
Ăn Vặt Tuổi Thơ 2024
Рет қаралды 81 МЛН
Дал денег, закрыл долги прохожим
0:24
Сергей Миракл
Рет қаралды 4,1 МЛН
ToRung short film: 🤫pick up money💵🤑
0:26
ToRung
Рет қаралды 13 МЛН
Waka Waka 🤣 #11 #shorts #adanifamily
0:13
Adani Family
Рет қаралды 10 МЛН