Why Do We Bond at the Service Panel and Not a Subpanel?

  Рет қаралды 1,165,788

Electrician U

Electrician U

Күн бұрын

An important question was raised by one of our viewers. Why do we bond at the Service Panel and not at the Subpanels? A very valid and super important question that Dustin brings answers to in the latest episode of Electrician U.
CHAPTERS
[00:00] INTRO
[01:07] Merch messages
[01:42] Start of explanation
[03:58] Objectionable Current
[09:21] Example 2
[13:05] Example 3
[18:28] Bonding Wrap up
[19:07] OUTRO
🤘⚡️MEMBERSHIP⚡️🤘
JOIN ELECTRICIAN U - become a member and get:
FREE Continuing Education every year
FREE Practice Exams
FREE Monthly Video Courses
FREE Monthly Educational Newsletter
Premium Members-Only Content
Private Discord Channel
Monthly Members-Only Discord Chats
Sign up here --- www.electricianu.com/electric...
🎧🎹MUSIC AND VIDEO:🎹🎧
/ descantmv
🎬✍️ART AND ILLUSTRATION:✍️🎬
www.daverussoart.com
So, in a typical scenario, we would bring our ungrounded (hots), grounded (neutral) and grounding (ground) conductors into our service. This is at the point that we would bond the grounded and the grounding conductors together. From there, our all the conductors leave and can enter another panel where they are kept separated with no bonding. The primary reason for that grounding conductor is to set an alternate path back to the voltage’s source (breaker or fuse etc.) in case something happens, so there is another path back for the breaker to trip. Without that alternate path, the chances for someone to get shocked are considerably higher.
One of the reasons we separate the conductors past the Service Panel has to do with Objectionable Current. Simply stated, it is current that is going multiple directions at the same time; those directions we DON’T want it to go in! normally, that current leaves the source on the ungrounded wire, travels through the source, and returns to the source on either the grounded conductor or the other ungrounded conductor at the equipment. Objectionable current would be if a wire came off and touched something it wasn’t supposed to and sent the current somewhere else. The neutral conductor is expected to carry current; ground wires are not meant to carry them on anything other than a fault condition. If we didn’t bond the neutral and ground together at some point, we potentially could have objectionable current flowing on BOTH the neutral and ground at the same time and trying to return to source creating a considerable amount of havoc along the way!
If there was an event, say a ground fault where one of the ungrounded conductors touched the case of a dryer, the grounding conductor would carry that objectionable current, momentarily, back to the service panel, where it is bonded to the neutral, thereby completing the circuit. In fact, since the load itself was taken out of the equation (by touching the case and bypassing the load itself) the breaker sees SO MUCH current, that it does exactly what it is supposed to do and will trip. If that grounding wire was not there, and the complete circuit was not made, there would be potential for current to be on ALL the metal downstream from the service point and someone could get severely injured.
So, wouldn’t extra bonding be good by bonding in each panel location? If we were to bond in EVERY panel, then we would leave MULTIPLE paths that the current COULD take on its way back to source to complete the loop, and we would be defeating the purpose of trying to direct the current back to its source. In addition, if the neutral and ground were bonded in EVERY panel, then under the same circumstances, we would be sending potential to EVERYTHING plugged into ALL the circuits. So, we BOND it at the one spot only so we can keep the current corralled along the way WE want it to go and not energize everything along the way!
Please continue to follow Dustin and his travels here at Electrician U. Don’t forget to check in often as we are adding new items several times a week!
#electrician #electrical #electricity

Пікірлер: 1 500
@johnpetruna8888
@johnpetruna8888 2 жыл бұрын
That is the best explanation of this concept/rule I have ever seen. And I'm almost a boomer!
@russashworth1340
@russashworth1340 2 жыл бұрын
your use of the term neutral jumps between code and slang in the trade. In Canada the the use of the word neutral is well defined. As far as bonding a neutral in a building not part of the "service entrance " is due to RF energy. Go back too school. HR Ashworth. 309 A ,309 D & Ontario masters. Inter provincial
@tiggeroush
@tiggeroush 2 жыл бұрын
@@russashworth1340 it is interesting, the differences between codes of different countries. The 2020 NEC does not define neutral but does define Neutral Conductor as the conductor connected to the neutral point of a system that is intended to carry current under normal conditions. It defines Neutral Point as the common point on a wye-connection in a polyphase system or midpoint on a single-phase, 3 wire system, or midpoint of a single-phase portion of a 3-phase delta system, or a midpoint of a 3-wire, direct-current system. It defines Grounded Conductor as a system or circuit conductor that is intentionally grounded.
@stevenriggs9631
@stevenriggs9631 2 жыл бұрын
@@russashworth1340 .. maybe Mm T5f fr f rv 6
@raisingcaine5480
@raisingcaine5480 2 жыл бұрын
Careful, or BOOM, BOOM, out go the lights!
@rjfontenotiii
@rjfontenotiii 2 жыл бұрын
I believe it is you that needs to go back "too" school.
@turmoilfab
@turmoilfab Жыл бұрын
I’m not even an electrician but this is now the only guy I go to to get an explanation I can try to grasp. Great job!
@neilbarrow666
@neilbarrow666 2 жыл бұрын
Hey Dustin. I'm an electrician in the Bahamas and this is the best explanation I've ever heard explaining this. Now I will use this video as a teaching tool when I get in an argument pertaining to bonding. Thanks.
@rg8110
@rg8110 2 жыл бұрын
Which part of the 🇧🇸???
@tiggeroush
@tiggeroush 2 жыл бұрын
Just out of curiosity what electric code is used in the Bahamas?
@neilbarrow8110
@neilbarrow8110 2 жыл бұрын
@@rg8110 Nassau
@neilbarrow8110
@neilbarrow8110 2 жыл бұрын
@@tiggeroush Canadian Electrical Code
@ottoroth3066
@ottoroth3066 2 жыл бұрын
Neil Barrow.....does the NEC we have here in the states apply in the Bahamas.....just curious!
@john65645
@john65645 2 жыл бұрын
I'm a retired IBEW inside wireman. You do a very good job of explaining this. There's so much information that a good electrician needs to know to work in the field and that's why continued training is a must. It's good to be retired.
@lor332
@lor332 Жыл бұрын
Local 38. Congrats
@charu002
@charu002 Жыл бұрын
424 here as second year apprentice. i agree
@waynegroves6922
@waynegroves6922 2 жыл бұрын
I'm going on 69 now, and I've done a lot of DIY wiring in my life. These principles you're showing, I've known - instinctively - yet, never have I understood it so well as now. You've explained it in a way that made way more sense than every textbook I've read.
@uppercutshurt5199
@uppercutshurt5199 Жыл бұрын
Very true
@goedelite
@goedelite 3 ай бұрын
How many textbooks have you read on the subject of electricity?
@nobadmojo70
@nobadmojo70 2 жыл бұрын
Man, you've really elevated your teaching game, which is really saying something, your older videos are really good. This new generation of Electrician U is outstanding! It's very well organized, demonstrated, explained and marketed. Thank you again for all of your efforts and pushing through the challenges. Keep up the excellent work!
@robertdabicci317
@robertdabicci317 10 ай бұрын
Been wanting an explanation for the multiple sub panel bonding issue and this is the best information I have found. I knew you didn't want to bond except at the main panel but didn't understand why until now. Thank you for a great video. Bob
@lawbulb
@lawbulb 2 жыл бұрын
As a layperson, I didn’t understand any of this until I saw your presentation. I can’t possibly explain it to someone else like you did, but I really get a feel for how this stuff works now. Fascinating stuff!
@HarrisonFrith-cr4ie
@HarrisonFrith-cr4ie 10 ай бұрын
Something that is often not mentioned is that if neutral and ground are bonded, a broken neutral at any point before the bond will cause all grounds downstream of the bond to develop a potential of 120V relative to earth, as they are seeking to return to the neutral via ground having lost their neutral. This was touched on in the video but it warrants further explanation as to the theory. Only doing the bond in one place minimizes the amount of conductor that would create this condition if it were broken. If the service neutral breaks it'd be very obvious. But if a feeder neutral breaks to a subpanel feeding your garage, you might not notice until you touch it later and get a shock from the grounded components that are now 120V to earth!
@kellyschlumberger1030
@kellyschlumberger1030 10 ай бұрын
If just a neutral breaks you still have hots. The earth ground would trip the breaker. Since only the hots run thru breakers (neutrals don't) earth ground is the only thing to save your life. This feels like time travel. Maybe the professional will read this and help us all?
@HarrisonFrith-cr4ie
@HarrisonFrith-cr4ie 10 ай бұрын
@@kellyschlumberger1030 The neutral breakage at a point where neutral and ground are bonded will cause the ground to develop 120V potential, because the power wants to return to source via the ground bond as it cannot get through the broken neutral so travels through the bond to the ground instead. separated grounds/neutrals don't have this problem, so that's why they are always separated whenever possible
@memozzy22
@memozzy22 2 жыл бұрын
I haven't been watching lately but I'm so glad you've grown your channel so much!
@spruce_goose5169
@spruce_goose5169 2 жыл бұрын
16:18 I believe objectionable current is more in reference to neutral current (i.e. normal operating conditions) rather than ground fault. In other words, the issue is less ground fault current traveling on a neutral conductor and more normal operating current that should be solely on the neutral traveling on the ground (EGC).
@toddtaylor7136
@toddtaylor7136 2 жыл бұрын
This is correct. You don't want the normal neutral current flowing through the ground wires as they are not sized or intended for this purpose. The rest of the video was spot on. Nice job Electrician U
@traditionaltools5080
@traditionaltools5080 2 жыл бұрын
Absolutely right. You see it in three wire, three phase systems when people want to be able to get both line and phase voltages. So they use ground as a voltage reference. Bad idea.
@brianbray5397
@brianbray5397 Жыл бұрын
@@toddtaylor7136 Yes, It also means that you have return current on anything bonded, such as the panel itself.
@plehmann72
@plehmann72 Жыл бұрын
With no bonding between neutral and ground, you don't have earth fault current on neutrals , you just have no path to source neutral? Also, current isn't the direct danger, it's the voltage which can lead to defibrillation when your body's resistance allows current to flow through you and affect the hearts rhythm.
@spruce_goose5169
@spruce_goose5169 Жыл бұрын
@@plehmann72 having trouble understanding your question (or is it a statement?). If you had zero bonding anywhere in the system (which is not what we want), then yes, a ground fault would have to travel to source neutral (transformer) via the ground rod connections. Definitely not what we want and may not trip the breaker. That's why we bond. In one place. Bonding in multiple places simply means more system components will carry current when they should not be, potentially causing a dangerous situation.
@williammoyer9063
@williammoyer9063 2 жыл бұрын
Kudo's from a retired Union Electrician on being able to break it down so well. Keeping the grounds and neutrals separate greatly helps when trouble shooting, GFCI issues especially.
@godfaithfamilythenme
@godfaithfamilythenme 4 күн бұрын
I’m getting back in the trade after 17 years, these videos have helped me a lot. Thank you very much
@aaaaaaaaaaaaaa1674
@aaaaaaaaaaaaaa1674 2 жыл бұрын
I don't think evey8ne knows how much of a help you are!! Your such an amazing content creator appreciate your time man !!
@winstonwright3613
@winstonwright3613 2 жыл бұрын
WHOA!!! When Dustin's Beard be GROWING AN INCH IN HALF A SECOND .... I know some serious s***is about to go down!!
@motorheadplatt8748
@motorheadplatt8748 Жыл бұрын
It's like Pinochio's nose.
@rossroberts3212
@rossroberts3212 9 ай бұрын
This is the only video I have found that actually helps build the concept in your mind. Very nice! The only thing missing is the explanation of "Service Panel" being the first junction past the meter or equivalent as the place needing neutral to ground bonding, be it a service disconnect switch or main breaker panel inside of the structure. Bravo!
@johnkruton9708
@johnkruton9708 2 жыл бұрын
Your illustrations and explanations are the excellent educational visual along with Mike Holt’s very technical history and explanation about bonding. Eg: Factory motors, DC pulse (lightning) literally taking 120V line and putting to earth and measuring the current and seeing if a breaker will trip (it doesn’t)….your visuals complete the brain circuit!!!
@raymond3722
@raymond3722 2 жыл бұрын
Your topics always filled with clarity at its best,and your demonstration is on Q.
@Propnut48
@Propnut48 2 жыл бұрын
Thank you for all the info in your vid’s. The more I learn from you the more informed I am. I can do most things but in big projects I rely on bonded/qualified people to install it. That way I’m not the one at fault and liable . Keep ‘em coming. 👍👍👍
@user-je1zw7hd5k
@user-je1zw7hd5k 11 ай бұрын
I do a lot of diy wiring, I've always followed this as a rule but never fully understood why. This is the best visual explanation anyone could ask for, Thank you so much!
@chrisshort8821
@chrisshort8821 2 жыл бұрын
Fantastic video , I’ve learned so much since subscribing to your channel. Very much appreciated for your time and effort you put into theses videos. I’ve only been in the electrical field for the past 6 years and other then being told that the bonding jumper has to be removed in the sub panel through practice, I never had a clear understanding of the reason. This video provided a perfect explanation , thanks again!
@kevinb5717
@kevinb5717 2 жыл бұрын
I am so glad I found your channel. I'm sure your channel will hit 500k this year. You have an awesome way of educating us and thanks for taking the time to do it.
@pibblesnbits
@pibblesnbits 9 ай бұрын
This comment aged well.
@cetyl2626
@cetyl2626 2 жыл бұрын
I've had a great many fond memories with my son helping me with electrical work. He helped me with the wiring in the shop (a separate building), but we've really only bonded at the main panel.
@emoryjiles6411
@emoryjiles6411 Ай бұрын
This fellow brought up some key points about sub-panel wiring I never really considered. He is a gifted teacher. I’ll be tuning in for more. I’m a humbled 30+ year electrical engineer.
@elBusDriverKC
@elBusDriverKC 2 жыл бұрын
Great topic. I actually already knew all of this, but wanted to make sure there wasn't any gaps I needed filled in. You do a good job of explaining! On that note, please do a video on portable gas generators in relation to grounding, neutral, back feed dangers etc...
@dwightdhansen
@dwightdhansen 2 жыл бұрын
Same here. The Army cable installer course actually did a pretty good job of explaining this stuff.
@kennyhammond7087
@kennyhammond7087 Жыл бұрын
I’m sure you do bus driver man.
@trardo890
@trardo890 2 жыл бұрын
Great video! I always steer my classmates to your channel any chance I get when they have questions on things that i've seen in your video's... Some of our teachers don't have the field experience you have and your video's provide great examples! Keep up the great work! It is very much appreciated!!
@tomygun1585
@tomygun1585 6 күн бұрын
Thanks for the video. Too many don't understand that there's a difference between grounding and bonding. And remember, every wire is a fusible link. Cheers.
@mikecollins8241
@mikecollins8241 2 жыл бұрын
I am a General COntractor, with a good bit of electrical experiance, but have always been unsure about this particular topic. This vieos did a grat job of explaing/ illustrainig how it all works :)
@BigYankeeBlue
@BigYankeeBlue 2 жыл бұрын
Oh no, lolol, jk. Safety first 😁
@lakeshoreelectric
@lakeshoreelectric 2 жыл бұрын
Even though i already knew this, i still watched the video. Great job explaining this clearly, this channel is a great tool for apprentices!
@plaintiveplainvanilla9729
@plaintiveplainvanilla9729 2 жыл бұрын
Even just as a layman with a very basic understanding of home wiring, this explanation really laid it out for me. Thank you for the clarity.
@hvfd5956
@hvfd5956 5 ай бұрын
11/2023 - FYI there are two new Oncor substations being built right now in Hutto. I was amazed at how big the foundation had to be for the tall poles entering and leaving a drop station like these. One I saw must have been 18-wheeler truck sized. They built the frame one day, the next day it was dropped into the hole, and the day after that they must have bought out all the concrete in central Texas. The foundation now sites waiting on the pole to be put together. A friend of mine used to live in a long ranch style house in Bee Cave. I seem to remember he had a 700 AMP service off of his own transformer. That house had at least 4 sub-panels. It was a massive house. We were trying to work on a radio building down by the barn and the closest plug was up by the swimming pool. We quickly found out that whoever had installed the pool did not do the grounds right as we got a bit of a tingle when we hooked up this building. Fortunately, we figured it out and 20 years later, that building is still in use. Thank You for what you do. I always enjoy watching your videos.
@jeffgreen7897
@jeffgreen7897 9 ай бұрын
I enjoy your videos. I am from Colorado and I just hit 40 years in the trade. I love what I do and I love learning I am a service electrician after being on new construction projects for 20 years when I first got in the trade and I have learned so much. Troubleshooting is the best class ever.
@pistolgrips
@pistolgrips 2 жыл бұрын
Always interesting and informative. You make things easy to understand for those of us whose primary dealings with electricity is to turn on the light switch.
@45-308
@45-308 2 жыл бұрын
I like you videos and want to point something out regarding this topic. Perhaps you mentioned it but I didn't catch it. You seamed to focus on fault conditions when speaking about objectionable current. If you bond in a sub panel you with have objectionable current on the EGC in normal conditions because it will be in parallel with the neutral (grounded conductor) back to the main panel.
@spruce_goose5169
@spruce_goose5169 2 жыл бұрын
Exactly. I'm pretty sure what you speak of is generally what 'objectionable current' refers to: current on the EGC under normal operating conditions.
@ElectricRob
@ElectricRob 9 ай бұрын
Nice explanation and your sketches really help to visualize the current flow thru the distribution system. One thing I'd add is that your examples mainly deal with fault conditions (short circuit and ground fault), but even during normal operation on for example a 120V load, if ground and neutral are connected at two ends, you just made the neutral a parallel set of conductors (neutral and ground in parallel), so current flows on both wires, and as you noted, we normally do not want current flowing on the ground wire (except in ground fault situations).
@fredsasse9973
@fredsasse9973 6 ай бұрын
Yes! Current does not only take the path of least resistance, it takes ALL paths. Granted, the current flowing through the path of least resistance will be higher than the inverse proportion of the level of resistance of the alternate path(s).
@pontspontbriand7723
@pontspontbriand7723 Жыл бұрын
Wow. Hvac tech here. I went down the rabbit hole on this channel from a completely different project I’m doing, and I’m amazed at how quickly I verified some of my questions about electricity and bonding. Super great video. And free ta boot. Wish I had access to you tube when I was early in trade. Great, great, videos. Liked and subscribed.
@NoName-OG1
@NoName-OG1 2 жыл бұрын
After having watched this, I have two comments. First connection of a neutral to ground anywhere outside of the main electrical service, is also considered a “ground fault“, not just hot conductors. It is technically any current carrying conductor with a connection in advertently to ground. If you have not already done an episode on how a GFCI works, it measures current going out, and then returning, and if there is a significant difference, it will trip. Indicating that there is current traveling on another path. The other comment, is somewhat mind blowing if you wrap your head around it. The neutral at a transformer it’s always going to be a current current conductor. Meaning that it’s always going to be varying at potential. When grounding it, you are not necessarily bringing the neutral conductor to the potential of earth, you are bringing the potential of the earth in the general area, to its potential of the neutral. Bringing them both closer together. The neutral, a.k.a. the grounded conductor, and your electrons of an area are brought to the same potential. This is yet another reason not to bond ground and neutral in subpanels in exterior buildings. Like a detached garage. And this is why metal piping systems are also brought to the same potential in each structure. Having a parallel current throughground, would have a voltage offset from that of the electrodes of the building. And while that may be minor, that still represents a hazard.
@donphillips5957
@donphillips5957 2 жыл бұрын
Question. An exterior panel with a main breaker in a separate box above it. Is it OK to have the ground to earth connected to both? Neutral is bonded only in the main panel.
@NoName-OG1
@NoName-OG1 2 жыл бұрын
@@donphillips5957 your main disconnecting means and/or meter enclosure is the only place to which the MBJ main bonding jumper is to connect neutral to ground…. This is also where your electrodes (connection to earth would connect in the United States) - to the neutral. These are what grounds the grounded conductor (aka neutral). Grounds from any other feeder or branch would follow the circuit paths along the same circuit paths as the current carrying conductors. So - other than the case of separate structures electrodes should connect to the main enclosure. And to the sun panel only in cases of separate structures. Like if you had a detached garage or pool house or shed that had a panel - the grounding electrodes should go to the panel serving that building. But not neutral to ground connection in that separate building. (At least since about 96)
@Yo-Yo888AA
@Yo-Yo888AA 2 жыл бұрын
@@NoName-OG1 I have a detached garage with its own panel (100A main breaker, 1- 30A 220, and 4 15A 110 breakers) I have a 3 wire, direct burial cable supplying 240v from my main 200A service panel. The garage panel is grounded to earth through its own ground rod. Should my ground and neutral be bonded in this panel?
@NoName-OG1
@NoName-OG1 2 жыл бұрын
@@Yo-Yo888AA up until about 1996 it could be. And after 2008, it was definitely illegal… After that all new installations would have grounding conductor with the feeder from the the garage from the main panel to the panel at the garage AND ALSO have a ground rod at the garage. But no neutral bond at at any subpanel. Even if it’s a separate structure after 2008. (Post ‘96 you would also have a grounding conductor for ranges and dryers be separate) The philosophy of grounding and bonding changed in that year 1996, and the years following continued to catch all the places in the code that missed being updated by 2008. To separate “fault current” and “unbalanced load current” into separate and distinct paths. So as not to have “Objectionable current” Each separate structure is required to have an “grounding electrode system” for that structure. Rods, concrete encased electrodes, and pipe systems bond to the electrode system. Those are bonded to the panel serving the structure. “Grounding conductors” are connected to that electrode system - to include those between structures. As branch equipment grounding conductors and feeder grounding conductors. Branch and feeder - Neutral conductors (AKA GROUNDED CIRCUIT CONDUCTORS) carry unbalanced load current, and as such have different electrical potential depending on where they are in the system. And should not have parallel paths on equipment cases or exposed metal boxes or anything else. This would be “objectionable current” And if bonded in multiple places would make the ground-ing conductors a parallel path for the current. Or conversely the neutral a parallel for fault current. “Objectionable” So the decision was made to make them completely separate apart from a single point at the main/meter panels. So that only fault current is on the grounding conductors, and only unbalanced load current is only on the neutral. So if your garage was built prior to 2008 it’s ok for the thinking of the time. And you may even lack a grounding conductor between structures and you would have the bond neutral to ground to have any ground fault path at all. And most inspectors would have you correct it if there were new construction in the garage for a new panel. If it was after 2008, it’s a code violation to bond neutral to ground in a separate structure. And a violation to not have a grounding conductor with the feeder to a separate structure. Hope this makes sense of the how and why…. If not look for “Mike Holt grounding - separate structure - fault current” and you’ll likely find an image depicting this with an explanation of reasoning. Or search “objectionable current separate structure NEC” or 250.32 in your code book.
@Yo-Yo888AA
@Yo-Yo888AA 2 жыл бұрын
@@NoName-OG1 so when you say grounding conductor feeder from main panel to garage your basically meaning a 4 wire set up? 2 hots a neutral AND a ground? Plus also need the ground rod which i have? Btw it was built before 96 and have had no issues and plan no other construction. But if there is a better/safer way ...
@notreallyme7465
@notreallyme7465 Жыл бұрын
I had a panel that the power would go way high then low whenever it wanted to. What I found was a loose neutral buss bar. Everything was loose. So, it would find different routes to neutral. The lights would get really bright and the picture on the TV would get bigger and smaller. Proves why you don't want things going through wrong places. Very well explained as always. Thanks
@Ibuildit2817
@Ibuildit2817 Жыл бұрын
Just came across this while checking out videos and this is by far one of the best videos I've ever seen! Excellent work.
@michaeldunn9018
@michaeldunn9018 2 жыл бұрын
1st year apprentice here, thanks for taking the time to make these easy to understand and simplified videos Dustin!
@LTVoyager
@LTVoyager 2 жыл бұрын
Maybe I missed it as I had a couple of interruptions while viewing, but I didn’t hear probably the most significant issue and that is the return current path during normal operation. I heard you mention a short to ground fault and a short to neutral fault, but not normal operation. If the dryer is operating normally with no internal faults, but you have the neutral and grounding conductors bonded at the sub panel farthest from the service entrance, the return current on the neutral will divide at the sub panel and now the “normal” return current will travel the rest of the way on both the neutral AND the grounding conductor all the way back to the service entrance. The current proportion will be based on the resistance of the neutral and the grounding paths, but likely will place substantial current on the grounding conductor. That is probably the biggest reason not to bond subpanels. Yes, the two fault conditions matter, but having current on the equipment grounding conductor during normal operation is the most insidious issue of all.
@bryanduchane2371
@bryanduchane2371 2 жыл бұрын
Absolutely correct and not many licenced electrician know that. What I've never got a good answer from anyone is why they require oversized neutral conductors??
@LTVoyager
@LTVoyager 2 жыл бұрын
@@bryanduchane2371 I thought this had been changed some time ago. This reference says in 2008. Since I’m retired, I no longer have access to current NEC documents. “This is fully recognized in the latest (2008) edition of National Electrical Code. Specifically, Article 310.15(B)(4) addresses the question "Should Neutral Conductors Be Oversized?". Noted is that "for NEC editions up to and including the 2005 Code, the neutral conductor ampacity was usually 125% of the maximum continuous current allowed by the overcurrent device." This is immediately followed by: "Revised for the 2008 Code, both 210.19(A)(1) and 215.2(A)(1) include a new exception that permits a branch circuit or a feeder neutral conductor to be sized differently. The sizing is now permitted to be 100% of the non-continuous load plus the continuous load, thus permitting a reduction in a neutral conductor size (calculated from previous editions) by as much as 25%."
@bryanduchane2371
@bryanduchane2371 2 жыл бұрын
@@LTVoyager From what I remember from my 25yrs in the Electrical Distribution business, I think an oversized neutral had something to do with harmonics and the use of digital equipment in a facility. This popped into my head as I was reading your reply. Only been out of the business since 2015 and the old saying if you don't use it you lose it couldn't be more true. I could easily get back in the industry, but would have a steep learning curve to learn all the new technology that has been released since 2016..... Loved the industry. Met some of my best friends through it.... It's a very rewarding career.
@LTVoyager
@LTVoyager 2 жыл бұрын
@@bryanduchane2371 I’m a retired EE and I don’t remember any discussion of the need for a larger neutral or related harmonics issues and I was going to school in the last 70s and early 80s. I always figured it was just an error carried forward from people who didn’t understand the phase relationships in AC and thought you had to add the currents from the two hot conductors as though it was DC. I never knew the history there.
@motorheadplatt8748
@motorheadplatt8748 Жыл бұрын
@@LTVoyager The harmonics are caused by many PC's in the same building and on the same transformer using high frequency switching DC power supplies. This problem didn't occur until around 1990.
@inuyasha333k
@inuyasha333k Жыл бұрын
Great video! I can not tell you how many times I watched one of your videos and things I was learning all clicked together! Thank you so much!
@HollandIdeas
@HollandIdeas Ай бұрын
Thank you! great explanation for someone like me who wants to do some work on my home but didn't really understand the bonding at the service but not on the sub-pannel. I have a mobile home that has a sub-pannel in the house that was built in by the manufacturer and a service panel outside the house on a pole. I plan to move the service to the other side of the house and take the service underground to the house. I plan to do the work myself and this was very helpful.
@michael.a.covington
@michael.a.covington Жыл бұрын
16:04 That is the key point: If the bond occurred downstream of the service entrance, a ground fault would elevate the neutral (raise it above ground voltage) from the bond all the way back the service entrance, causing incorrect and possibly damaging voltages all along the way.
@d46512
@d46512 4 ай бұрын
That would be bad. Meanwhile, if a neutral wire becomes loose on any circuit, the ground potential throughout the house would be raised. A very dangerous type of fault.
@ScrewThisGlueThat
@ScrewThisGlueThat 2 жыл бұрын
Dustin... keeping with the sub-panel subject, can you please answer this question... "Can you add an additional ground rod at the sub-panel?" I ask because in a previous build I had a detached garage about 150 feet away from the main panel and the inspector had me add an additional ground rod to the sub-panel in the detached garage. Thanks and I hope you can answer and explain.
@electricalsociety5593
@electricalsociety5593 2 жыл бұрын
Yes it is required. its better to install a ufer ground but if the garage foundation is already poured then you need to install a ground rod. 250.32 (a)
@rcmrcm3370
@rcmrcm3370 2 жыл бұрын
Assume you only bonded the case, and not the neutral to that sub-panel, it's protection so grounding would still cause ground fault trip on GCI, but you don't bond neutral on sub-panel. Bonding neutral in two points creates circulating current, not good.
@taylorlightfoot
@taylorlightfoot 2 жыл бұрын
Separate ground rods are required for separate structures. Since your garage was detached, it's sub panel (fed from the house) needs it's own ground rod too. This is because ground rods have nothing to do with providing a place for fault energy to flow to; fault energy wants to return to the source, which is the transformer, not to the ground. Ground rods exist solely for lightning strike protection and if your garage was struck by lightning and didn't have it's own ground rod, the energy from the lightning would travel down the ground wire that goes back to the main house and you'd melt every other wire in the conduit between the house and garage.
@motorheadplatt8748
@motorheadplatt8748 Жыл бұрын
@@taylorlightfoot Electrical service grounding has nothing to do with lightning protection, it's for personal safety. Lightning rods and wiring are intended to keep lightning out of your building by providing a path to earth.
@MrTouchstone86
@MrTouchstone86 2 жыл бұрын
Just found your channel and I'm working through your Playlist. I work around electricity daily and try to educate myself for troubleshooting purposes. (Fuel Dispensers/pumping systems). (I let the electricians handle anything I'm not 100% confident with) I would be considered a novice and I can say you presented material in a way that is digestible and It "clicked" for me at ~13 minutes with that 4 panel picture. I can see you've come a long way since your first few videos. Keep up the great content!
@danwahl5231
@danwahl5231 Жыл бұрын
Thank You, I watched a lot of videos about this topic, and this was a great explanation. I was about to use a ground as a neutral wire, because I knew they were hooked together in the main panel anyway, but now that I know how this is supposed to work, I will pull the extra wire and hook it up correctly. Thanks for helping me understand why my idea that would have probably functioned is better off being wired as intentioned even if it’s going to be a lot more work for me.
@roadie193
@roadie193 2 жыл бұрын
Thanks man! Great vid. I have heard this rule but didn’t know why. I’m starting to work on panels lately so this was very good info to know
@MyClutteredGarage
@MyClutteredGarage 2 жыл бұрын
This is still confusing to me, but the example with multiple panels really helped a lot! I'd probably have to do or see an actual exercise/install from start to finish. Maybe you can do a benchtop demo?
@Gary-ts6dh
@Gary-ts6dh Ай бұрын
1:57 - Good save! I had a "discussion" with the instructor in apprenticeship class back in the day over this very topic. The grounded conductor carries juice all the time; the grounding conductor only carries juice in the event of a fault.
@graciemiller9596
@graciemiller9596 10 ай бұрын
Thank you very much Dustin for explaining that subject so clearly. It was such a simple explanation for me to understand. Thank you.
@ClericChris
@ClericChris 2 жыл бұрын
I'm interested in the theory when a generator is used. Has there been a video on that. I've found your videos most helpful.
@paaao
@paaao Жыл бұрын
You bond the ground and nuetral at the source, and anywhere power is transformed. So in the case of a generator, it is the source of the power. You want any equipment fed from it, to have a path back to it, not back to the house service ground, aka the utility's ground. Ideally, a generator used to feed a house in the event of say, a power outage, should have a means of disconnecting and isolating from the utility. ATS switch, or manual means to avoid backfeeding the utility in the event of a fault, or open. The utility grounds out all the lines prior to working on them, and sometimes in certain blackout situations. Homes running generators that are hooked up improperly, back feeding, or even sharing/referencing the utility neutral/ground, usually burn up pretty fast in these situations. The utility feeds your meter with 240V hot/hot, and brings a ground/neutral wire by center tapping the transformer. This center tap is their bonded neutral/ground. It is directly in the center of the 240V windings, which is why each leg to neutral/ground provides 120V.
@vtgoldprospector
@vtgoldprospector Жыл бұрын
@@paaao Typically in whole home generators there will be a transfer switch that takes the place of the main panel. This transfer switch should be rated as "service rated" meaning that it has a main breaker (not an ordinary breaker). The main bonding jumper that connects the neutral and ground is located here which was previously located in the main panel. Since there can be only one bonding jumper, the existing main panel should be updated as a sub-panel so that all grounds and neutrals are separated, the main bonding jumper removed and the neutrals landed onto an isolated bus bar. The wire that was between the meter and the main panel should be replaced to now connect the transfer switch to the panel and will have an extra conductor for the ground, which it previously did not have coming from the meter. This is the difference between an SEC (service entry cable L1-L2-N) and an SER (service entry riser L1-L2-N-G).
@kinterest1562
@kinterest1562 Жыл бұрын
​@@paaao watch Mike Holt videos. Grounding and Bonding at the generator is dangerous!
@joe72205
@joe72205 2 жыл бұрын
Other than the fault concern, the bond at the subpanel will mean any load downstream will return half its current over the EGC to the main panel even during non-fault situations (IOW, all the time). And since conductors carrying current develop a voltage drop, all the EGCs from that subpanel will be a few volts above earth potential - or fully energized if the main GES bonding is damaged.
@zm6301
@zm6301 2 жыл бұрын
If the bonding is damaged then current on the ground should be very low as the only path back to the source is between grounding rods at the panel(s) and the utility pole. The only way the ground would be energized is if the neutral is cut somewhere between the panels and you disconnect the ground while power is still on, anything upstream would get energized, anything downstream would not be. Bad news if you happen to be holding the ground wire on the now "hot" side and/or if you're standing in a puddle near a grounding rod. I'm sure people have gotten injured or killed this way and thus it gets written into the code, usually how it works.
@mrnade333
@mrnade333 2 жыл бұрын
Wow! Eye opening! All about trying to keep us and the system safe! Thanks so much! Could you do a part two about bonding pools and show the potential around them!? Thanks again! Keep up the good work!
@ChadCourtneyTAZ427
@ChadCourtneyTAZ427 2 жыл бұрын
In short all sub-panels have their neutral bonded to ground via the main panel. But adding extra bondings at the sub-panels creates dual pathing between main and subpanels for a return path which will result in current on the ground, which is bad.
@CybekCusal
@CybekCusal 2 жыл бұрын
No. Bonding occurs at the service termination not the main panel. Don't give advice if you don't know what you are talking about.
@wim0104
@wim0104 2 жыл бұрын
in recent years, we now see more panels/pans that combine the meter and the service termination in one box, the first panel(s) fed from that would be the main panel(s). the neutral+grounding bond has to be where the service is being terminated/landed. So that might NOT be in the panel you're thinking of. Just remember to never turn a grounding conductor into a neutral with a rogue bond: an energized grounding system is extremely likely to shock people, because the grounding system is bonded to everything: plumbing, metal enclosures (washer, drier, heating,...), metal cages of fixtures, chandeliers etc... ppl will be touching it.
@rthinds
@rthinds 2 жыл бұрын
@@CybekCusal He knew what he was talking about. Bonding occurs at literally every main panel, which is "service termination". Duh. You said exactly what he said. Please re-read it again before commenting again. Mmmkay?
@RusredGuTH
@RusredGuTH Жыл бұрын
You and other electricians that do vids like this are blessed with wisdom and the love for others is appreciated. Thanks for being awesome 😎. I’m well on my way to being an apprentice that knows his sh** before I even get an interview
@michaelballinger4185
@michaelballinger4185 2 ай бұрын
Great lucidity and clarity. Thanks!
@shelbymurphy7864
@shelbymurphy7864 Жыл бұрын
this was super helpful!! Taking a home inspectors class and their videos just do not explain well what I'm actually looking for inside an electrical box. The diagrams were extremely easy to understand and I feel significantly more confident in my little knowledge lol
@jamiestarr1022
@jamiestarr1022 2 жыл бұрын
Great video. I have watched a number of other videos trying to explain this concept and I always leave scratching my head. Your video was very informative and explained this topic well for a non-electrician. Based on what you said this applies to all sub-panels down the line correct? I ask because I want to check the sub-panel installed for my swimming pool equipment (that is next to the pool) and make sure the neutral and ground and NOT bonded there. Thanks again Dustin.
@taylorlightfoot
@taylorlightfoot 2 жыл бұрын
Yes, ALL sub panels, even if on separate structures or out in the garden by the pool. You're only allowed to bond Neutral at the first disconnect for the electrical system. There are exceptions if you have a house wired before old three prong dryer or cooktop/oven, those will have neutral and ground bonded together at the appliance. The 1996 NEC mandated these branch circuits be 4 wire to include separate ground to avoid bonding, the exemption exists for homes built prior to this.
@clermontglock
@clermontglock 2 жыл бұрын
Question: Home has 400 amp service with a 200 amp main service panel (bonded) and a 200 amp sub panel service (NOT bonded). An electrician recently installed two Eaton CHSPT2ULTRA surge protectors, one in main service panel and one in sub panel service. Wiring for main service is per the surge protector installation instructions, Red/Black to 50 amp breaker, White to neutral bar and Green to ground bar. The wiring for sub panel is Red/Black to 50 amp breaker, and BOTH the White and Ground to ground bar. Also per surge protector installation instructions regarding LED's, it says "Protected when both lit". Both LED's are lit in main panel but have noticed that sometimes the sub panel has both LED's lit and sometimes only one LED is lit. Question: Is the surge protector in the sub panel wired differently with White to the ground bar because it is a sub panel and NOT bonded (neutral and ground are separated)? Or is it wired incorrectly?
@Mark-ev8qb
@Mark-ev8qb 2 жыл бұрын
Thanks. Great explanation. When we had a Whole House Generator installed, and the outside Change over panel became the Main Service Panel and the 200A garage Circuit Panel, he isolated ground from White Return. Now I understand Why! Again, Thanks, Great Explanation! Mark
@djaztec97
@djaztec97 Жыл бұрын
Your drawings help me visualize what's really happening in the circuit. Better than someone trying to talk without drawings, and I have to picture what's going on to understand.
@frankcarone3657
@frankcarone3657 Жыл бұрын
If you bond the grounding conductor at multiple points, you also create a current differential across those points, so your grounding is no longer at one potential and there is current flow across the bonded (grounded) metal parts. This mean you could get a shock by, let's say, touching the metal on your laundry machine even though everything is working fine and there is no short.
@asmoore82
@asmoore82 5 ай бұрын
Yep, there are so many bad videos telling people the wrong info on connecting a hot tub. Hot tubs are required by code to have a GFCI shutoff near the tub itself so are a small subpanel in every case. If you bond neutral and ground on that hot tub panel then you have a parallel loop back to the main panel and electricity is a self-leveling force of nature. If your hot tub is drawing 120v and 2 amps, then you absolutely have roughly 1 amp on the ground leg and 1 amp on the neutral leg of that parallel loop at all times. The hot tub can draw 240v 10+ amps for its largest pumps and heaters and you are safe from that because it bypasses neutral, but all of the control boards, lights, speakers, and smaller pumps might run on the 120v. The GFCI won't trip because it can only protect downstream and the parallel loop is upstream from it. Everyone using the hot tub is relatively safe, but the house is now a danger for any other electrical work.
@okaro6595
@okaro6595 4 ай бұрын
No, you would not get a shock unless the wires broke but it could cause stray currents that cause problems with AV and IT equipment. For you to get shocked there would have to be loss of tens of volts in the wires. Such a system would just not work. For some reason people need to make things too dramatic, as if you die if some rule is broken.
@ryanmoran1188
@ryanmoran1188 Жыл бұрын
Why does your illustration show a separate ground coming from the transformer and feeding the Main service panel? You should have only your 2 phases and your grounded conductor.
@jamescameron2969
@jamescameron2969 18 күн бұрын
There is a ground coming from the transformer as well. It’s the bare wire.
@ricardofonseca1537
@ricardofonseca1537 12 күн бұрын
Could be a cold water and ground rods wire
@bryannorris
@bryannorris 6 күн бұрын
Truth!!
@waynepowell567
@waynepowell567 Жыл бұрын
Excellent. My Dad was an Electrician back in the day and he would approve, Thanks for sharing. Be safe, Man.
@brianc9210
@brianc9210 Жыл бұрын
Best explanation I have seen. Checked my garage panel and it was incorrect. I fixed it. Thank you.
@dwmcever
@dwmcever 2 жыл бұрын
So, my question is does the Sub-Panel Metal enclosure need to be grounded to a ground-rod. If the Ground bar is electrically attached to the Sub-Panel Box and is grounded by wire to the Main Box does that count as ground? In same bldg or in remote bldg? Think your readers might be interested in this.
@yandr4life1
@yandr4life1 2 жыл бұрын
Full disclosure: I'm not an electrician, but what he has explained is you always want to go back to the source of the power, your service panel, where it is grounded with a rod. Any feeds off that panel, regardless of location, always goes back to the original source. But I could be wrong..
@dwmcever
@dwmcever 2 жыл бұрын
@@yandr4life1 I was looking to an Electrician for the answer. One current on the Code. My code books are out of date. As am I. ;-)
@0pinion0lympics
@0pinion0lympics 2 жыл бұрын
10-210 Grounding connections for solidly grounded ac systems supplied by the supply authority (see Appendix B) The grounded conductor of a solidly grounded ac system supplied by the supply authority shall a) be connected to a grounding conductor at one point only at the consumer’s service; b) have a minimum size as specified i) for a bonding conductor; and ii) for a neutral conductor when the grounded conductor also serves as a neutral; c) be connected to the equipment bonding terminal by a system bonding jumper; and d) have no other connection to the non-current-carrying conductive parts of electrical equipment on the supply side or the load side of the grounding connection.
@KevinCoop1
@KevinCoop1 2 жыл бұрын
@@dwmcever Would a retired electrical design engineer 35 years on the job work for you? If so, if the sub panel is within the same building, then wired exactly as Dustin showed on objectionable current diagram. If a feeder is run from one building to another building, still separated, but a Grounding Electrode Conductor (GEC) and Electrode(could be ground rod) is required. Please be aware that the “To Earth” connections (ground rod) has absolutely nothing to do with this video. Electrodes(ground rods, metal pipes in grade, re-bar in concrete, etc) are connected to electrical systems to dissipate surges and lightning strikes. Nothing to do with ground faults. BTW, feeding other buildings from one building grounding, flip flopped back and forth several times in the 70’s thru 80’s. Hope this helps.
@BillC-64
@BillC-64 2 жыл бұрын
The ground for a sub panel is equipment ground. The ground rod is for the earth grounding system - for a path for lighting or static electricty. They are two different things.
@taylorlightfoot
@taylorlightfoot 2 жыл бұрын
Good info, not the clearest for people just learning though. Your first diagram showed a ground going up with the service wires, we don't get a ground wire from service. ground rod is only there for lightning, you can just say that, showing the neutral midpoint of the washing machine motor is confusing, makes sense for service transformer. You could touch on the fact that ground wires are sized smaller than neutrals and if we have a parallel path, we could overload the ground wire with current meant for the neutral wire, etc.
@timg6850
@timg6850 2 жыл бұрын
1) "Your first diagram showed a ground going up with the service wires, we don't get a ground wire from service." : Yes you do as the Earth (Ground) is shared with the Neutral wire from the Transformer until it gets to your Main Panel where its separated into the Earth (Ground) and Neutral wires. 2) "ground rod is only there for lightning" : This is incorrect the Earth (Ground) rod makes sure the Neutral wire is at Earth potential (0 Volts). If the Neutral wire is not at Earth potential it is possible, likely even, for it to rise to Mains potential. 3) "showing the neutral midpoint of the washing machine motor is confusing," : What he was trying to show there was the Fault current dividing along the Neutral and Earth (Ground) wires if the Sub panel was incorrectly wired. If the fault current does this the circuit breaker may not trip. 4)"if we have a parallel path, we could overload the ground wire with current meant for the neutral wire, etc." : That has nothing to do with the point he was trying to get across which is the Earth (Ground) wire should only carry current when there is a Fault. This is ensured by making only one connection between the Earth (Ground) wire and the Neutral wire at the Main Panel.
@spruce_goose5169
@spruce_goose5169 2 жыл бұрын
The first diagram is showing the Grounding Electrode Conductor (GEC) - the wire to the ground rod - not a ground feed from service.
@spruce_goose5169
@spruce_goose5169 2 жыл бұрын
@@timg6850 "the Earth (Ground) rod makes sure the Neutral wire is at Earth potential (0 Volts). If the Neutral wire is not at Earth potential it is possible, likely even, for it to rise to Mains potential. " This statement doesn't make total sense. Mains potential referenced how? If ungrounded, a system would have indeterminate potential (voltage) to ground. There would be no path for mains current to flow through someone or something to ground, thus 'mains potential' would not really exist. Taylor is correct that the earthing helps to dissipate static charge, though all the reasons to earth a system (or not) is certainly complicated.
@timg6850
@timg6850 2 жыл бұрын
@@spruce_goose5169 "This statement doesn't make total sense. Mains potential referenced how?" If the Neutral wire loses its connection to the Earth Rod, via the connection between the Earth (Ground ) wire and the Neutral at the Main panel, then the Neutral can rise to Mains potential because it is connected in series with the Active (Hot) wire at the outlet. By connecting the Earth rod to the Neutral wire you ensure that ithe Neutral is at Earth Potential (0 Volts) and therefore will not rise to Mains Potential.
@timg6850
@timg6850 2 жыл бұрын
@@spruce_goose5169 "The first diagram is showing the Grounding Electrode Conductor (GEC) - the wire to the ground rod - not a ground feed from service." Yes, it is a poorly drawn diagram as to make it clear he should have only had the Earth (Ground) wire going from the Earth Rod to the Main Panel. Until the Neutral wire gets to your house it acts as a combined Neutral and Earth (Ground) wire. What the first Diagram is showing is the Combined wire from the Transformer being separated into a Neutral wire and a Earth (Ground) wire. The Earth Rod connection to the Neutral wire at the Main Panel makes sure the Neutral stays at Earth Potential (0 Volts) inside your home.
@davidguzman8243
@davidguzman8243 2 жыл бұрын
You're videos are some of the best on KZbin, thanks I've really learned alot from you.
@D70340
@D70340 Жыл бұрын
An amazing explanation. Best i`ve seen to date! I do my own electrical wiring, i didn`t learn anything new here, but this will help so many that do not understand, and why this is so important, and it is very clearly explained.
@jimmckinley8110
@jimmckinley8110 2 жыл бұрын
If a neutral is bonded to ground anywhere in the house, current could travel on the green bond wire or any metal bonded to ground in the house, back to the neutral in the service panel during normal operation. This can cause shocks when 2 metal parts are touched.
@jasongayman3994
@jasongayman3994 Жыл бұрын
Exactly! We want our metal panels and equipment chassis to be at earth ground (0V). Wiring has resistance just like the loads they drive. And while we would like for there to be zero voltage loss, some has to be tolerated until we can find an affordable way to wire buildings with superconductors. In a 120V world, the neutral can develop a slight potential difference from earth ground the further it is away from the main panel. That's fine and acceptable. However, if a sub located on the other side of the building bonds the ground and neutral, now the neutral will also be at a non-earth potential. And while the voltage may not be that much above/below earth ground, depending on the situation it could be enough to introduce hydrolysis (accelerated corrosion essentially of all exposed metal parts that may find a slight path to ground) and other undesirables.
@kellyweaver8422
@kellyweaver8422 2 жыл бұрын
If you bonded your ground and neutral at both the main and sub panel and you have a fault on a 120 volt circuit then you could get 120 Volts on the neutral. So ALL of the 120 volt circuits that are feed from the other hot lead will have 240 volts on it instead of 120 volts. Which could cause additional equipment failure and cause more faults as well as destroying equipment.
@taylorlightfoot
@taylorlightfoot 2 жыл бұрын
This would not happen, but even if it did, it would be short lived as the breaker will trip nearly instantly. The main problem is parallel paths and current intended for the neutral will also flow through the ground wire. We size our ground wires smaller, so there's an opportunity to overload it if we have parallel neutral paths and this can cause a fire.
@htseb
@htseb Жыл бұрын
This is the answer I was looking for. If a fault happens, then my 120v toaster would make my sliced bread too dark. [A parallel path to neutral is actually good because it splits the current between the two wires.] It's the voltage, not the current that is the problem.
@thewhitefalcon8539
@thewhitefalcon8539 Жыл бұрын
That's called a lost neutral, sometimes it happens to people's whole houses, and it has nothing to do with bonding neutral and ground at subpanels.
@TheTubejunky
@TheTubejunky Жыл бұрын
@@thewhitefalcon8539 correct!
@scottgarner2701
@scottgarner2701 2 жыл бұрын
Great video - I really like how you explain things - one very important detail I would like to add. Imagine a 50-amp GFCI circuit breaker installed in the main panel where the ground-neutral bond can (should) be found. Now imagine a sub panel supplied by that 50 amp beaker, except that there also has a ground-neutral bond in the sub panel. The 50 amp GFCI breaker will always think there is a ground fault and trip. So no GFCI or similar safety devices will work if there is a downstream ground-neutral bond. Thanks for listening and good luck!
@k20in321
@k20in321 2 жыл бұрын
in all my years ive never had this explained like you did! Thank you!!!!
@jesusm8081
@jesusm8081 2 жыл бұрын
Nice explanation. Also to add even if there is no fault. Bonding at a subpanel creates a path for your neutral to travel back to the main pane / transformer through ground. Keep up the good work.
@yren3386
@yren3386 Жыл бұрын
Pointing out one thing: In most SFH, there's no ground conductor coming from the service. Ground is provided on premise by the ground rod. And that's why you need bonding: because ground bar alone doesn't provide enough fault current. If there was a ground conductor provided by the service (for example many commercial buildings have a shared ground across the building) bonding is not needed, because that ground conductor provided by the service provider is a good enough low impedance path back to source. You can still ground the service-provided ground again on-premise, there's never too many grounds on ground wire. BUT don't bond it with neutral again, there can be only one bond.
@Wheel_Horse
@Wheel_Horse Жыл бұрын
I noticed that also. In the first graphic he's showing FOUR wires from the pole... typically there are only THREE. The two HOTS and the NEUTRAL. As you say, the GROUND ROD is at the service entrance.
@jamesporter7979
@jamesporter7979 Жыл бұрын
I stumbled on this video by mistake but seriously impressed. Now I'm going to check out your other vids.
@enriquerodriguez2451
@enriquerodriguez2451 Жыл бұрын
Thanks it’s perfectly clear I needed that wisdom to keep safe
@Wrenchen-with-Darren
@Wrenchen-with-Darren 2 жыл бұрын
Great video... now, PLEASE, PLEASE, PLEASE, do a vid on grounding rods. I've been told more than a 1000 times, to put grounding rods at every building. Here on the farm we would NEVER do that ( I know, farms are different ) because of potential "stray voltage". And, what does NEC say about multiple grounding rods? Thanks SO much.
@jim_locks
@jim_locks 2 жыл бұрын
Same. I've read that you should have a grounding rod at a sub panel. I'd love a video explaining that.
@Wrenchen-with-Darren
@Wrenchen-with-Darren 2 жыл бұрын
@@jim_locks read? Last I knew. N.E.C. 250.52 (A) (5) talks about grounding electrodes. I believe, there can only be one per service.... per N.E.C. but, I've had inspectors require more????
@Blahblahblah8016
@Blahblahblah8016 2 жыл бұрын
Yea , are grounding rods primarily for lightning? Or what else are they for? How many do you need, where and why? I think a video focusing on grounding rods would be nice!
@45-308
@45-308 2 жыл бұрын
Most electrical systems require a grounding electrod. The NEC generally requires all grounding electrodes be connected together, "bonded". A building may have more than one grounding electrode available, the water main and the rebar in the footing. If you may need to add a grounding electrode if there is not one available such as in a pole barn. The most common way to do this is with a driven rod. "Ground rod" The NEC says if you have 25 omhs or less resistance on this connection to the earth one electrode is sufficient. If you have more than 25 ohms resistance a second electrode is required. So the common practice is to add a second rod instead of trying to prove you have less than 25 ohms of resistance. The connection to the earth gives you electrical systems a reference to earth and helps stabilize the difference in potential between your electrical system and earth. It also creates a path to earth for any electricity the was induced on to your system that doesn't belong there.
@Wrenchen-with-Darren
@Wrenchen-with-Darren 2 жыл бұрын
@@45-308 that helps, thanks. It gives the electricity multiple paths back to the main panel, if there is a ground fault... wait, we don't want that???? I give up.
@electricalron
@electricalron 2 жыл бұрын
A: Because we don't want a parallel path specifically for fault current (to clear a fault, faster, much faster).
@psywiped
@psywiped 2 жыл бұрын
Because you don't want to create a ground loop that can have current induced by a magnetic field.
@electricalron
@electricalron 2 жыл бұрын
@@psywiped A ground loop?
@michaelbourassa2379
@michaelbourassa2379 7 күн бұрын
Thank you it's really unbelievable to me that you have to explain that. Even though you made it so simple to understand people are still having a problem with it. That's what I don't understand. But I see so many messed up panels that aren't done right.
@BettyBooty
@BettyBooty 5 ай бұрын
This video just cleared up so much mind fog that was clouding my understanding... Thank you dearly for your talent 👏👏👏🙏🙏🙏👍👍👍
@SK-yw5ih
@SK-yw5ih 2 жыл бұрын
The reason you dont want bonding in the sub panels is that you dont want REGULAR current from the white wires travelling on the grounding (green) conductors, because those are supposed to be at zero volts except they are to carry current under fault conditions, as that is what keeps you safe in the event of a fault. THAT is what they mean by objectionable current. If the green or bare bonding (grounding) wires are carrying current under normal conditions because they are bonded to the white bus in the subpanels, it could lead to someone getting a shock. I don't think you explained it very well. Also, the white (neutral) going back to the transformer is grounded at the pole transformer. Also, the ground rod should take most of the fault current, if it was done right, it does't have to go all the way back to the pole transformer. Bottom line is don't take electrical advice from youtube videos or comments, hire a licensed electrician.
@michaelstaley9979
@michaelstaley9979 Жыл бұрын
Dustin, great explanation on this subject. This is something I could never get my head around. But you gave a great explanation with your diagram. Thank you.
@layz_her2673
@layz_her2673 2 жыл бұрын
That was super informative. I have 7 years experience and I'm gonna play your channel in my office, Thanks dustin!
@michaelmakowski8223
@michaelmakowski8223 Жыл бұрын
That was the best explanation of objectionable current I've come across. Thank you.
@angelozullitti6491
@angelozullitti6491 9 ай бұрын
That was a great video explaining the bonding process. This video really explained the reason behind bonding at the service panel and not at the sub panel.
@vmax4575
@vmax4575 Жыл бұрын
Nicely done. One of the best explanation and demonstration (via the magic white board) I have seen in quite a while.
@chasmontecarlo7271
@chasmontecarlo7271 Жыл бұрын
Great explanation , I’am in the process of putting a outlet in my garage and was concerned about the ground and neutrals it’s the first point of disconnect is my panel.Thank you for knowledge I know I can do it.👍
@DaddyBeanDaddyBean
@DaddyBeanDaddyBean 2 жыл бұрын
I watched a couple videos on this topic last year. I have a sub panel in an upstairs closet, and on a whim, pulled the cover off to inspect - sure enough, the grounds and neutrals were bonded. I got that cleaned up, then checked the sub panel in the detached garage - installed by the previous owner, the same as the one upstairs - and they were bonded there too. And, the garage did not have its own grounding electrode, and had an abandoned metal water pipe that was also not bonded to ground (but buried too shallow to qualify as a ground electrode). It's all fixed now, but until this video, I knew not-bonding was important, without fully understanding why.
@allanamen6267
@allanamen6267 Жыл бұрын
Hi Iam an electrician from Papua New Guinea and retired. Found you explanation very interesting and simple. Good on you.
@ethanmcnally21
@ethanmcnally21 Жыл бұрын
The most sensible explanation I’ve heard of this topic, thanks
@noelpichay9229
@noelpichay9229 4 ай бұрын
I 've been a long time electrician and this is the one I got more informed about bonding and its nature to equipments etc. that what might happen, thanks!
@parlenkow
@parlenkow Жыл бұрын
This Chanel is Gold in value!!!!best info in KZbin thanks
@christopherdekonstrukt444
@christopherdekonstrukt444 Жыл бұрын
Back in the 90s I worked for a switch mode power supply company and we used isolation transformers on the AC line because the supplies had different signal grounds within the same unit separated by optoisolators. Sometimes a variac would be wired incorrectly and the metal case would pick up a potential. Oscilloscopes were often floating as they couldn't be grounded. Metal chassis could mean a nasty shock under certain conditions. Once I crossed a different ground path with the oscilloscope probe and it literally melted.
@johnlieber4687
@johnlieber4687 Жыл бұрын
In your example you have multiple subpanels all flowing through each other. In the case of a single subpanel, say in a garage, in my mind it seems like having the neutral and ground bonded in the subpanel means that during everyday operation, neutral current can flow back on either the neutral or ground wire or both! This does not seem like a good idea, and I would be very curious to know why anyone EVER thought bonding these in a subpanel was a good idea. Maybe I am misunderstanding something. Thank you and love your channel, very clear and to the point!
@matthewknight5641
@matthewknight5641 Жыл бұрын
Bro you are saving lives as well as educating us all that see your stuff. Thanks
@chrisno7495
@chrisno7495 Жыл бұрын
The best explanation I've seen as well! Your content is as valuable as review as it is learning!!!
@mechantics
@mechantics Жыл бұрын
This is great information. In preparation for my NACHI (home inspector) exam, I had to know that this is the rule, but I wasn't completely understanding WHY. Electrical is so often misunderstood, and while an uninformed explanation might be able to satisfy a specific scenario, the risk of that improper logic being detrimental in another application is great. Thank you
@aaronmagers6539
@aaronmagers6539 7 ай бұрын
Thank you for your wisdom !
Neutral Imbalance in Multiwire Branch Circuits (Two Hots, One Neutral)
16:41
What is the Difference Between Grounding, Bonding and Neutral?
15:15
The World's Fastest Cleaners
00:35
MrBeast
Рет қаралды 132 МЛН
I PEELED OFF THE CARDBOARD WATERMELON!#asmr
00:56
HAYATAKU はやたく
Рет қаралды 27 МЛН
Kitten has a slime in her diaper?! 🙀 #cat #kitten #cute
00:28
Won't These Melt?!? 15amp Receptacles on 20 amp Circuits!!!
11:47
Electrician U
Рет қаралды 1,2 МЛН
How to Install and Wire a Sub Panel
35:23
SgtDonovan
Рет қаралды 1,2 МЛН
Why Neutrals and Grounds are Separated in a Sub Panel
17:46
Benjamin Sahlstrom
Рет қаралды 3,5 МЛН
Does Current Flow on the Neutral?
23:03
Electrician U
Рет қаралды 1 МЛН
10 Common Mistakes DIYers Make In Circuit Breaker Boxes
13:55
LRN2DIY
Рет қаралды 2,1 МЛН
What's the Difference Between All These Wire Types?!?!
14:48
Electrician U
Рет қаралды 255 М.
Sub Panels Explained - Why are neutral and ground separated?
16:22
The Engineering Mindset
Рет қаралды 1,1 МЛН
How NOT to Wire Light Switches in 2024 (New Rules)
15:21
Backyard Maine
Рет қаралды 694 М.
Grounding and Bonding
8:01
schulerruler
Рет қаралды 659 М.
The World's Fastest Cleaners
00:35
MrBeast
Рет қаралды 132 МЛН