Update: if you have a single series string no fuse is required. If you have multiple series strings, then a fuse is required. 🎁Get FREE diagrams to kickstart your Off-Grid journey! View and get them here: cleversolarpower.com 🎁
@spruce_goose5169 Жыл бұрын
I think you only need OCPD's when it is MORE THAN 2 series strings.
@TexasRanger-b8j5 ай бұрын
This is VERY VERY helpful. You answered all the questions I have in mind. Now, I'm more comfortable doing my project. You have a new subscriber here. Keep adding more videos man. Thanks!
@cleversolarpower5 ай бұрын
Thanks for the sub 🙏
@HelloKLW5 ай бұрын
your video is very informative. thank you.
@cleversolarpower5 ай бұрын
Glad it was helpful!
@alanblyde8502 Жыл бұрын
Great review description mate👌🇦🇺
@kaundabwalya7776 Жыл бұрын
Well explained 👏Thanks Sir 👍
@bmbpdk3 ай бұрын
A very nice and clear video, thank you!
@samsonrobinson23923 ай бұрын
This was super helpful. thanks
@cleversolarpower3 ай бұрын
Glad you liked it!
@dougiee65899 ай бұрын
I like simple math and this video is it
@fujchi21724 ай бұрын
why did you use 6.2 amps in the calculations when the panels showed a rating of 5.8?
@cleversolarpower4 ай бұрын
I use the Isc, highest possible current.
@Shane7son8 ай бұрын
Love your videos this is a big help for me and you explain things real simple unlike the other guys You also get straight straight to the point I don’t like to reload my fridge all the time because I work outdoors. I have power tools like you that are battery power. So thank you. Can I run a refrigerator
@cleversolarpower8 ай бұрын
Thanks Shane! I try to keep my videos to the point so I don't waste people's time. I made a video about how much power my fridge consumes. Check it out on my channel page.
@loganreynolds43967 ай бұрын
Thank you for you video - I have 4 550 W panels, with the following specs. What configuration would you recommend ? 2S2P? For Fuse 1 and Fuse 2 (14.01 x 1.56 = 21.86) would a 30a inline fuse work?? And then for the Fuse 3 - what type of fuse should be used?? Is there any benefit of doing a 2P2S configuration?? thank you! Series 1 & 2 = 100v and 14A = 100v 28A going to the charge controller. VMP: 41.96 IMP:13.11 ISC:14.01 VOC:49.9
@johntheaccountant5594 Жыл бұрын
In your calculation 6.2A x 1.56 = 9.6A where did the 1.56 figure come from? OK; the 1.56 is a safety factor but before you were using 1.25
@cleversolarpower Жыл бұрын
The safety factor for being outdoors changes because it can get hotter outside. Imagine a black wire on a black roof at noon will get much hotter than a wire inside your house.
@abitofeverything19857 ай бұрын
I still don't quite understand where 1.56 came from? Is it Maximum Series Fuse 15 A figure? My panel have (Ipm) 8.86 A, and Maximum Series Fuse 20 A. What fuse i need??
@vellyyt35723 ай бұрын
Is the 1.56 safety factor written in NEC? Where is it come from?
@hardeekpatel19442 ай бұрын
1.56 is standard value....give by NEC standard
@cleversolarpower22 күн бұрын
@@abitofeverything1985 1.25*1.25=1.56
@thesolarpowerinstallersass635 Жыл бұрын
Very good information tks
@qodaxdhuuni53327 ай бұрын
Thank you. What drawing program did you use?
@cleversolarpower7 ай бұрын
For the videos I use videoscribe. For the drawings edraw.
@Khaztr7 ай бұрын
if you're adding fuses on the positive line, doesn't that add some resistance, and therefore require you to add some extra wire on the negative side to equalize the resistance between both lines?
@niallparker36554 ай бұрын
Can't think of a good reason to increase losses just so the voltage drops on each side are the same, what are you trying to achieve? The controller only cares about net differential voltage at its input.
@adex2000ng8 ай бұрын
Well appreciated video
@FareFejzic3 ай бұрын
Helpful explanation. I need instructions: How should I connect two solar panels that are on different sides of my mountain house of 450W each to a 12V 160Ah battery. Thank you very much
@michaelrowland-us3he25 күн бұрын
What exactly does the fuse you talk about look like??? A picture would be good.. also are they placed just before the branch connector?
@cleversolarpower22 күн бұрын
An inline MC-4 fuse for F1,2, and 3 and a DC breaker for F4.
@FarqueKnowsWhere5 ай бұрын
The 3 panels connected in series has an array amperage of 6.2, and a maximum series fuse rating of 15A, the array doesn’t need to be fused, the fuse won’t do anything.
@shaynegadsden4 ай бұрын
You are stupid right, did you not listen to the statement at the start
@truesight912 күн бұрын
What if one of your panels is 20A fuse and the other is 15A ?
@JerryMartins-vh9vc5 ай бұрын
Good day , this safety factor 1.56 is it common/ constant to all countries ?. How can we find this safety factor ??
@cleversolarpower5 ай бұрын
It's a standard factor for cables that are outside under the sun. Indoors safety factor is 1.25
@ThomasNowicki-m5sАй бұрын
there is no factor. a panel I max is a absolut number a panel can produce only this or lower currents!! so to prtect against a 100% limited current is pure nonsens in any aspect. so on panles no fuses theyx are for nothing existing. on the battery side coz a battery is a umlimited power source a fuse will be needted and this is best set below your wire limits without factor nonsens !!! lets say you you a wire that can handle ~40 Amps current max, on this conditons it get war, over time so the best way to set a real protection to it set from battery to charger a 35 Amp fuse to wire never will run on its limits and you protect the wire from this. no mgic factor or nonsens theories from youtubes use your brain. make yxour build with bigger wires then you really need maximium the set the fuse below this wire maximum to give this wire a real protection. that is all the magic.
@smvsspould Жыл бұрын
Where do you get the 6.2amps and the 1.56 from?
@rdd8094 Жыл бұрын
I didn't understand either ...
@cleversolarpower Жыл бұрын
6.2A is the Isc (short circuit of the panel) and 1.56 is a safety factor for calculating current in a conductor for outdoor wiring.
@JohnDoe-pn3qu Жыл бұрын
where is the '1.56' in your formula ISC x 1.56 = minimum fuse size coming from? I ask because my solar panels have Isc 8.75A. So 8.75 x 1.56 = 13.65A minimum fuse size, but the panel indicates: 'max series fuse = 12A'.
@manonfire7675 Жыл бұрын
yeah, i don't get this too.
@cleversolarpower Жыл бұрын
Hello John, good question. This is because the cabling is mounted outside. We need to apply an additional 125% safety margin. So it becomes 8.75A x 1.25 x 1.25= 13.67A. if you look on my website, the article about 'how to calculate fuse size for solar system' it's explained there.
@narotica1 Жыл бұрын
@@cleversolarpower so why 1.56 not 1.25?
@cleversolarpower Жыл бұрын
@@narotica1 check my previous answer
@narotica1 Жыл бұрын
@@cleversolarpower yeah it was a shit explanation, 1.25 * 1.25 is 1.56 for everybody else
@Torumees07 ай бұрын
my isc A show 6.68, should i use 10A and 30A or i need to go 15 and 40?
@ThomasNowicki-m5sАй бұрын
nothing. to put ona limit powwer source a fuse in pure nonsens. if you panel makes 6.68 Amps max iin a short this number will never be higher so to protect your panel / wire against 10 Amps, where thsi 10 amps will come from? for what? where this 10 Amps will came from if your panle have a absolut limit that is 6,68 A in best conditions and only can be this or lower???? there are alot of youtuber telling trash in videos and dont explain how this fuse will work or exactly against what it will protect.
@sheldonlampson63682 ай бұрын
Where do you get the number 1.56?
@cleversolarpower2 ай бұрын
Safety factor for outdoor wiring. This is because the cable can get very hot in the sun.
@pasheatsiАй бұрын
Thank you very much for clarifying this. I want to connect only two 200 watt panels in parallel to a portable power station (Ecoflow Delta 2 Max). Do I still need 3 fuses, or can I just use one for each panel?
@cleversolarpowerАй бұрын
I would use a fuse for every panel because they are placed in parallel.
@tembonemon2 ай бұрын
Hi. Can i use a fuse and a dc circuit breaker at the same time
@cleversolarpower2 ай бұрын
Yes, but why would you do that?
@nnamdi.ohaegbuchi3 ай бұрын
Which size of wire should I use in 3 pieces of 350w solar panels system
@cleversolarpower3 ай бұрын
Check my video about wire sizing for charge controllers.
@naveencruise155911 ай бұрын
How did you get that 1.56 value ??
@cleversolarpower11 ай бұрын
1.56 is the safety factor considering wires that are outside. The sun will influence the temperature of the cable, so thats why the safety factor is 1.25x1.25=1.56
@jonnytacooutdoors Жыл бұрын
So where do you fuse the panels ? Did I miss that
@cleversolarpower Жыл бұрын
The fusing happens as close to the power source as possible. This can be an inline MC-4 fuse. You can also add the fuse next to the charge controller right before it enters the input of the charge controller. You can also use a combiner box if you have parallel strings.
@jonnytacooutdoors Жыл бұрын
@@cleversolarpower I’m using a PV shut off switch. As close to the power source as in the panel or the battery? So if you meant the panel then just clip it onto the panel mc4 output cable right?😎
@cleversolarpower Жыл бұрын
@@jonnytacooutdoors To the panel. Yes, if that is physically possible. If you have parallel strings, then you can do it after the combiner box.
@jonnytacooutdoors Жыл бұрын
@@cleversolarpower am I just fusing the positive line? I plan on just plugging in the fuse to the positive line coming out of the first panel and then have that wire go down into the truck
@SetchiPaunda Жыл бұрын
great video ! Very clear
@slr617hp3 ай бұрын
If the short circuit current is 13.58A; open circuit voltage is 38.95V with max fuse at 25A: For a 3S2P setup, 13.58A x 1.56 x 2 = 42.3A is that correct? Would I be able to get a 45A fuse?
@cleversolarpower3 ай бұрын
You should fuse every series string first with 25A. So you need two MC-4 connectors fuses. Then have one DC circuit breaker so you can turn off the whole solar system. This is can be a 64A DC circuit breaker suited for solar (1000VDC).
@clintoncoker62 жыл бұрын
I've never understood the reason for fusing solar panels. Even if you rub through a solar wire and it shorts to earth, the fuse will not blow as a) it is sized lower than the solar current (as it has to be), and b) the fuse would be near the charge controller, so your short would typically be after the fuse, and c) typically the charge controller would stop any battery current trying to flow back through the panels in case of any wiring fault.
@cleversolarpower2 жыл бұрын
In a series configuration, yes. But in a parallel configuration, you need it. If one panel is shorted, the other panels will back feed into the broken panel, sending lots of current to it. In order for the panel not to melt, the fuse of the broken panel melts. However, I think it's still useful and good practice to fuse a series connection.
@Ibian666 Жыл бұрын
Houses catch on fire from unfused parallel panels, is why.
@susiejrgensen704110 ай бұрын
@clewersolar I need to paralel, because my panel give 12,2 Amp Isc, and 41 Voc volt, and my controller max 75 volt, I have 2 panels, shall I use 12,2 Amp x 1,25 = 15/16 Amp ? Thanks
@marcvandaele18783 ай бұрын
@@susiejrgensen7041you need *1.25=32 Amps breaker
@nnamdi.ohaegbuchi3 ай бұрын
Can i use a combination of fuse and diode in 3 pieces of 350w solar panels
@cleversolarpower3 ай бұрын
No, a diode only prevents backwards flow of electricity.
@nnamdi.ohaegbuchi3 ай бұрын
@@cleversolarpower thanks
@nnamdi.ohaegbuchi3 ай бұрын
Can i use a diode rather fuse?
@cleversolarpower3 ай бұрын
No
@nnamdi.ohaegbuchi3 ай бұрын
@@cleversolarpower thanks
@croomcas3 ай бұрын
For me in series 11.4A x 1.56 = 17.784A Do I use a 20A even though my panels Max series fuse rating is 20A? Thanks
@cleversolarpower3 ай бұрын
Yes.
@cardinhamkilligrew971210 ай бұрын
I have two 120 watt solar panels (ss 6.8 amps) in parallel. was planning on 12 awg wire from panels to mppt and 10 awg from mppt to batteries. before combiner was going to use 15 amp inline fuse and a 20 amp MPPT. will that work? i assume the combined power was 21.6 volts at 13.6 amps. Thoughts?
@cleversolarpower10 ай бұрын
6.8*1.56*2 panels in parallel = 21A. 20a fuse is on the edge but ok.
@dheller77710 ай бұрын
I have three 300 watt panels that will be wired in parallel due to shading. Each has a short circuit current of 18.1 amps. So I woll need 3 20 amp fuses one for each panel. How big of fuse will I need forthe iotput end of my 3 into one adapter? Thank you
@cleversolarpower10 ай бұрын
No, isc x 1.56
@johntheaccountant5594 Жыл бұрын
Can you use an MCB instead of a Fuse?
@cleversolarpower Жыл бұрын
An MCB from a reputable brand is more expensive. MCB's are used in AC switchboards because they can be switched off often. For DC, it's cheaper to have fuses. If you look at the end of the video you can see a popular MCB which is unbranded. It's known to cause problems and heat up under use.
@DomainUltra Жыл бұрын
Is a fuse required if only one 100w panel is plugged directly into a solar generator with built in MPPT?
@cleversolarpower Жыл бұрын
No, but a breaker could be depending on your local code.
@awesomedee5421 Жыл бұрын
Great summary. Is there a device to boost up voltage after the combiner so don't have to have such a thick cable, and then on the other side of the run bring the voltage back down?
@cleversolarpower Жыл бұрын
Not that I am aware of. A solution is to wire your panels in series.
@HariPLTS2 жыл бұрын
Nice info
@bestillandknowthatuaregod10 ай бұрын
What Fuse Size for 150W Solar Panel - ISC Amps 8.76 should I use? THANKS
@cleversolarpower10 ай бұрын
8.76x1.56=13.6 so a 15A fuse is ok. But you don't need a fuse for one panel.
@bestillandknowthatuaregod10 ай бұрын
Im only using 2 150Wats Panels in parallel. Still need fuse?@@cleversolarpower
@СергейВиноградов-м9ъ10 ай бұрын
Why you don't need a fuse for one panel? @@cleversolarpower
@hollygrinstead725210 ай бұрын
Why no fuse needed for one panel?
@Bendy509-cz8vz6 ай бұрын
Do one about circuit breaker dc and ac please
@aysensvoboda2274 Жыл бұрын
Great video. May I ask which tool you use for those drawings? Thank you
@cleversolarpower Жыл бұрын
Thanks. I use Edraw.
@tembonemon2 ай бұрын
Lovely
@expeditionchef222 Жыл бұрын
Where do you get the 1.56 from?
@cleversolarpower Жыл бұрын
It's a safety factor.
@The_Resistance_1961 Жыл бұрын
OK, I bought two solar panels and don't plan on linking them at all. I'll be running both control boxes that came with each panel. Now, the wires, control box etc can all be handled easily by the wires and by the control box itself, so would I need a fuse between each panel and the control box? The solar panels are rated at 15 Amps each, control boxes are 30 Amp.
@cleversolarpower Жыл бұрын
No need for a fuse if there is only one solar panel per controller.
@The_Resistance_1961 Жыл бұрын
@@cleversolarpower Yeah I watched a couple more vids and got around adding solar panels by simply running each panel (350W) on the controller that came with them, but I might add a busbar to minimise the number of rings around the battery terminals. Yeah, then I figure it can't go wrong given that SLA batteries give off a ''resistance'' which each controller reads and moderates, although one must apparently make one of them the master controller so that the batteries don't ''equalise'' more than once a month. Nevertheless I've added 30 amp circuit breakers between panels and controllers, and put 200 ah fuses between each of the four batteries in my bank. It's not that hard when you watch videos such as your own.I've had a simple philosophy all my life - if you don't know something just ask someone who does.
@chansuihing1416 Жыл бұрын
Where can I buy the book
@cleversolarpower Жыл бұрын
You can check the link in the description.
@SweetFLGuy1 Жыл бұрын
cleversolarpower What size fuses should I use when connecting four 180w solar panels in 2series2parallel. Each panel is rated 10.5 amps max with a series 15 max rating on each panel going into a 15 amp max rated portable solar generator. I'm guessing the formula is 10.5 x 1.56 = 16.38 amps so would I need two 15 amp fuses going into a 30 amp fuse or two 20 amp fuses going into a 40 amp fuse after that before it goes into the solar generator rated at 15 amps max. Will it work and safely to protect my panels and solar generator without constantly blowing fuses? Let me know. Thanks
@cleversolarpower Жыл бұрын
You need two 15A fuses and one 30 amp fuse.
@joeking3966 Жыл бұрын
Hello, thank you for the informative videos, love the content! I have a stupid question, at 3:46 when you are explaining the voltage drop across different wire sizes, I was wondering how did you come into the conclusion that the 14awg wire is sufficient? Or at 4:17, 12awg is sufficient voltage drop for the 2 strings? Is there a rule of thumb on the % drop is acceptable? Thank you in advance!
@joeking3966 Жыл бұрын
Haha, nevermind, i just saw your other video that explained the voltage drop of 3%. Thank you!
@nickchlapanas2987 Жыл бұрын
Great video, great analysis. I have a question though, what is the difference between mc4 fused connector and mc4 diode connectors?
@nickchlapanas2987 Жыл бұрын
I also would like to ask what fuse should I use for a 7.75a panel? 10 a or 15a?
@cleversolarpower Жыл бұрын
The max fuse size will be indicated on the back of the panel. I recommend watching the video again. MC4 fuses is just a fuse holder which fit MC-4 connectors. I suspect that MC4 diode connectors are the same. Why would you use a diode?
@netrocker9990 Жыл бұрын
@@cleversolarpoweryou're wrong,mc4 diode is used as blocking diode to avoid shading issues between two parallel strings/parallel panels
@Greg652 жыл бұрын
There is no reason to place a "combined current" fuse (F4 @ THE 1:38 mark) after the normal parallel fuses (F1, F2 & F3) as it serves no purpose, if anything goes wrong after these fuses they will blow anyway (before fuse F4 can blow).!
@cleversolarpower2 жыл бұрын
It's a solar disconnect breaker (resettable fuse). Maybe I should have made it more clear what it is. The breaker is there to isolate the solar panels from the system. It is required to do so.
@Greg652 жыл бұрын
@@cleversolarpower Thanks for the reply, yes that makes 100% sense of things!
@MrHanzeeman2 жыл бұрын
@@cleversolarpower yes, maybe you can add a caption to clarify that. It certainly didn't come across in the video like that.
@Floyd112007 Жыл бұрын
Yes, this is now clear. Exactly like in my combiner box. @@cleversolarpower
@davidjosephhansen8555 Жыл бұрын
I'm installing twelve 400w panels at my cabin. The EG4 3000w MPPT/inverter has an input limit of 500w and 80a max charging current. These panels are 36.8v and 13.85A. short circuit current 13.55A, Pmax -0.34%/C. I was first going to make two strings of 6 and put them in parallel for 27.7A, but you made me reconsider and think about putting them all in series. 36.8v x 12 =441.6 V for the series, less than the 500v the inverter can handle. In Wisconsin, it is possible to get a -37C event in winter, so using the Pmax I figure that could be a voltage increase of 13% to 499V. I don't know if that Pmax uses the panel's temperature or ambient temperature, but is that cutting it too close? Should I stick with two strings in parallel for 27.A or try for all in a series at 13.85A? I have a fairly long cable run of 120', so I figure I'd be much better off with the lower amperage and fusing would be simpler.
@cleversolarpower Жыл бұрын
You need two series strings to make 6S2P. Your voltage will be over 500V. Voc*12*1.25=max 500V. In your case this is: 36.8V*12*1.25=552V. Your charge controller can get damaged on cold sunny days. 1.25 is a safety factor.
@expeditionchef222 Жыл бұрын
My panels have a maximum fuse rating of 20A. I have 22 panels in seri parallel with 2 strings. 495 wats per panel. What would you suggest regarding the fuse’s?
@cleversolarpower Жыл бұрын
Fuse every series string, and then the combined array for a total of 3 fuses.
@expeditionchef222 Жыл бұрын
@@cleversolarpower thank you very much. And what fuse rating you suggest? 20amp for individual and 32 amps for combined? Thank you
@bogdan.dobrowolski Жыл бұрын
Do I need a fuse for a single solar panel, for example 300W. ???
@cleversolarpower Жыл бұрын
No
@bogdan.dobrowolski Жыл бұрын
@@cleversolarpower THANKS !!
@ΔημητριοςΑραβιδης2 жыл бұрын
What about Solar DIODE connector fuse. Is it the same ?
@cleversolarpower2 жыл бұрын
The diodes are already on the back of the panel in the small box. You need to add the fuse with an MC-4 connector fuse holder.
@josegarcia-th3pj Жыл бұрын
it has to be a fuse or can be a breaker
@cleversolarpower Жыл бұрын
Can be both, a fuse will be cheaper.
@danieleercole9973 Жыл бұрын
Hi…thank you for your video is amazing …I have a question …I have 2 solar panel 200w 18.2v 11.7 amp and 1 100w 20.4v 5 amp …the question is …what tipe of fuse do I need for the 200w panels ? And one more question …the fuse that will go string after the 3to1 adapter will a need a 50amp fuse and if so is going to make any problems with the mc4 connector due that they are rated only for 30amp …thank you for your help
@jacqalas Жыл бұрын
Hi. Will the fuse be helpful for lightning in any way or is the fuse just for over current and not high voltages?
@cleversolarpower Жыл бұрын
a fuse will not help with lightning, you should consider it a loss when it hits your panels. Don't ground the panels and bring it inside of your house where it can destroy more equipment.
@БојанКостић10 күн бұрын
👍👍👍👍👍👍👍👍
@ronhanishАй бұрын
Formula ISC? You lost me on that. Can you explain the formula.
@cleversolarpowerАй бұрын
Isc * 1.56 -> 1.56 is 1.25*1.25 which are two safety factors multiplied with each other for outdoor temperatures.
@USA-GreedyMenOfNoIntegrity2 жыл бұрын
No fuse needed paralleling two series strings or two individual panels. Fuse each when three or more in parallel.
@cleversolarpower2 жыл бұрын
Every parallel string needs a fuse. And for simplicity reasons I recommend fusing solar panels.
@davebenz82712 жыл бұрын
@@cleversolarpower Is that required, or just you being overly cautious?
@cleversolarpower2 жыл бұрын
@@davebenz8271 Fusing is required for parallel strings. I do recommend fusing series solar panels if the combined Isc of the panels goes over the rated current of the wire.
@MrHanzeeman2 жыл бұрын
I think rv10flyer has a point... Please correct me if I'm wrong. If the first of two panels in parallel, has a short, it's fuse may blow or may not, depending on how much over Isc you installed. Now say it didn't blow, and the second panel in parallel starts to back feed it... It also won't blow it because it can only provide 1 times the Isc. 3 or more panels in parallel... Different story. Edit: Or do you still add in the being produced by the shorted panel?
@cleversolarpower Жыл бұрын
@@MrHanzeeman No need to have a fuse when you have one or two parallel strings. You need to calculate the Isc though. If you have three parallel strings or parallel panels, then you need to fuse because the combined ISC is higher than the 1.25xIsc of the panel. Hope this helps.
@Swenser Жыл бұрын
The solar panels can't provide anymore current in series than rated. No need for fuse in series.
@cleversolarpower Жыл бұрын
Correct. If you have multiple series strings, then a fuse is required.