No video

DON'T Install DC Isolators On Solar, Electricians Warned

  Рет қаралды 88,433

eFIXX

eFIXX

Күн бұрын

Пікірлер: 372
@legominimovieproductions
@legominimovieproductions 7 ай бұрын
Sounds more like a "DON'T INSTALL CRAPPY CHINESE OFFBRAND DC ISOLATORS WHICH COST 1/50th OF A SAME RATING PRODUCT FROM A KNOWN BRAND"
@UKsystems
@UKsystems 8 сағат бұрын
Using proper approved testing methods I have found the Chinese isolators from some brands are as good as UK brands. It’s mainly to the people do not talk down the connections or they think the links are optional.
@davidw460
@davidw460 7 ай бұрын
To blame the DC isolator for a fire begs the question as to exactly why it has failed - unapproved switch design or incorrect selection / installation. This recommendation to delete an isolator seems strange to me. Perhaps solar panels should not be installed in a sunny location? Then everything will be within ratings 😂
@deang5622
@deang5622 7 ай бұрын
It is not as odd a request as you think. BS7671 still needs to be complied with, and it says a means of isolation needs to be provided. What the insurance companies are talking about is removing of or not installing a separate DC isolation switch, and under the regs you don't need one if there is one integrated into the inverter. So they are actually talking about the removal of a redundant component.
@ClosestNearUtopia
@ClosestNearUtopia 7 ай бұрын
Doesnt matter if you switch ac or dc, the point is, there could be reasons why you want to switch the dc side, and if you do have to choose the right equipment for that dc voltage, and be able to switch max current in and out, choosing the wrong one could cause fire, just like choosing the wrong one to switch the dc side.. op is right.
@ClosestNearUtopia
@ClosestNearUtopia 7 ай бұрын
@@deang5622it is an odd request, you for sure need to be able to switch you dc input off on your inverter for reasons..
@MikeyisNinja
@MikeyisNinja 7 ай бұрын
​@deang5622 it's redundant until a lighting strike blows out the inverter and you have to replace it. The isolator is definetly more convenient when you are trying to mash the cables into a dc converter or charger.
@deang5622
@deang5622 7 ай бұрын
@@MikeyisNinja Never heard of lightning conductors? You don't use or rely on a DC isolator to protect your installation from lightning strikes. That's where lightning conductors and spark gaps, surge protective devices come into play. An isolation switch is NOT a surge protective device.
@deang5622
@deang5622 7 ай бұрын
A fire caused by a faulty solar charge controller is nothing to do with a DC isolation switch, if a separate isolation switch is installed.
@Mike-01234
@Mike-01234 7 ай бұрын
Sound like lithium battery fire to me said it was off-grid likely DIY battery.
@Mr424242424242424242
@Mr424242424242424242 7 ай бұрын
It's more that the design of the PV install is fundamentally faulty, you should never let PV panels that are exposed to full sunlight just float, they need to be grounded or run into a loadbank when not connected to a load. It's a known issue that PV installers don't want to deal with, because then you probably need a seperate grounding system just for the PV to let it discharge the energy into the earth, and you need a DPDT switch to isolate them, and even then, the solar panels remain under liver current.
@odoohub5010
@odoohub5010 7 ай бұрын
@@Mr424242424242424242 The PV grounding is meant to help incase of lightning strike.
@deang5622
@deang5622 7 ай бұрын
@@Mr424242424242424242 What is the danger posed by a floating solar panel?
7 ай бұрын
@@Mr424242424242424242 wouldn't the option be to cover the panels so that the power generated is diminished or reduced be a partly solution? It's just a thought.
@electrician247
@electrician247 7 ай бұрын
Horrendous to hear about the tragic loss of life, especially someone so young. Nobody should be exposed to danger when going to work that can result in injury and worse death. Thoughts with the family. Got to say I agree with the comments here. DC isolators in true form separate to electrical equipment aka an inverter are essential. It allows safe working practices. Its time industry faced up to the real problem of poor installation. From the hooks to the isolators. I have written to the authors of that document discussed to find out who exactly was involved in its production and if they would like to help remove those poor installation practices rather than essential system components. Thanks for sharing!
@gabor.nadudvari
@gabor.nadudvari 7 ай бұрын
DC isolator installation depends on country regulation. In my country if the DC cable goes inside the attic then within 5 meter from the entry point a DC isolator must be installed and operated remotely. The idea is that is should be controlled by the main/firefighter switch to isolate the panels from DC cables that are running inside the house to avoid electronic shock. There is only few high quality 1000V DC rated products are available. There is always a cheap alternative from a well known online reseller, but I would not install those to my house.
@arthurreeder8451
@arthurreeder8451 7 ай бұрын
So, who is going to trust technology over a switch? In the same way, a 3phase Spd that takes the supply straight down to earth without any over current protection. Those of us that have been around long enough will know, if something can go wrong it will. So, when it goes wrong, will your insurance pay out? To me at least, when it comes to electrical safety, give me a good old fashioned isolator any day. When it's off, it's off end of story.
@johnburns4017
@johnburns4017 7 ай бұрын
I _think_ the report means that: *1)* *_poor quality_* DC isolators; *2)* cables with *no* bootlace ferrules; Should *not* be fitted.
@cradlefive
@cradlefive Ай бұрын
I fit ferules on all the PV connections to get the best connection but if the equipment’s failing that’s worrying because these big PV companies always blame the installer
@demonkey123
@demonkey123 7 ай бұрын
A tragic story about Matthew Camble. The strong reminder that if we feel that it’s not safe doing something, then it probably isn’t. As an electrician who has deviated away from the mainstream for sometime, I look forward to watching your videos to keep me abreast of the industry changes. Thank you 👍
@jagarcogheart
@jagarcogheart 7 ай бұрын
if the dc isolator on the inverter is ok as an isolator I see no problem useing that only. however if the inverter is monted inside the building I would want a Dc isolator installed outside the house incase there is a Fire for whatever reason so the fire brigade don´t have to go inside the bulding to look for the isolator switch.
@efixx
@efixx 7 ай бұрын
Thanks for your viewpoint. 👍
@normanboyes4983
@normanboyes4983 7 ай бұрын
How do you do that for a domestic dwelling (to isolate the mains supply)?
@edc1569
@edc1569 7 ай бұрын
Isn't the fault likely on the roof, or in the attic, doesn't this extra new outside unit and connections just add more risk than it takes away.
@nathonsweetman4409
@nathonsweetman4409 15 күн бұрын
In many places this is actually required in order to be code compliant, regardless of whether or not the inverter has a built in disconnect. Every Firefighter and Lineman know what a disconnect looks like, they don't necessarily know if a particular inverter has one built in., Where I am we are actually required to have rapid shutdown at the panel level; for all solar roof installations.
@NckBrktt
@NckBrktt 7 ай бұрын
Do not disconnect under load for 500V DC ? There must be 1000's of solar PV installations just in the UK. I bet 99% of them have a DC isolator since the regs does mention it - ours does.
@juhajuntunen7866
@juhajuntunen7866 7 ай бұрын
I think main reasons are 1) poor quality components 2) poor quality work
@ten-bob-note
@ten-bob-note 7 ай бұрын
So how exactly does a separate DC isolator cause a fire?
@edc1569
@edc1569 7 ай бұрын
1) Poor connection causes overheating of the terminal, breakdown, extensive sustained arcing until combustion of adjacent materials. 2) failure of the isolator itself causes sustained arcing until combustion of adjacent materials. Look up what a 500VDC arc is like, nothing like AC.
@deang5622
@deang5622 7 ай бұрын
1)Poor contact resistance, 2) Metal parts not rated for the current 3) Plastic parts not rated for the temperature 4) Excessive operation of the switch when under load, the arcing causing premature erosion of the contacts leading to increased contact resistance. The arcs produced by switching DC are a much bigger problem to dissipate than for AC.
@travoltasbiplane1551
@travoltasbiplane1551 7 ай бұрын
Crap terminations. Links removed etc.
@blow0me
@blow0me 7 ай бұрын
@@edc1569 And are they connected in series to be running at 500v ?
@TheChipmunk2008
@TheChipmunk2008 7 ай бұрын
@@blow0me that's how solar works generally yes, seen up to 1kv on a solar array. I think we should be using old style MEM Excel isolators on it
@wazza33racer
@wazza33racer 7 ай бұрын
In Australia, the DC isolators usually corrode, and catch on fire, besides they offer no overload/fault protection and are pretty much useless. Problem is that the Australian code says that they must be fitted, but they at least should not be up on the roof, where the weather causes them to fail, and instead be sited in a proper weatherproof cabinet.
@MikeyisNinja
@MikeyisNinja 7 ай бұрын
How about using tinned marine cable? And why isnt wire corrosion a problem with other circuits in similar locations?
@michaelcostello6991
@michaelcostello6991 7 ай бұрын
The pvc boxes containing the isolators always allow rain in , Sometimes the cable entry points are not done properly -- not water tight etc etc
@kennethausten
@kennethausten 7 ай бұрын
So the problem really is bad installation of the isolator or an unsuitable type. Excess heat with those hot summers you have and then not waterproofed if it rains. Everything is watertight in UK for external use. Fireman's switch a good example. Regulation requirements and never seen a faulty one in all my years. We get rough weather here and survive.
@Phantomthecat
@Phantomthecat 7 ай бұрын
@@kennethausten It's usually the cheapest nastiest isolator that the Electrician can get their hands on, then installing it in a crap location. It's not the rain that causes issues initially but the sun here - even UV stabilised plastics cop a flogging over a few years and slowly warp or degrade until they allow water in. Installing the isolator in a location like near the inverter on the south side of the house for example (equivalent to the north side for you) alleviates these issues, but the amount you see stuck up on the roof is amazing.
@shmayazuggot8558
@shmayazuggot8558 7 ай бұрын
I use a polarised 500v breaker and double insulate the solar cable connetion point, cut the ferrule to size, but to cut power my inverter has an intigrated isolator switch. At max current & volts the temperature of the breaker connection points is not more than 2 degrees above ambient. Personaly I think testing thermals during max loading is a must.
@MervynPartin
@MervynPartin 7 ай бұрын
I would be interested to know the mode of failure of the dc isolators on PV installations. Having worked in industry with extensive dc systems- 55V, 110V, 240V, and 485V, I have never experienced any of the dc switchgear to fail. Indeed, I regard isolators as essential, so is this just a knee-jerk response to incidents or has proper investigation identified the fault? Why would an isolator within the control panel be any safer than an external one? By the way, an endorsement from Greta Thunberg would not tempt me to buy anything, even with triple Nectar points!
@benharris4436
@benharris4436 7 ай бұрын
Usually - water ingress, especially via the conduit to the roof. Otherwise improper screw terminal tightening.
@mrtechie6810
@mrtechie6810 6 ай бұрын
​@@benharris4436drip loop?
@RichardSmith-ck2dd
@RichardSmith-ck2dd 7 ай бұрын
I don’t understand. Neither of the failures highlighted related to DC isolators. How do the ones fitted inside inverters differ from those selected for use outside inverters. Simply stating “there is a problem with them so don’t fit them” doesn’t seem to make any sense to me. Surely a review of the selection and choice of the isolators would be more appropriate.
@sang3Eta
@sang3Eta 2 ай бұрын
If they are incorrectly wired, incorrectly labled, or manufactured badly they don't work properly and the arc causes heat. I think someone has a KZbin video of one on fire and explains the issue.
@andrewstafford-jones4291
@andrewstafford-jones4291 7 ай бұрын
Talk about a "U turn" on DC isolators, first they insist you fit them, despite the Inverter manufacturers stating they are unnecessary - you just couldn't make it up.
@Umski
@Umski 7 ай бұрын
Yeah seems it was all the rage 10 years ago even though my SE inverter has one built in - suspect the external isolator isn’t even explicitly rated for DC - fortunately the SE optimisers can deal with dropping any HV DC down to safe levels
@markrainford1219
@markrainford1219 7 ай бұрын
Yeah, I'm about to give up.
@MikeGleesonazelectrics
@MikeGleesonazelectrics Ай бұрын
This is the insurers.. when were they expert electrical practitioners?
@bill2960
@bill2960 27 күн бұрын
@@MikeGleesonazelectrics You will find that the insurance company’s drive most of the changes to all trades
@MikeGleesonazelectrics
@MikeGleesonazelectrics 27 күн бұрын
@@bill2960 could be, doesn't mean they know best tho, just to avoid payouts I guess!
@retrozmachine1189
@retrozmachine1189 7 ай бұрын
It's fascinating to see how regulations and recommendations around the world lurch around like this. Personally I reckon you always want an external way to remove supply from a device. Everything has a built in on/off switch yet we still have means to isolate wiring in standard AC wiring. That shouldn't change with PV. If anything given the sort of voltages that are permitted it should be mandatory. Not sure on the max voltage over there but many places are now moving to allow 1kV or higher even in domestic. Use a non-rubbish properly spec'd DC isolator and don't put it in a situation where it is going to be weather damaged.
@jix177
@jix177 7 ай бұрын
Where's the explanation about how a DC isolator could cause a fire?
@deang5622
@deang5622 7 ай бұрын
See my post. I explained how
@user-tj5nk7lb8l
@user-tj5nk7lb8l 5 ай бұрын
right on bro this is a 'kin infomercial waste of space clickbait shite
@patricklyons7683
@patricklyons7683 7 ай бұрын
Victron doesn't make crap, they have no chance of blaming victronenergy.
@amenaspecialist
@amenaspecialist 7 ай бұрын
100% it was dodgy connection or similar. no chance it was the victron, that shit is solid.
@squeaky_honda
@squeaky_honda 7 ай бұрын
It was definitely a bad connection, probably on the AC side. I've seen a video of a fire with a Victron system caused by that. Victron's connectors are very weird, so a DIYer misjudged how much copper to expose. Also they discourage the use of ferrules, because on boats the shaking makes that weird stuff come loose.
@joesmith1142
@joesmith1142 7 ай бұрын
@@squeaky_honda i disagree but i realize this is a hotly debated topic. ferrules are widely recomended on boats for the very reason of preventing loose connections. compressed wires will loosen up soon after install due to the wires slowly compressing, not to mention repeated heating and cooling. ferrules work perfectly in victron gear. i just installed 6awg ferrules in a victron charger yesterday no problem. a bigger issue might be that these connections never get re-checked soon after the initial install when they will likely have loosened up, especially if its a diy'r who doesnt realize or its a professional install and no one comes back to check.
@squeaky_honda
@squeaky_honda 7 ай бұрын
@@joesmith1142 Google for "Ferrules are not to be used with Victron MPPTs", quotes included. You'll find an official statement from Victron that bans ferrules and why. I've seen it in some of their docs, too. I favour ferrules, so this stood out to me.
@bloepje
@bloepje 8 күн бұрын
Back in 2010 I got a warning from my solar installer to never disconnect the solar during the day. I now live offgrid with a completely new installation by persons I trust. They told me the same: There is a thick isolator: disconnect during the night, or extreme emergency. Victron MPPT's don't disconnect, but you can turn them "off": they will let the solar float, and hence it is safe to disconnect. The disconnect is for a 202V max measured setup.
@blow0me
@blow0me 7 ай бұрын
So why can an isolator, a safety device....cause fires ?
@dragonfireproductions790
@dragonfireproductions790 7 ай бұрын
As a firefighter and an electrician, picture this: We're responding to a fire involving a solar panel fire and they removed the isolators on the solar panels so we're gunna yank mc4s until they're all isolated? yea I'm sticking to a remote disconnection device that isolates panel to panel connections my house is powered by a hybrid solar system (it can act as a grid tied system and an off grid system) for 5 years now and nothing happened no fires nothing. I even built the batteries myself sometimes it's when people get curious and touch what shouldn't be touched like the solar installation I did to a residential structure I told them not to tamper the settings and even let them sign a waiver that if there are signs of tampering, I have the right to waive my involvement in an incident involved, lo and behold they got curious they touched the settings and permanently damaged the lead acid batteries by charging it with the wrong voltage and current causing it to bloat and explode
@deang5622
@deang5622 7 ай бұрын
No. You just go to the inverter and perform one of two actions: 1. Turn the isolation switch in the inverter 2. Pull the connectors on the cables to the inverter. The difficulty for the fire brigade is educating every fireman the different topologies: With or without a separate isolation switch. And then there is time spent searching trying to identify whether a separate isolation switch is in use.
@dragonfireproductions790
@dragonfireproductions790 7 ай бұрын
@@deang5622 you probably don't know how PV systems work, when a solar panel fails it can cause a problem if it's a series circuit hence the use of an internal bypass diode. now if you isolate the inverter does it isolate the solar panels connected in series? That's also why an inline PV fuse is used and also rapid shutdown devices should be implemented, 500v solar arrays are an extreme pain in the ass if they have problems. I am a registered tradesman and i probably know how to install PV systems
@deang5622
@deang5622 7 ай бұрын
@@dragonfireproductions790 I know more about solar panels than you could ever know in your life time mate. I have formally studied them. As for diodes...I have solved many problems with Ebers Moll. Don't be so condescending as you might just be talking to someone that knows far more about this than you do. I was making PN junctions and other semiconductor devices probably before you were born. If you are an electrician, even if you have specialised in PV installation, then I guarantee you you don't know as much about this as I do.
@dragonfireproductions790
@dragonfireproductions790 7 ай бұрын
@@deang5622 but you probably don't know the most recent safety devices used in solar systems nowadays, look up rapid shutdown devices used in solar power plants it individually isolates all of the solar panels in a system making it easier to prevent a domino effect
@deang5622
@deang5622 7 ай бұрын
@@dragonfireproductions790 Let me explain it to you. If you are trying to isolate a PV circuit, it does NOT matter where you put the isolator, except it is better to put it in the positive line from the panels. In that way you are removing any lethally high voltage. If you break the circuit, current stops flowing. IET regs say that if the inverter contains an integral isolation switch, you don't need a separate isolation switch. This is a fact and it is not up for debate. And that inverter integrated isolation switch is as far away from the panel from a circuit point of view, as possible. Clearly there is no obligation to place the means of isolation close to the panels. The reason for this is because in an electrical circuit, you can break that circuit anywhere and current will cease flowing. So what is being discussed in the regs about isolation is about the isolation from the panels to the inverter. They are NOT talking about isolating individual panels and trying to protect against short circuit faults among the panels! Talking about series or parallel connected panels is a complete irrelevance. The series configuration results in two cables going to the inverter. If you need an isolation switch then you put one in in one of those cables. In a parallel configuration, there is a decision to be made as to how those pairs of conductors from each panel or sets of panels are routed to the inverter. Let's suppose there are 2 panels in parallel, that's 4 wires. If all 4 are routed to the inverter then you will need two separate isolation switches. If those two pairs of two conductors are commoned together so that only two conductors are routed to the inverter then you only need a single isolator. The problem that might arise in a PV installation is when an electrician post initial verification is wanting to make changes to the configuration of panels and the isolation switch is integrated down in the inverter, or the individual strings of panels do not have their own isolation means, that potentially dangerously high voltages may be present across multiple panels. You are not likely to be electrocuted by touching bare wires or terminations from a single panel - unless it's a f..g big panel. Just think it through, for crying out loud.
@WooShell
@WooShell 7 ай бұрын
Many countries (e.g. Germany) actually mandate DC isolation switches for solar installation for fire reasons.
@007floppyboy
@007floppyboy 7 ай бұрын
I would suggest that perhaps many isolators are not capable of clearly breaking the on line voltage at the rated current. A line of panels can easily get up to 600v (shouldn't but they do), if installers are not allowing for this and not wiring the internal switches in series then all hell is going to occur. With DC the trick is to make the gap on the contacts as big as possible, and that means series contacts, and each contact must be capable of carrying full current. I would suggest a factor of at least 1.3 safety. Panel array = 20Amps at 450v(theoretical max), then an Isolator made to break full load current at full voltage of around 25 or 30 Amps at 585-600v DC. Often that means wiring 2 sets of contacts in series in both legs. Many 'isolators' are not meant for ON-load breaking but often only capable of OFF-load disconnection, it you shut the inverter down, then isolate the panels (with lock) to work on them. I also suggest that the Isolator is placed in a floor accessible position. Roof is no good.
@gabor.nadudvari
@gabor.nadudvari 7 ай бұрын
SolarEdge line voltage is fixed 750V the production is switched on when the line voltage practically around 930-950V without load then it is regulated to the fixed 750V.
@007floppyboy
@007floppyboy 7 ай бұрын
@@gabor.nadudvari depends on the system, many inverters work on a max of 600v, some are 1000v but thats pushing every connector on the solar array. best you go check your maximums on your kit, if you are getting 900-950, then I suggest thats your problem.
@MagicianMan
@MagicianMan 7 ай бұрын
Great content but I think you buried the lead on your first article on "DC Isolators"....................! Literally on the next paragraph down is the statement; "The Code applies to all stages of a project....... **The recommendations in this guide are NOT INTENDED for single residence dwellings (detached or connected), or to roof-integrated PV Panel systems" That's a very definitive distinction.
@junkerzn7312
@junkerzn7312 5 ай бұрын
So, those news media reports are ... ridiculously lacking in any detail or knowledge. A fire investigator can absolutely tell the difference between a fire caused by a solar panel, an isolator on the roof (a huge huge mistake), or a charge controller fire (typically situated inside or in a sealed enclosure). DC isolators exposed to the elements should be avoided ALWAYS. Now I know there was a time when I think parts of Australia tried to require them up on the roof for fire fighters, but manual isolators just shouldn't be up on the roof or ever exposed to the weather, even if they have IP65 or IP67 sealing. IMHO, I would avoid as much junk up on the roof as possible. The combiner box, for example, should not be up on the roof either. Backhaul the individual strings down to an easily accessible place for the combiner box. Why? * Manual DC isolators are usually NOT spring loaded and cannot quickly break ARCs. This causes carbon build-up on the contacts. Particularly at the voltages solar panels operate at. * Manual DC isolators CANNOT be switched under load, but most people do it anyway. This causes carbon build-up on the contacts. * Manual DC isolators DO NOT HAVE A THERMAL TRIP, meaning that they will not automatically trip on the most common failure case for manual DC isolators. * The contacts are extremely vulnerable to corrosion and oxidation due to exposure to the weather. This causes additional resistance. The carbon build-up and resistance ultimately creates a thermal event. The plastic casing will melt and depending on how it is mounted eventually catch something on fire. Having this up on the roof where it is difficult to inspect regularly makes it doubly dangerous. And that is why manual DC isolators should never be installed anywhere where they are exposed to the elements, or anywhere "just because it might seem like a good idea", by installers or anyone else. Use proper UNPOLARIZED double-pole DC breakers for your disconnects. The only DC isolator you ever see should be the one integrated into the solar inverter (if there is one). And even that might not be the best idea in the world. Proper unpolarized double-pole DC breakers rated for the solar voltages involved should be used pretty much wherever you want a disconnect. They should be in properly sealed boxes or inside and NEVER exposed to the elements. - Why unpolarized? Most people, even electricians, tend to wire polarized DC breakers incorrectly and in solar applications it is often impossible to wire them correctly because the power might flow both ways, and the short condition might also come from either side and thus also flow both ways. Unpolarized DC breakers typically do not have the two magnets on either side of the arc gap to direct the arc (polarized DC breakers typically have such magnets). - Why 2-pole. To properly isolate the subsystems you want to isolate both the positive and the negative. - Why DC breakers instead of manual disconnects? DC breakers have thermal trips, spring loaded disconnection, and ARC extinguishers internally. The typical failure case for a properly installed DC breaker is to trip rather than catch fire. - Automatically trips on over-current and instantly trips on a short, and can be tested as such. - But be warned that IMPROPER installation of a DC breaker (improper voltage range for voltages involved, improper use of a polarized DC breaker instead of using an unpolarized breaker) can also lead to a fire. -- Also, the wiring for a solar string MUST ALWAYS BE FUSED, in addition to any breakers. This is typically done inside the combiner box (and you should have a combiner box even if you aren't paralleling any strings). The fuse MUST be a 10x38mm 1000V DC ceramic fuse for solar applications, period, and the amperage should be as specified by the panel label. Each string must be separately fused (the combiner box typically has a fuse position for each string being combined, including if only one string). Some people argue about breakers and fuses on the same string, and think the breaker's function is somehow rendered useless by the fuse. It is not. That breakers and fuses serve two different functions. The fuse is the primary protection against a short. The breaker is primarily there as an ARC-safe disconnect, and also serves as a backup safety device against a panel short. Plus having a breaker at the combiner box AND ALSO just prior to the charge controller provides protection for wiring faults that backfeed through the charge controller from the battery. "Popping the fuse" IS NOT AN ARC-SAFE disconnect. Its a last resort if it didn't blow on its own and the breaker didn't trip either, but you don't pop a solar fuse as your "disconnect". You can only pull the fuse safely after turning off the breaker. -Matt
@postiemania
@postiemania 4 ай бұрын
I use specially designed Kraus and Naimer 1000 volt DC isolators. There are 2 lots of 3 poles in series in these isolators. Rule 1 never open the switch when it has a load on it. Started in the trade in 1974 and I might just know a bit more than some insurance Johnny.
@FutureSystem738
@FutureSystem738 7 ай бұрын
This was the law until recently in Australia. (ROOFTOP isolators) It caused HEAPS of fires! Finally the requirement of rooftop isolators has been dropped.
@maxbrooks1191
@maxbrooks1191 Ай бұрын
I never understood why roof top isolators were made mandatory over isolators that were mounted by the Inverter and better protected from weather,just doesn, t seem to be a safer way apart from being able to isolate at the cable run at the panel string,surely they are and have been more prone to failure.My Daughters installation from 5 years ago has both panels and on the wall external to inverter the Fronius also has it's own dc isolator switch.
@acelectricalsecurity
@acelectricalsecurity 7 ай бұрын
How is an isolator causing fires,some inverter manufacturers recommended or require separate DC isolators, despite their equipment having a built in isolator, so what happens then. As usual, things like this happen and there's no proper guidance we have several bodies giving conflicting information and the only losers are the installers and customers.
@JaymzFlood
@JaymzFlood 7 ай бұрын
If your pulling DC strings out of an inverter under load, you are dancing with the DC Arc Angels! Its not going to be nice for you in the right conditions. I'm an advocate for THE CORRECT TYPE of isolators.
@TheJensss
@TheJensss 7 ай бұрын
In many countries a DC isolator is required by law, and it is required to be mounted on a non flammable surface. Personally I think all electronics related solar panels including batteries should be mounted in a fire proof room, and ideally in a separate part of the house or in a separate building that are non flammable.
@blow0me
@blow0me 7 ай бұрын
likewise EV's, should not be allowed to be parked inside any garage that us integral to the house. But battery installations etc, should be outside, and have some fire detection/alert systems built in for an early warning
@TheJensss
@TheJensss 7 ай бұрын
@@blow0me A separate garage from the house is always smart. However, having batteries outside can be problematic because of low temperatures.
@blow0me
@blow0me 7 ай бұрын
@@TheJensss Safer than hot fires inside though. People need to accept the blatant reality that lithium ion batteries are dangerous. Even more so large ones/quantities of them
@TheJensss
@TheJensss 7 ай бұрын
@@blow0me Agree, that is why people should build a separate part of the house out of a non -combustible materials such as concrete, leca, bricks, etc. for batteries and solar components
@gg-gn3re
@gg-gn3re 7 ай бұрын
yep. laughing at this guy's video with a bunch of stuff on plywood in the back instead of having concrete board over the plywood lmao
@sergiofernandez3725
@sergiofernandez3725 7 ай бұрын
I am not sure I agree with RISCA, do they know something the IET do not? If there is no DC isolator then how do you isolate when you need to run tests on the panels and most importantly. In a few years time when you need to replace the inverter do they think it will be done at night so there is no DC voltage/Current? (I am assuming Domestic here) Very important point to consider is that not all Solar PV panels have an optimiser which detect no inverter and drop the output to 1volt. If they think the MC4s or the DC isolators are the cause they need to investigate if they are upto the job. are the MC4s on the panel compatiable with the installers MC4s connectors and crimp tool? Not all brands play together nicely. If they are upto the job was the install done properly by a competent person. Local isolation is in BS7671 for a reason and that reason is to save lives.
@deang5622
@deang5622 7 ай бұрын
You need to go back and listen to what Joe said. The IET regs on this say that a means of isolation *_IS_* required. There is no doubt about this. The question is around how that isolation is to be provided. Whether it be provided by a separate dedicated DC isolation switch or whether the integrated isolation switch inside the inverter is to be used, if there is one.
@sergiofernandez3725
@sergiofernandez3725 7 ай бұрын
@@deang5622 How would you isolate the solar PV string when you need to work on the inverter or replace the inverter?
@keswickcowboy
@keswickcowboy 7 ай бұрын
No load no problem. A trained and competent person would be able to work safely on a solar installation. Followed up with suitable and sufficient RAMS usually does the job.​@sergiofernandez3725
@Hipyon
@Hipyon 7 ай бұрын
With out a DC isolator you would have to make the PV connection in the night I can’t see how a dc isolator of the correct specifications can cause a fire
@persona250
@persona250 7 ай бұрын
Why ? The isolator on the inverted disconnects the circuit .
@edc1569
@edc1569 7 ай бұрын
MC4 connectors are protected, just don't plug/unplug it on load. The guys on the roof are plugging and unplugging them when installing anyway so there is no extra new hazard.
@deang5622
@deang5622 7 ай бұрын
Excessive contact wear possibly by switching too many times under load. Shouldn't happen to a good quality, suitably designed switch, but I bet it does.
@edc1569
@edc1569 7 ай бұрын
@@deang5622 You never disconnect an on-load DC circuit by means of an isolator.
@deang5622
@deang5622 7 ай бұрын
​@@edc1569People are gonna do it
@sirgregoir
@sirgregoir 7 ай бұрын
A legal requirement in Australia, roof mounted double pole isolator for Firemen to access during a fire.
@retrozmachine1189
@retrozmachine1189 7 ай бұрын
Are you sure about that? Checked the latest regulations? I think you'll find they do not have to be on the roof anymore, not least because of the ironic fire hazard. You now have the option of putting them elsewhere and simply having an indicated disconnection point on the array showing a place where a (MC4) connector is to be found that will disconnect the array from the downstream wiring. Despite the reason being given being for firemen to disconnect the array that was the opinion of one man and not the general recommendation of the firemen themselves. Firemen aren't stupid and don't want to get up on a roof of a building that is on fire and likely structurally compromised then falling through and being injured or dieing. Put simply, the roof top isolator did nothing for improving safety and actually resulted in several fires in Australia.
@brianwood5220
@brianwood5220 7 ай бұрын
The beard looks good on you , Joe. Thanks for the news. Happy New Year.
@efixx
@efixx 7 ай бұрын
Not as good as yours Brian! Cheers mate! 😊
@democracyforall
@democracyforall 7 ай бұрын
@@efixx The UK government should pass a law that clearly states that anyone who installs solar systems on the roof must make the roof fire proofe there is no other way to be hundred percent safe.
@jerome8670
@jerome8670 7 ай бұрын
@@democracyforallthere is … skilled workers ! To many acclaimed electricians who… A- can’t make an mc4 off correctly B- can’t ferrule crimp a flexible cable in the DC isolator C- use a torque driver on the connections or even panels That’s why there’s so many loose connections …. I’ve done a stack of solar and they do some amazing neat work … and then the connections are hooooorifix! (See what I did there😅)
@democracyforall
@democracyforall 7 ай бұрын
@@jerome8670 CORRECT so that is one of those reason the roof needs to made fire proof by law. the solar panel itself inside also is not perfect it catches fire in some cases even if you did it all correct so a law is needed.
@jerome8670
@jerome8670 7 ай бұрын
@@democracyforall 💯 the more fire proof items the better I’ve always wondered why h the there’s no AFDD’s on the DC side also?
@keswickcowboy
@keswickcowboy 7 ай бұрын
Solar strings are class 5 cables and should have an ultrasonic weld or a bootlace ferrule as a minimum. I've never seen any signs of heat damage with the above but too many without. Also, adhereeing to MI for torque settings and use a descent tool will certainly help to reduce lose terminations and heat.
@KA9DSL
@KA9DSL 7 ай бұрын
I use a snubber circuit (a resistor and condenser in series) across the contacts on the switch which stops the small dc arc across the switch when opening and closing the contacts. (it's old school man)
@errolpaul8043
@errolpaul8043 Ай бұрын
👍
@TRS-Tech
@TRS-Tech Ай бұрын
Victron kit is pretty good kit. Charge controlers and inverters are suposed to be mounted on fire proof boards anyway. Very sad to hear but glad everyone is alive but the fault could have been a multitude of things.
@christopherleubner6633
@christopherleubner6633 7 ай бұрын
You can but they need to be the tandem type breaks with a mosfet switch and isolates with a electromagnetic contactor. These are also built into several types of charge regulators as well.❤
@UKsystems
@UKsystems 8 сағат бұрын
Surely in the event that so equipment is catching on fire it should be placing something like a metallic enclosure more as a common sensing and a regulatory thing so you can have adequate ventilation but it will contain a fire
@billsbasementworkshop1902
@billsbasementworkshop1902 7 ай бұрын
How would we go about testing on an EICR if we can't isolate the DC comming in?
@JaymzFlood
@JaymzFlood 7 ай бұрын
you can isolate DC underneath the inverter and then carry on with your AC tests at the AC isolator :)
@pierrelombaard820
@pierrelombaard820 Ай бұрын
I searched for a DC isolator switch when installing my first solar system I could only find 160 volt DC switch Knowing the danger of isolating DC I wired my solar in serie and parallel for a maksim of 126 volt Since then the new inverters mppt range is 120 to 500 volt or higher That present a problem So the only way to isolate is to remove the load first Switch everything off before isolating the pv supply DC voltage and current flow cause a significant arc that is difficult to break and will burn the breakers Any carbon caused by the arc in the breaker switch area will cause current flow and eventually a fire 45 Jr ago I observed in training the switch used to isolate 400 volt DC The switch ( knife) had a separate blade parallel with the main blade that was attached to the main blade with a spring When opening the main blade, the auxiliary blade remained connected and pulling out until the spring can cause the final current break at high speed Faster than you can move the switch with your hand That was used on 400 volt DC system's Since then semiconductors scr igbt MOSFETs etc, made the need for isolating DC obsolete Now we isolate on the ac system side Solar pv isolating switch of the load current down to zero isolate.
@petermontgomery85
@petermontgomery85 7 күн бұрын
What is the difference between ac and dc isolators . Both have make and break contacts and should be rated at appropriate capacity. Normally there would be arc quenching filters to avoid contact arcing. As these isolators are only operated on a very low duty cycle it seems that the installation may be suspect.
@davidunwin7868
@davidunwin7868 Ай бұрын
Australia has had its fair share of solar house fires, many caused by faults in the DC isolators. Regulations and DC isolator designs have changed over time. A lot were caused by condesation forming inside the isolator which led to arcing. The design has changed a few times.
@calmeilles
@calmeilles 7 ай бұрын
Can someone explain how a DC isolator might cause a fire? Or how a fault that caused a fire might not have done so had there been no DC isolator installed? As Joe said there's a hefty line up of expertise behind this advice, so it should be taken seriously. But even so what is the _exact_ problem?
@ehsnils
@ehsnils 6 ай бұрын
Use of the wrong type of isolator or improperly installed would be my take, not that the isolator itself is the problem. Firefighters also don't like it if the solar panels can't be disconnected and might refrain from putting out a fire and instead go for letting the construction burn.
@sirgregoir
@sirgregoir 27 күн бұрын
It's the law in Australia, illegal install if there is no isolator.....!!
@MrEuan616
@MrEuan616 2 ай бұрын
The problem is people picking the wrong DC isolator and using them in the wrong configuration. Installers cutting costs by taking the link out and halving the current rating then putting two strings through the same DC isolator. DC isolators are also excellent for any maintenance or repair works, what if you cannot depend on the built in DC isolator? What if an MC4 has been damaged and you need to replace it? Poor workmanship and purchasing inferior products is the problem here not DC isolators.
@samfish6938
@samfish6938 3 ай бұрын
there are manufactures of breakers with magnets and arc chutes to quench an arc for high DC interruption. They are designed to open under load and quench the arc. Please note they are polarity sensitive as the polarity determines the direction of the arc blow in the magnetic field. Polarity must be observed to blow the arc into the arc chute instead of away from it. Many breakers for DC have low voltage ratings due to the difficulty in quenching an arc. For panel arrays, ensure the breaker is able to quench the open circuit voltage under load. Other DC disconnect devices have multiple series contacts to break the arc. Large gap knife switches work well as the gap when open is more distance than the current can mantain an arc. Use the type often used for inductive loads such as for a heat pump disconnect switch. Double break and an open distance greater than 1 inch is good to stop the arc. The distance is important the same way cutting the cable broke the arc. You need a large device with the ability to make a large gap when open. For over current protection, use the sand filled multi-element fuse for at least the rated voltage. The sand falls into the arc to quench it.
@A.Y.A
@A.Y.A 7 ай бұрын
The selected words of the week are fungus and gingerbread . And as always thank you very much. It's really fun to see the electricity news, I appreciate it very much.
@spoonss777Gaming
@spoonss777Gaming 7 ай бұрын
I see no reason to banish DC isolators seeing as the inbuilt DC isolators are exactly the same mechanism, seems ridiculous to me. Also how are you supposed to safely test short circuit currents without an additional DC isolator. (If you don’t have the pv specific test equipment)
@PhysicsViolator
@PhysicsViolator 10 күн бұрын
My dc isolators are rated for 400V while it’s 360 volts so it’s should be fine, never had a single problem so far..
@freddiewithers9617
@freddiewithers9617 7 ай бұрын
Just had a really fun time trying to pry off some old brittle mc4's under an old SMA inverter. Voc=800V - really would have appreciated a DC isolator!!!
@jerome8670
@jerome8670 7 ай бұрын
Just cut the cable …. Job done! The problem with DC isolators is that they causing more problems from loose connections arcing and burning out as opposed to isolating for maintenance! There’s not enough electricians who can do a ferrule crimp and connect correctly … they twist the flex or it splays out of the connections … I’ve seen some horrific connections on some amazing looking work!
@freddiewithers9617
@freddiewithers9617 7 ай бұрын
@@jerome8670 I do get it. I do think that during an MCS inspection they should have a proper look at the actual installation work rather than spending so long on the poxy quality management system that nobody cares about.
@jerome8670
@jerome8670 7 ай бұрын
@@freddiewithers9617 the MCS ….. feels like it’s just aiming completely in the wrong direction! Way too bureaucratic for me…. Like a chicken and an egg scenario …you can’t do solar with out being MCS buuut you can’t be MCS without knowing solar 😂
@kludgeaudio
@kludgeaudio 2 ай бұрын
I am not sure I understand what the DC isolators have to do with the fires described, which seem unrelated. I am also not sure I understand how a well-designed and properly-installed DC isolator could cause a fire.
@joeamos-somasystemspvbatte6
@joeamos-somasystemspvbatte6 7 ай бұрын
MCS install fail if you don't fit an isolator separate from the inverter so ill wait until there is an update telling me otherwise. Insurance company 'experts' Isolators don't cause fires unless you use an AC instead of a DC and vice versa.
@slavric
@slavric 7 ай бұрын
Thank you for this valuable information. When I was installing my panels last year, I already didn't put any DC isolator on the roof. All MC4 connectors are secured and ON the roof tiles, which are made of concrete. Electrical engineers are well aware, that the main problem in electrical circuits are contacts and switches. High voltage DC is the worst, if arcing starts, it will burn until the contacts are separated at least an inch or so. I have MC4 HV fuses on positive and negative side and a HV DC fuses before the inverter. Solar cables are laid separated about 2 inches, in case of rodents would eat thru insulation. I think this will do. Better safe then sorry.
@mrtechie6810
@mrtechie6810 6 ай бұрын
How do fuses help, unless you are connecting panels in parallel? In series, the fault current is already limited by the output of the solar panels!
@slavric
@slavric 6 ай бұрын
@@mrtechie6810 You are absolutely right. Since I have two fuses on each side of the string and another double DC fuse at the inverter side I'm hoping that in case of "mild lightning", I mean not direct lightning strike, fuses together with over voltage varistors would save my inverter. Each string gives 18Ap and fuses are 25A, so solar will never trigger them by itself. It's just my over engineering with a bit of hope in mind.
@andrewallen9993
@andrewallen9993 2 күн бұрын
As an electrical engineer I would just like to ask all the Sparky's on this channel how much temperature they think a small arc welder with IGBT's (so D.C.) generates. Then think of why they call it an arc welder😂
@bernardcharlesworth9860
@bernardcharlesworth9860 7 ай бұрын
Most inverter isolators are non lockable. DC isolators are double pole with air gap but some have screw terminals could this be the weak link. Maybe the connection should be mc4 as we see on Chinese made isolators
@edc1569
@edc1569 7 ай бұрын
What is the point in locking them, the voltage is still present on the MC4 terminals
@johnwaby4321
@johnwaby4321 7 ай бұрын
Very interesting. .can't see how a dc isolator would have caused the problem. .do the pv installers fit smoke alarms in the attic space .
@USA-GreedyMenOfNoIntegrity
@USA-GreedyMenOfNoIntegrity 27 күн бұрын
I guess you should’ve put all of your solar equipment on cement board, so that even if the switch burns up, it can’t catch anything on fire. Same with your batteries, inverters, solar charge controllers. Keep everything at least 20 feet from your house so that if it does catch on fire, it doesn’t burn your home down too. Stop putting solar panels on your roof. That should be common sense. Get some RF connected smoke detectors. Then buy some CO2 fire extinguishers to keep around.
@WayneMcNab
@WayneMcNab 28 күн бұрын
Question. What is a dc isolator, what does the circuit look like with one installed, how does it start fires?
@roberthuntley1090
@roberthuntley1090 7 ай бұрын
My solar PV system was installed in 2015, and has DC & AC isolators. So far the only failure has been the AC isolator (a couple of years after installation).
@thomashardin911
@thomashardin911 7 ай бұрын
My best bet would be some of THESE words: fungus, Joe, square, circle, gingerbread, Mail, air fryer. Teacher A Trade, flame, Icon, cigar, few frights, Swiss Army knife, Boy Scouts, Ultra, kit for explosive areas, Grizzly Adams, and torque calibrated arm Thank you :-)
@UKsystems
@UKsystems 8 сағат бұрын
Will the party telling you not to install isolators assist you if you have to replace an inverter? Are they going to come out and safely isolated because there are not many ways you can do that?
@errolpaul8043
@errolpaul8043 Ай бұрын
So what is the difference between the external isolator and the inverters built in isolator that makes the inverters built in isolator safer?
@Reaktanzkreis
@Reaktanzkreis 20 күн бұрын
Solar panels are current sources and sholud be handled like those. Never open the circuits in current sources , they have to be short- circuit. solar inverters use this method to inactivate the solar power. input. And you cannot protect current sources with fuses. Cuurent sorces got a high internal resistace (Ri) , high open loop voltage so exact the other way round than voltage sources like the electical mains. When install solar panels, never place connectors , taps or splittings underneath the roof /attic. Install wires in one piece from the panel to the inverter/charger. Use high cross sectional wire gauges, not because lower loss, but rather of the mechanical sturdiness. Install connection boxes in a fireproof environment e.g on a brick walls. Do not store flammable items in the vicinity of inverters and solar installations. Battery banks shoud not be installs inside of homes / flats. The best is a separate shelter apart from the house.
@eliotpalfreman1232
@eliotpalfreman1232 7 ай бұрын
Air fryer and gingerbread house, seem like additional oddities to me 😊
@dukemaximus1639
@dukemaximus1639 4 ай бұрын
I do not understand why UK electricians don’t explore micro inverters more. Easy to commission and much safer due to isolation and dealing with smaller DC voltage.
@pstanyer1
@pstanyer1 20 күн бұрын
Just how exactly can an dc isolator cause a fire.. If there is no power how does it set on fire...
@nervousfrog101
@nervousfrog101 6 ай бұрын
Handy info. I would be interested to know how old the PV systems were that caught fire. My oldest system has been in for 13 years now and it's not caught fire yet. Maybe I should start checking the DC isolators with a thermal camera as a precaution?
@johnwarwick4105
@johnwarwick4105 2 ай бұрын
Well that's an interesting concept. We allow companies to manufacture isolators that arnt fit for purpose and fail dangerously, then change the rules so they sent required anymore 🤷🏻‍♂️. In industry we often have multiple isolation points on motor circuits nobody ever said "you are introducing more potential failure points" what a cop out. 44 years since I started, back then if your isolator was rated at 32a 500v, that was it's all day rating 24/7/365. Would have been good for twice that short term. At the same time we have idiots complaining they can't fit solar batteries in lofts anymore.
@losttownstreet3409
@losttownstreet3409 7 ай бұрын
There should be some regulations to minimize the fire risks: as few components between charge controller and solar panels as possible, minimize wiring between each component and all component rated with safety in mind (700V array => rated for 700V + 20% => 900V). Why you need to connect all solar panels in series? 30V per panel and 120V to 240V should be enough to build an array to get the cables down. Look what a cable isolation fault on a 700V system looks like and you never put the + and - cables in the same pipe.
@garythespark6295
@garythespark6295 7 ай бұрын
I’m gonna guess fungus and gingerbread as the two words you had to sneak in.
@kiloohm
@kiloohm 7 ай бұрын
no mention of why Isolators are bad? why?
@jefftysoutube
@jefftysoutube 6 ай бұрын
Instead of an isolator, could a switch to ground be as effective? ( Or between + and - of the solar leads) This way the contacts are not in use until that time of need. Could be installed as a single use emergency device to ensure solar voltage is zero.
@XX-ww8lh
@XX-ww8lh 7 ай бұрын
Shame you don't explain why solar isolators are considered dangerous. Why is this?
@NicolasRaimo
@NicolasRaimo 7 ай бұрын
Livoltek battery in that solar training firms leaflet... cough reviewed that good system
@martinwinlow
@martinwinlow 6 ай бұрын
I am sorry for the friends and family of the man killed but how on earth is it the responsibility of a company that a tree happens to fall onto one of their workers? If we are saying that the man killed should not have been working outdoors in a storm then we are heading for very extended power outages during poor weather that will make today's mains failures look like a very minor inconvenience - waiting for 'acceptable' or 'safe' weather to fix things. Who decides what is 'acceptable' or 'safe'? *Surely* it has got to be the person (or his immediate supervisor) 'on the ground'? This is such a random event that could happen to *anyone* even someone happily sitting at home. We need to have a sensible system in place to prevent over-bearing and impractical safety regulation whilst at the same time providing compensation for those unlucky enough to be involved in this sort of tragedy (especially public service workers) without labelling companies (let alone individuals) as 'criminals'!
@karimali3477
@karimali3477 Ай бұрын
Is the course available online
@andysims4906
@andysims4906 7 ай бұрын
I’m glad I don’t have solar and never will
@mikerowe123
@mikerowe123 7 ай бұрын
Don't want a fire? ENPHASE.
@hikotech4065
@hikotech4065 6 ай бұрын
They should have installed In-line fuses for the solar panels then the DC panels wouldn't be a problem.
@JimWhitaker
@JimWhitaker 7 ай бұрын
But that recommendation clearly says: " . . . not intended for single residence dwellings . . . ". So HMO's and up?
@phizicks
@phizicks 7 ай бұрын
yet, I had my bypassed and the electrician found the installers did a dodgy job as he worked on the bypass. I only have the isolators next to the inverter now, even though they did a dodgy job there too.
@jwstolk
@jwstolk 7 ай бұрын
If the Victron system had no DC isolator switch, why mention it here? Are there no example cases where the DC isolator switch actually caused the issue?
@efixx
@efixx 7 ай бұрын
Australia has plenty
@jwstolk
@jwstolk 7 ай бұрын
@@efixx Then use those as an example, or make the video title match what issues are actually shown.
@europana7
@europana7 25 күн бұрын
Would fuses have prevented the panel fires?
@imval_tech
@imval_tech 6 ай бұрын
This is a serious allegation about Victron energy's MPPT. Do you have a source for that?
@michaelraab5669
@michaelraab5669 7 ай бұрын
Perhaps, with all the news of house fires allegedly being caused by photo voltaic systems, the creators of a training program might think of a different name than "Green Spark"
@Hipyon
@Hipyon 7 ай бұрын
This morning I tested a mc4 connector to see if it would burn result they support fire and do not self extinguish There for a damage mc4 plug in /out under load is a fire 🔥 risk
@efixx
@efixx 7 ай бұрын
Why should you ever need to disconnect under load ?
@Hipyon
@Hipyon 7 ай бұрын
they no why but if there is no isolator it could happen many soler System are install by in experience technician high voltage dc is not the same as ac and many early System were in install by unqualified technicians
@Hipyon
@Hipyon 7 ай бұрын
More important is mc4 burn
@michaelcostello6991
@michaelcostello6991 7 ай бұрын
Question. i rent a unit with a garage down stairs with only light circuit. probably has no earth (at least not at switch when i checked ). I want a power point supply to mess with hobby electronics only in shed. Can i take power off the light or is there a chargeable device that i can plug into mains in the unit and carry it downstairs to shed as a temporary power supply ? Thats assuming there is no earth at the light fitting when i get around to checking it.
@MS-ug8iu
@MS-ug8iu 7 ай бұрын
go for the full ZZ-Top!
@imscanon
@imscanon 7 ай бұрын
Advice please. I need 15kwh a day to power for power outages that can last from a couple hours to a few days. I'm in Michigan so my solar hours is 4.48, 1,278 Kwh per 1Kw, says need 4.24 Kwh array I'm looking at a 400w, 36v panel, says output DC 39V, 10.25a max, transfer efficiency greater or equal to 21% A MPPT Charge controller of 100a, says 12/24/36/48v Auto, Max Input 100v. Max charging current 100a. Max Input volts of panels should be 30v-45v (for 24v battery). Max Input power of panels should be 2000w. Output voltage DC5v/1.5a Inverter of 4000w/8000w Peak, Pure Sine Wave Power Inverter, DC24v-AC110 And Battery is LiTime 24v 100Ah, LifeP04 Lithium Ion, Build-in 100a BMS, 2,560 Wh Energy. Up to 4P2S (don't know what that means) 48v battery 400Ah of 20.48 Kwh It's only 1000sq' apartment, 2bd/2ba. Old Kenmore Fridge, elec range, micro, dishwasher (which I'd forgo during an outage), a couple computers and tvs, wifi, lights, a mini-fridge, that's about it. No washer/dryer and if I did use my hair dryer, it's 5 mins or less, but I don't use it every day (and my housemate is bald). For obvs. reasons I wanna keep the heat on and the fridge. We'd unplug things we don't need for a few days, but I'll stick with what we've averaged over the last year anyway just to be safe at the 15Kwh a day. Am I on the right track here? Too much, too little, just right? Any part of this not work with another or could be downgraded or done better/easier/cheaper? Any part of it I don't need? Anything I do that's not here? What I have here is about $1,450. Thanks for your time!
@georgescott6967
@georgescott6967 2 ай бұрын
I am far from an expert, but it seems to me that if you want to power your house for 2 days you will need 2*15k/2560=12 of those batteries. My suggestion is to radically rethink your requirements. The biggest power consumer that you mentioned is your range (I assume oven and hotplates) - suggest planning to use something else, maybe a microwave or little camping stove. You didn't mention what you use for house heating, so I assume that it is not electric. Using what you have you could probably keep the fridge and (low power) lights running. 4P2S means that you can connect a maximum of 4 of those batteries in parallel and 2 in series. There might be other problems with your configuration - I stopped looking after the first one. There are lots of good videos in yt about off grid solar. "Will Prowse" also does a lot of beginner friendly videos with good information.
@Martyn-ey9lw
@Martyn-ey9lw 6 ай бұрын
Sorry may be just I'm just a bit thick Please explain How does an isolator cause a fire
@tossancuyota7848
@tossancuyota7848 Ай бұрын
just use diodes and caps and breaker combo. this probably is caused by a reversal in transformer due to high sudden current surge
@oiuslags
@oiuslags 7 ай бұрын
How are you supposed to change a faulty inverter if you can’t isolate the dc & ac supplies ?
@MikeyisNinja
@MikeyisNinja 7 ай бұрын
Disconnect under no load with inverter off. Definitely less convenient than with an isolator.
@oiuslags
@oiuslags 7 ай бұрын
@@MikeyisNinja magic stuffed under a staircase trying to change an inverter with 300 volt dc cables swinging about hoping the sunshine doesn’t come-- double f-that
@MikeyisNinja
@MikeyisNinja 7 ай бұрын
@@oiuslags of forsure. My least favorite part is trying to shove live conductors into a dc charger or converter.
@multiskilledelectrician1
@multiskilledelectrician1 7 ай бұрын
What is the standard Cable size for solar power supply (from the panels to the solar charger?
@jwstolk
@jwstolk 7 ай бұрын
According to the standard, the wire size depends on the maximum current, but also the type of cable and conduit and the distance and acceptable voltage losses. The maximum current depends on the type of solar panel and when multiple panels are connected, how they are wired together.
@multiskilledelectrician1
@multiskilledelectrician1 7 ай бұрын
@@jwstolk thank you for response.
@dieseldragon6756
@dieseldragon6756 7 ай бұрын
I'm not a qualified Sparkie and perhaps I'm thinking about _old_ old PV panels here, but can modern panels produce enough current to cause fires if improperly isolated/not connected to a suitable load? If that's the case then long gone are the days when leaving a PV panel disconnected was safe - Sounds like we _Ha'a Goers_ need to start treating these with the same degree of care and caution as for a Li-Ion battery pack! ☀🔋🔥😳 Though if modern PV panels are *that* powerful, perhaps the concept of installing a couple on the walls of my North-facing flat is no longer as ridiculous an idea as it once might've sounded. If they can produce 200wH even in that sort of siting, that's still a saving¹ of 80p/day on my electricity bill... 💰😀 (¹ - That's of course before we start getting onto the cost of 2-4 PV panels, the inverter, and the fact that - Due to escape route considerations - My installation has no safe place to site a battery rack! 😉)
@GraemeMurphy
@GraemeMurphy 7 ай бұрын
Insurance companies are not electrical companies.
@the_industrious_electrician
@the_industrious_electrician 7 ай бұрын
Air fryer and Gingerbread. Great listen.
@deang5622
@deang5622 7 ай бұрын
That's three words, not two.
@the_industrious_electrician
@the_industrious_electrician 7 ай бұрын
@@deang5622 actually it's 6 words if we are being pedantic. At least someone read my comment 😂
@returner323617
@returner323617 7 ай бұрын
Gingerbread & Campari..? Good content, thanks.
SpaceX Finally Adresses Important Starship Catch Problem!
20:37
What about it!?
Рет қаралды 205 М.
黑天使遇到什么了?#short #angel #clown
00:34
Super Beauty team
Рет қаралды 42 МЛН
If Barbie came to life! 💝
00:37
Meow-some! Reacts
Рет қаралды 64 МЛН
WORLD'S SHORTEST WOMAN
00:58
Stokes Twins
Рет қаралды 188 МЛН
Harley Quinn's plan for revenge!!!#Harley Quinn #joker
00:49
Harley Quinn with the Joker
Рет қаралды 32 МЛН
5 MISTAKES to avoid when installing Solar ❌
12:25
Artisan Electrics
Рет қаралды 106 М.
The Jaw-Dropping Difference Between AC & DC Isolators!
5:39
I-Team: Hidden cameras reveal dark side of solar power
6:21
FOX 5 Atlanta
Рет қаралды 4,6 МЛН
Have we been doing Solar wrong all along?
13:30
Undecided with Matt Ferrell
Рет қаралды 1,9 МЛН
The Shocking truth about Who REALLY Owns England?
13:55
Paul Whitewick
Рет қаралды 354 М.
UK Parliament To Act On This Circuit Fault Danger
8:58
eFIXX
Рет қаралды 74 М.
DC Isolator - Wiring a Solar PV Disconnect Switch
13:18
Signature Solar
Рет қаралды 12 М.
Tesla Solar Roof Review: Was it Worth It?
30:27
Marques Brownlee
Рет қаралды 12 МЛН
黑天使遇到什么了?#short #angel #clown
00:34
Super Beauty team
Рет қаралды 42 МЛН