Hi Dave. I have moved to a flat with a Vitodens 100. I don t know how to operate the remote controller. Any ideas about instructions? Looked on website but can t find. Thanks
@grayhalf18549 ай бұрын
The connections to the nest link at 4:10 ... is there any voltage across that connection? Or is it simply powering the boiler up when the thermostat calls for heat and makes a connection across those two wires? (So just shorting them would mean the boiler would fire continuously??)
@chrisakester95463 жыл бұрын
Great Video followed it exactly, but I get cannot find opentherm device error when setting up the nest I have the same boiler I have temporarily wired it as an on off system but would like to use opentherm Do you have any suggestions
@DaveDoesUK3 жыл бұрын
Did you use the X21 cable harness?
@chrisakester95463 жыл бұрын
@@DaveDoesUK Yes I bought a new one
@sinner_87792 жыл бұрын
Hello, i set up my 050-w to opentherm and the pump its working non stop. The burner works ok. Any ideea why the pump its working non stop? When i mounted the thermostat i removed that link from 230v .
@eliotmansfield3 жыл бұрын
Dont suppose you could tell me the pinout for the brown cable with the choc block on the end for opentherm - my boiler doesn't have that connector, i can make one up easily enough - but I cant find a drawing which shows which is pin 1,2,3,4 on the actual PCB.
@DaveDoesUK3 жыл бұрын
There's a diagram on the black cover, I believe it is pins 1 & 2
@eliotmansfield3 жыл бұрын
@@DaveDoesUK Thanks - just looked at the pcb and pin 1 is marked.
@DaveDoesUK3 жыл бұрын
You can see it on this part of the video from the manual too kzbin.info/www/bejne/nZjScp1pataKZrc
@Maxiride Жыл бұрын
The manual also says that the jumper labelled D in the wiring diagrams has to be removed. Didn't saw this step in your video, did you remove it anyway?
@jlangham851111 ай бұрын
This wire/link/jumper had already been removed when the boiler was installed. But yes, you need to remove the jumper cable linking 1 and L. If you didn't remove this wire/link/jumper, the boiler would constantly run the heating.
@Maxiride11 ай бұрын
@@jlangham8511Thank you very much! Installed a Netatmo modulating thermostat and works smoothly.
@Billybobnob2 жыл бұрын
Do you need to do anything to make the boiler start using open them?
@jorkirasalas27262 жыл бұрын
Nest documentation seems a bit sparse. With OpenTherm connected does the boiler and pump run all the time? Or only when a CH period is scheduled?
@pareshcha96413 жыл бұрын
Hi Dave, could you let me know where you get the choc connector with the 4 brown wires for the open term from, as I have tried to google with no luck. Thanks
@DaveDoesUK3 жыл бұрын
Link is in the description
@pareshcha96413 жыл бұрын
@@DaveDoesUK thankyou
@iainlinfoot27813 жыл бұрын
Great explanation but as other comment, nest cannot find opentherm device, error H73. My boiler is 100w heat only not combi but shouldn't be a difference for opentherm? Contacted Viessmann and they told me this boiler has old protocol so not compatible with nest! - Does anyone have a fix?
@DaveDoesUK3 жыл бұрын
Maybe it only works if its the combi version with hot water. The model number of mine is WB1C 26kW if that helps?
@iainlinfoot27813 жыл бұрын
@@DaveDoesUK Yes mine is WB1B heat only and confirmed does not have OpenTherm. Very disappointing as its not clearly stated!
@chrisakester95463 жыл бұрын
@@DaveDoesUK mine is also the WB1C I even bought the X21 wiring loom from Veissman. What voltage do you have across the opentherm coupling?
@DaveDoesUK3 жыл бұрын
@@chrisakester9546 i see 6-7v
@DaveDoesUK3 жыл бұрын
Just a thought, have you done the factory reset procedure on the boiler itself?
@PereiraShane3 жыл бұрын
Hi Dave, u got the new 2021 boiler Veizzman vitodens 100w and the boiler installer said it nest does not work with that specific boiler. Any suggestions ?
@DaveDoesUK3 жыл бұрын
Mine was installed in 2013, and I fitted the Nest to it in 2017. Not sure what they have changed on the recent model you have, you should still be able to connect the Nest using the normal wiring diagram provided by Nest but you probably won't get OpenTherm.
@DannyDL1ght3 жыл бұрын
The new models with wifi have opentherm, your installer was most likely drunk or stupid
@PereiraShane3 жыл бұрын
@@DannyDL1ght thanks yeah I had to ring veissman support and they say Opentherm is compatible with nest and then finally got the installer to change it from ON/OFF to opentherm.
@DannyDL1ght3 жыл бұрын
@@PereiraShane do you also use the vicare app or not?
@PereiraShane3 жыл бұрын
@@DannyDL1ght @PainDannyful Yup I do have the veissmann app installed but since it's changed now to opentherm with Nest, Nest system takes over the operating controls for the boiler. The only thing I can control is hot water temp. Also Holiday feature on veissmann app is not available to me. So have to use Home/Away feature on Nest
@cavendishelectricals2 жыл бұрын
Top Man! A Star!
@MrKlawUK2 жыл бұрын
for the opentherm setup, is the 75c the radiator flow temperature? If so, is that the max and does it vary based on weather and/or load - so will lower flow temperature as the radiators approach the target temperature?
@DaveDoesUK2 жыл бұрын
Yes that is all correct. You may be able to set it slightly lower, depends on the energy efficiency of your home and how quickly you want your radiators to heat up.
@DaveDoesUK2 жыл бұрын
There's a good explaination on flow temperature here www.theheatinghub.co.uk/articles/turn-down-the-boiler-flow-temperature
@DaveDoesUK2 жыл бұрын
I've adjusted mine down to 65 degrees, seems to be working fine. Got my thermo set to 18 degrees, to keep the chill off. For 5 hours of use in the evening I'm using roughly £3 of gas per day.
@dacelticcross3 жыл бұрын
Is this the old vitodens 100 because the new ones have copper pipes inside ?
@DaveDoesUK3 жыл бұрын
Boiler was installed in 2013 according to the certificate I have.
@CrashUK283 жыл бұрын
I have vitoden 100 2021 it has copper pipes inside.
@BenjiMcbarett3 жыл бұрын
Hello, whats the supply option to 75 means ? I need to put to 75 everytime ? The temperature set to the Nest is bit the same on the boiler screen when Im running water. Anyone get an Idea ? Thank you
@Nickolas63000 Жыл бұрын
Doing it ok but hot water setup at 45 but viessmann is going higher than this value so for hot water it doesn't work