Diesel Generator fuel consumption | Diesel consumption of DG

  Рет қаралды 49,843

Mechanical Engineering Practices

Mechanical Engineering Practices

Жыл бұрын

In this video, we will learn to calculate per hour fuel consumption of diesel generator (10kVA to 1000KVA) at various load level i.e. 100%, 75%, 50%, & 40%. An obvious question when looking at buying a diesel generator is, how much fuel do they consume? Generator has a fixed RPM so we can work out how much fuel they will use across various load levels approximately? Actual usage may vary due to a number of factors so specific calculation method of the fuel consumption of diesel genset from capacity 10kVA to 1000kVA as under;
Most generator manufacturers use G/kWh as parameters, which mean how many grams (G) of oil the Genset consumes per kilowatt per hour? & then change unit to liters (L) to know that you are an hour Fuel consumption costs.
Generally, the fuel consumption of diesel genset is calculated according to 0.2-0.26kg/kWh. One liter of diesel is about 0.84-0.86 kg. Then 1KW per hour is 0.2-0.26kg divided by 0.84 = 0.238 liters-0.3 liters, multiplied by kilowatts equals to fuel consumption per hour.
So Genset consumes 0.26 Litres of diesel per kWh produced considering frictional losses & other factors.
.
.
.
#dg
#engine
#dieselengine
#dieselgenerator
#generator
#dgset
#gcet

Пікірлер: 54
@junaidsultan8687
@junaidsultan8687 Жыл бұрын
Very informative and also verified through IOT fuel monitoring solution.❤ Keep it up Sir❤
@mechanicalengineeringpract140
@mechanicalengineeringpract140 Жыл бұрын
Thanks
@SahilKhan-in4gd
@SahilKhan-in4gd 7 ай бұрын
Nice information thanks 🙏🙏🙏
@mechanicalengineeringpract140
@mechanicalengineeringpract140 7 ай бұрын
Thanks
@muzaffarshabir5937
@muzaffarshabir5937 Жыл бұрын
Nice, very informative..
@djtarunverma6743
@djtarunverma6743 Жыл бұрын
Bahut achhi jankari diye ho sir ..ye formula to Google me bhi nai milega 😊
@mechanicalengineeringpract140
@mechanicalengineeringpract140 Жыл бұрын
Thanks my dear, kindly share with your Friends Pls also watch oil change frequency of diesel generator
@mechanicalengineeringpract140
@mechanicalengineeringpract140 Жыл бұрын
Oil change link is kzbin.info/www/bejne/pKCvmZ6mgpKgaNU&feature=share9
@mechanicalengineeringpract140
@mechanicalengineeringpract140 10 ай бұрын
kzbin.info/www/bejne/j4C2kq2wYseIrbMsi=turwULRsUC94GPWp Kindly watch this newly uploaded video on bearing basics may be helpful for you Best regards
@shanugaur8218
@shanugaur8218 3 ай бұрын
Q1 Is this conversion factor of 0.26 ltr Per unit applicable to all Kinds of DG Sets ( Greaves , Ashok Leyland , Cummins ) Q2 How did you arrive at this conversion factor of 0.26 ltr/Unit.
@mechanicalengineeringpract140
@mechanicalengineeringpract140 3 ай бұрын
This factor is considered by any DG OEM manufacturer Best Regards
@AyanJani-ox6zc
@AyanJani-ox6zc 10 күн бұрын
Sir 25 kv Ka generator hai .. rpm 20 par hai km Kaisy Hoga
@mechanicalengineeringpract140
@mechanicalengineeringpract140 8 күн бұрын
20 rpm NAHI hota. DG normal RPM are 1500 and high upto 1800. It can control from AVR by resitting frequency at 50HZ if is is not adjusted to desire rpm, pls check governor functioning and also check fuel injection system thoroughly and calibrate if required. oil pump malfunctioning also shows this problem, check rotor chrome of pump as well Best Regards
@djsjsjjsbsbsbdbdb5970
@djsjsjjsbsbsbdbdb5970 8 ай бұрын
Thanks
@mechanicalengineeringpract140
@mechanicalengineeringpract140 8 ай бұрын
Welcome
@zeeshan9888
@zeeshan9888 Жыл бұрын
Thanks sir g
@CeyhunAbasov-lq8pr
@CeyhunAbasov-lq8pr 3 ай бұрын
If I run a 20kva diesel generator at 0%, does it use more or less fuel?
@mechanicalengineeringpract140
@mechanicalengineeringpract140 3 ай бұрын
It will be run in underload which is not recommended due to more torque required. Less 40% is underload consuming high fuel and more than 75% is overload, will also consume more fuel so safer range is 40% to 75% load on genset in term of efficient fuel consumption and also to avoid erosion in moving n mating parts of dg Best regards
@sachingaikar1197
@sachingaikar1197 Жыл бұрын
Hi sir 0.26 per kwh per diesel use hota he lekin 0.26 he kya he or kahase liya
@mechanicalengineeringpract140
@mechanicalengineeringpract140 Жыл бұрын
I ưill upload complete calculations soon. Regards
@sachingaikar1197
@sachingaikar1197 9 ай бұрын
@@mechanicalengineeringpract140 ok sir
@rajeshbariki8266
@rajeshbariki8266 3 ай бұрын
Sir to convert kva to kw 0.8 stand for??
@mechanicalengineeringpract140
@mechanicalengineeringpract140 3 ай бұрын
It is power factor i.e. 0.8 Best Regards
@muhammadtauqeer8717
@muhammadtauqeer8717 Жыл бұрын
V informative
@mechanicalengineeringpract140
@mechanicalengineeringpract140 Жыл бұрын
Thanks
@user-jw2ky9yc3e
@user-jw2ky9yc3e 11 ай бұрын
Sir,koi v DG ho uska normal fuel consumption, 0.26 hi hota hai??
@mechanicalengineeringpract140
@mechanicalengineeringpract140 11 ай бұрын
Yes in ideal conditions
@rakeshdalai7005
@rakeshdalai7005 3 ай бұрын
But bhai 1 unit ko kese 0 .26 diesel consumption higa malum nehne hua pls thoda expelain kejeye
@mechanicalengineeringpract140
@mechanicalengineeringpract140 3 ай бұрын
It is conversation factor which is taking into consideration while assembling of any DG by oem manufacturer Best regards bhaiya
@sheshnathsingh9465
@sheshnathsingh9465 3 ай бұрын
HEMM engine ka bhi banao
@mechanicalengineeringpract140
@mechanicalengineeringpract140 3 ай бұрын
Ok my Brother
@debasisdas9667
@debasisdas9667 3 ай бұрын
0-40% pe jyada fuel consumption kiun kartahe ?
@mechanicalengineeringpract140
@mechanicalengineeringpract140 3 ай бұрын
Torque load is increased when we operate DG underload at less than 40%. In this case DG takes definitely high fuel than recommended Best Regards
@CeyhunAbasov-lq8pr
@CeyhunAbasov-lq8pr 3 ай бұрын
@@mechanicalengineeringpract140What is the main reason for low consumption of diesel fuel?
@mechanicalengineeringpract140
@mechanicalengineeringpract140 3 ай бұрын
There are many factors involved for less fuel consumption 1. DG working with in safe operating range i.e. 40% to 75% load. Beyond this range, will result more fuel consumption, erosion in moving parts etc. 2. Calibration of fuel injection system when required 3. Timely oil change as per recommended frequency of particular DG whatever it is. 4. Balanced connected load on three phases. Unbalanced connected load like phase one-100A, phase two-140A, phase three-90Amp which is not recommended so all phases load should be equally distributed like phase one=100Amp, phase two=100Amp, phase three= 100Amp 5. DG consume engine oil due to eroded rings, pistons,liners, valves etc. so DG should be got top end or major overhaul depending upon requirements Best Regards
@CeyhunAbasov-lq8pr
@CeyhunAbasov-lq8pr 3 ай бұрын
@@mechanicalengineeringpract140 Çox sağ ol. Generator test rejimində işləyirsə, daha çox və ya az yanacaq sərf edəcək?
@mechanicalengineeringpract140
@mechanicalengineeringpract140 3 ай бұрын
@@CeyhunAbasov-lq8pr I don't understand your language also this message have no any easy translate option
@jyotirmoyghosh95
@jyotirmoyghosh95 11 ай бұрын
Dhanabad
@mechanicalengineeringpract140
@mechanicalengineeringpract140 10 ай бұрын
kzbin.info/www/bejne/j4C2kq2wYseIrbMsi=turwULRsUC94GPWp Kindly watch this newly uploaded video on bearing basics may be helpful for you Best regards
@BHAGWANGOYAL-nv6wl
@BHAGWANGOYAL-nv6wl 3 ай бұрын
20% load par kitana consumer hoga
@mechanicalengineeringpract140
@mechanicalengineeringpract140 3 ай бұрын
It is not recommended to use any Genset on 20% load. safer range is 40% to 75% connected load on Genset and fuel consumption will be calculated as described in video. At 20% load, generator will run on underload ,will produce more torque resulting more fuel consumption as per recommended factor of 0.26 Best Regards
@g.gunanithi4354
@g.gunanithi4354 5 ай бұрын
How come 0.26 Please let meknow sir.
@mechanicalengineeringpract140
@mechanicalengineeringpract140 5 ай бұрын
It is factor which is used to calculate capacity of any DG while assembling by OEM manufacturer Best Regards
@mdabuzafar5958
@mdabuzafar5958 7 ай бұрын
It's for kirloskar dg
@mechanicalengineeringpract140
@mechanicalengineeringpract140 7 ай бұрын
For all makes of dg
@mechanicalengineeringpract140
@mechanicalengineeringpract140 7 ай бұрын
Its for all makes of dg Cummins Perkins CAT Kirlosker, volvo, DP, Rolls-Royce. Ford, Millat, khonyser etc.
@Lokeshkumar-lf5kt
@Lokeshkumar-lf5kt 7 ай бұрын
.26 kya h Iska samajh nhi aaya
@mechanicalengineeringpract140
@mechanicalengineeringpract140 7 ай бұрын
It is factor for designing of any capacity fc. Gensets are assembled considering this factor of FC Best regards
@purushottamraj1
@purushottamraj1 9 күн бұрын
Bhai urdu mein kyon bol rahe ho english mein bol detey samajh nahin aaya kuchh points
@mechanicalengineeringpract140
@mechanicalengineeringpract140 8 күн бұрын
As desired, Kindly share your WhatsApp so can I explain you in English
Chadha Sunil Generator 10 kva 25kva 30 kva 40 kva 50 kva 62 kva Generator Price Dispatch to Channai
9:13
Chadha Generators Private Limited Ladwa Kurukshetra
Рет қаралды 1,2 МЛН
Finger Heart - Fancy Refill (Inside Out Animation)
00:30
FASH
Рет қаралды 31 МЛН
НРАВИТСЯ ЭТОТ ФОРМАТ??
00:37
МЯТНАЯ ФАНТА
Рет қаралды 9 МЛН
Lehanga 🤣 #comedy #funny
00:31
Micky Makeover
Рет қаралды 26 МЛН
Diesel Generator Size Calculation | How to Calculate the DG Size (KVA)
9:33
MEP TECHNICAL WORLD
Рет қаралды 67 М.
How to compute specific fuel oil consumption
6:08
KEEP IT Jelord
Рет қаралды 18 М.
How To Choose The Right Power Generator For Your Home
12:12
Slater Young
Рет қаралды 246 М.
Diesel Generator Parts and its Functions | Major Parts of DG Set
12:41
MEP TECHNICAL WORLD
Рет қаралды 145 М.
Finger Heart - Fancy Refill (Inside Out Animation)
00:30
FASH
Рет қаралды 31 МЛН