ECM to PSC Blower Motor Conversion (Detailed)

  Рет қаралды 161,382

Zack’s in the Shop

Zack’s in the Shop

Күн бұрын

Tradesman Podcast - thetradesman.li... HVAC Shop Talk Podcast - workingjoes.lib... Get on the Shop Talk Email List - eepurl.com/c2eywf

Пікірлер: 120
@USA-GreedyMenOfNoIntegrity
@USA-GreedyMenOfNoIntegrity Жыл бұрын
One thing you want to be careful about when replacing a variable speed or a constant torque motor with a PSC is that you can overload the new PSC motor even if it is the same fractional horsepower rating. The blower wheels are usually bigger on variable speed and constant torque motors for the same tonnage system. That’s why we install variable speed or constant torque motors because they can develop higher static pressures helping on lowballer, jackleg ductwork. So, upsizing a fractional horsepower rating size is recommended when going from VS or CT to PSC. You can always use a lower blower speed, but if you’re overloading the motor and your CFM is already 25% low, there’s not much you can do but change the motor out.
@DayClanTribe
@DayClanTribe 3 жыл бұрын
Was so cool to see you put that grommet in. It was driving me crazy looking at all the wires passing through all those unprotected locations.
@DayClanTribe
@DayClanTribe 3 жыл бұрын
I really respect techs that don't push the new system sales and can salvage a unit and save people money. And then there's the Super Techs that go above and do a nice job and take pride in their work.
@ethelryan257
@ethelryan257 Жыл бұрын
@Harupert Beagleton I work in a related field. Master Electrician. One of my brothers is HVAC and his side of the business occasionally has us pull and replace motors. This was good work. One thing I always do, any parts not needed for the mounting set-up get yanked. I've seen those rubber vibration dampers at the front and rear pull loose. No problem at the rear, in the front, though, can make one heck of a racket. I'm glad you warned about capacitors holding a charge. It's useless, of course, the mucho-machos are incapable of learning, but more than enough joules there to kill you - and way more than enough to fry sensitive electronics, even if you don't care about the danger to people.
@kaochao8882
@kaochao8882 Жыл бұрын
That's what I do to help my customers, too.
@Imwright720
@Imwright720 4 жыл бұрын
Why doesn’t anybody check if the module or the motor is bad. The module can be replaced separate of the motor. Module alone runs a little under 400 but labor is quick. 2 bolts and 1 plug. Recommend to the customer to have a whole house surge installed. I do need to learn changing it to the other motor. Thanks for taking the time.
@pattanzi2673
@pattanzi2673 8 жыл бұрын
My unit had an x13 control board. I had to replace it with another ECM and I had to have it programmed. I'm sure I could've put a PSC in but I had to change the board also or put relays in. This board has its 24volts in and 24 volts out for controls to the motor. My 240v was connected on the line side of the transformer. But it worked out. Got the motor the sameday and installed it. But it will burn again because the duct work was an abortion. The airflow must be so bad. I did advise them. Also lucky you, your was outside, mine was in the 140 degree attic. Bro. I was dying up there. I actually turned on the condenser let the coil get cold and ran the attic fan. It was better then nothing. LMAO. NICE WORK AS ALWAYS BROTHER. BE SAFE OUT THERE.
@joeykohout8710
@joeykohout8710 6 жыл бұрын
You definitely got lucky with that unit. Seeing as it had a control board that was meant for a PSC motor. Especially with a gas pack. I did one on a Nordyne gas pack couple weeks ago and was not that lucky. Had to add relays. I was thinking maybe I could get a different control board from Nordyne that was used with a PSC motor but that board is almost $300 if I remember correctly. So it was a lot easier to just add relays
@jacklowe3788
@jacklowe3788 3 жыл бұрын
So I'm little rusty on field work been about 20yrs- So when I got out of the trade these were. I ming on - Now I have 12 yr old Trane xr13 unit w/ Air handler that has 3 circuit boards- House hit by lighting at least main board fried but because age & expense was thinking about cutting all the boards wiring out running old school motor w/ capacitor relay just having one speed- Is this reasonable on old unit w/ no warranty but otherwise looks like new?
@AmalgmousProxy
@AmalgmousProxy Жыл бұрын
I was just considering if this was possible, so I did a search and found this video. Those ECM motors are stupid expensive. This one was killed by an electrical surge (guess, customer said power flickered during a storm and that was it). Unfortunately I have to add a relay, but that's nothing. A PSC motor, relay and cap is far less than just a ECM motor. Thanks!
@derrickowens3072
@derrickowens3072 8 жыл бұрын
I've done that a lot with those they make it so easy to go back to psc
@zacksintheshop
@zacksintheshop 8 жыл бұрын
Oh yes, this was nice with the taps on the board already
@albertastorms
@albertastorms 6 жыл бұрын
I am not a fan of multi speed or variable speed fan motors on a furnace or air handler and two or more stages on both heat and ac because I find a single stage heating and cooling system in my home does not fluctuate the temperatures when cycling therefore I feel comfortable!
@Brandon-to9vp
@Brandon-to9vp 3 жыл бұрын
Also carrier package units with lh33wp003 are easy to replace just have to relocate g wire off ecm board and plug it back into lh33 board haha
@travisk5589
@travisk5589 6 жыл бұрын
So Matthew McConaughey has been Moonlighting as an HV AC repairman. Nice.
@davidchipman6573
@davidchipman6573 4 жыл бұрын
Alright
@XMguy
@XMguy 4 жыл бұрын
You kept the X13 board. My X13 ECM went out. I’m looking to convert mine to PSC too. I didn’t think I could use the X13 board. I like your mod.
@Brandon-to9vp
@Brandon-to9vp 3 жыл бұрын
Buy a ge evergreen plug and play and you won't burn your house down
@jonfarrell9053
@jonfarrell9053 4 жыл бұрын
Why didn’t you check to see if the motor was good and just the module was bad? I just bought the module after testing and showed the motor was actually good and only cost me 184$ and not 300- 500 for a whole new motor.
@newstart49
@newstart49 2 жыл бұрын
Of course you must check the motors amp draw with ALL of the panels/covers in place.
@joeywhisnant9948
@joeywhisnant9948 5 жыл бұрын
I believe u meant 24v coil,to allow line voltage to pass thru the motor........or just replace the motor module itself. Only 2 screws,and a small plug. 99 out of 100,motor good, module bad.
@mikereynolds6118
@mikereynolds6118 4 жыл бұрын
5:33 Says The Tech with A Black and Decker Drill. LOL!!!
@handymanbrian8269
@handymanbrian8269 5 жыл бұрын
i still have a 22 yar old carrier furnace. im not looking forward to a new r410 system!
@joeydelmarsjr.646
@joeydelmarsjr.646 5 жыл бұрын
same more pressure more issues
@prettycureforever7102
@prettycureforever7102 3 жыл бұрын
@@joeydelmarsjr.646 No not really its really good we just installed one at my home its running real quite and the be ecm motor is great too starts up slow then ramps up
@joeydelmarsjr.646
@joeydelmarsjr.646 3 жыл бұрын
@@prettycureforever7102 what seer make and model is it
@USA-GreedyMenOfNoIntegrity
@USA-GreedyMenOfNoIntegrity Жыл бұрын
Yes, you need to recommend new or additional ductwork, larger filter surface area. 1.8A on a 1/2HP. Guess what happens when you have low airflow in the summertime? You end up with a high temperature drop. Guess what happens when a cold steel heat exchanger is exposed to very humid outdoor air, whether it’s in Florida or up here in the hypocrite belt. Condensation and rust!
@metime-kw4tx
@metime-kw4tx Жыл бұрын
Hilarious "hypocrite belt"
@eddiesellers8522
@eddiesellers8522 8 жыл бұрын
great video. I enjoy the "out of the box" process thought when changing x13 over to psc motors. one question, in your years of service do you think the A/C units (of any type) are getting made more poor vs the units 15 - 20 years ago?
@zacksintheshop
@zacksintheshop 8 жыл бұрын
they are made to satisfy the government instead of the customet
@Ed-gc6ln
@Ed-gc6ln 4 жыл бұрын
It mostly comes down to install and pm. Done right, the unit will last a good 20 years. Done wrong.. it’ll be a trane wreck from the start.
@cutabove9046
@cutabove9046 4 жыл бұрын
Considering the age of the unit (7 years) should not the motor been replaced for free under warranty? And that being the case wouldn't it make sense to use the exact oem replacement motor?
@zacksintheshop
@zacksintheshop 4 жыл бұрын
That only applies to warranties that are registered
@etlawson6939
@etlawson6939 3 жыл бұрын
I got a carrier on order. 17 days ETA.
@dynasty4851
@dynasty4851 2 жыл бұрын
So much for the customer getting variable speed again. At least it didn't cost them an arm and a leg
@zacksintheshop
@zacksintheshop 2 жыл бұрын
The original was not variable speed, it was an X13
@phillipjoy8191
@phillipjoy8191 8 жыл бұрын
When you change from ecm to psc do you change horsepower ? Good video
@zacksintheshop
@zacksintheshop 8 жыл бұрын
+Phillip Joy you can in some cases but I chose to go back with 1/2 hp in this case.
@joecamp32
@joecamp32 2 жыл бұрын
Man you make this look easy, is it possible to do this with a different board then that one for example my blower was ran from a control transformer for high voltage power via a common and 240 volt wire. Then the low volt was ran from “x13 spd, x13g, x13 com”. I disregarded those and the common and 240 volt to the control transformer and routed the control transformer to a relay. On the relay I have my motor common and motor high and the common from the ct on the open circuit to other common and the medium speed to the 240 volt via closed circuit on relay. What do I need for the 24v on the relay and when I do so, how do I get the thermostat to communicate with the blower and compressor.
@cameroncameron4792
@cameroncameron4792 5 жыл бұрын
Nice job thanks.
@chicoabdallah3944
@chicoabdallah3944 6 жыл бұрын
Good video was very helpful thank you
@zacksintheshop
@zacksintheshop 6 жыл бұрын
Thanks for watching
@acrepairnearme
@acrepairnearme 6 жыл бұрын
Cool video. Very cool explanation!
@kaochao8882
@kaochao8882 Жыл бұрын
Thanks for the video
@RobHVAC
@RobHVAC 8 жыл бұрын
Nice repair.
@mylummechanical
@mylummechanical 8 жыл бұрын
thanks for the detail!
@bobpaulino4714
@bobpaulino4714 Жыл бұрын
Always check tesp.
@joeydelmarsjr.646
@joeydelmarsjr.646 3 жыл бұрын
just replaced my rheem seer 10 3.5ton with rheem seer 16 4ton and this came with and x13 i hope it lasts if not im going psc once the warranty dies
@zacksintheshop
@zacksintheshop 3 жыл бұрын
I am sure it will last forever.
@joeydelmarsjr.646
@joeydelmarsjr.646 3 жыл бұрын
@@zacksintheshop forever? No way
@nathanhouk402
@nathanhouk402 3 жыл бұрын
Oh yes...FOREVER! X13 modules are as reliable as the sunrise!!
@joeydelmarsjr.646
@joeydelmarsjr.646 3 жыл бұрын
@@nathanhouk402 i got 10yrs of warranty to replace that x13
@jamesgutierrez8606
@jamesgutierrez8606 2 жыл бұрын
I'm dealing with a wimpy 2 ton heatpump that needs more balls for the indoor fan speed,they want to feel that air hit their skin
@zacksintheshop
@zacksintheshop 2 жыл бұрын
That’s tough since the right airflow may not offer them that result ( of course it can be just wimpy like your saying)
@jamesgutierrez8606
@jamesgutierrez8606 2 жыл бұрын
@@zacksintheshopI feel responsible even though I can walk away I am going to see if the company I bought it from will exchange it for a three ton package and I'll pay the difference in cash if they would kindly accept the unit back that's the only way I can make it happen right away if I have the money I would just get them another one right away and sell their unit if
@Cg41418
@Cg41418 2 жыл бұрын
Some smart engineer had nothing to do and designed those ecm blowers instead of keeping it simple with a psc. And then charge double for the ecm.
@rodneythornhill9526
@rodneythornhill9526 7 жыл бұрын
good job
@austingerrard2667
@austingerrard2667 6 жыл бұрын
Im looking to replace my furance, condenser and A Coil. Should I buy a Variable speed or multi speed blower furance?
@aztecautos6337
@aztecautos6337 3 жыл бұрын
I'm working on the same thing it's rotation is clockwise I need it to be counter clockwise is there any way to reverse rotation ?
@joeshearer1247
@joeshearer1247 8 жыл бұрын
Award winning duct system lol
@DoeyPP
@DoeyPP Жыл бұрын
When you replace the emc motor and replace it do you use the same hp?
@socalcomfort2342
@socalcomfort2342 Жыл бұрын
Were did you hook up your black wire to
@skoservices4619
@skoservices4619 6 жыл бұрын
if i connect high voltage to contactor directly and just cover all old ecm wires with tape it will work too no?
@pedrocastano6410
@pedrocastano6410 3 жыл бұрын
24/7
@keithwray2587
@keithwray2587 6 жыл бұрын
This is great, wish all was done this way lol
@montygo2003
@montygo2003 3 жыл бұрын
i just installed an ecm x13 motor the rotation is counter clock but this new motor is going clockwise it suppose to run for 30 second and stop then go counter clock but it never did that even after 5 minutes ,is there a way to make it go opposite direction? counter clock
@JeremyFloyd-s3j
@JeremyFloyd-s3j 29 күн бұрын
I little shocky shock 😂
@nickh5585
@nickh5585 8 жыл бұрын
Good video bud
@tomcat27557
@tomcat27557 7 жыл бұрын
good repair!
@alejandro85
@alejandro85 4 жыл бұрын
VERY GOOD VIDEO WOW THANKS
@zacksintheshop
@zacksintheshop 4 жыл бұрын
Thanks
@joshuameadows5574
@joshuameadows5574 7 жыл бұрын
Quick question a lot of times especially on carrier,comfortmaker ,bryant etc the x13 motors will have two speeds that are tapped into the blue wire is usually going to low voltage terminal 2 and white for low voltage tape 4 . My question is what is the purpose of that if even in a heat call you have a g call which would activate low voltage terminal 2 medium speed. Is is a safety ?
@zacksintheshop
@zacksintheshop 7 жыл бұрын
+joshua meadows for heat strip calls (like emergency heat)
@Zelaznogsiul-63
@Zelaznogsiul-63 5 жыл бұрын
Great video. How do you figure out the rpms, I was working with one of those X 13 motors but I did not see the rpm on the motor just the horsepower.
@jonfarrell9053
@jonfarrell9053 4 жыл бұрын
How do you know when you can bump up the CFM. My diagram says it should be on 2 but I was wanting to bump it up to 3. The heaters on 4 and 5 is open. 1-5 are all active but I was concerned that going to a higher CFM my be bad and I was hoping you could elaborate on that or direct me to one of your videos if you already covered that
@RM-np1gm
@RM-np1gm 3 жыл бұрын
Increasing or decreasing CFM affects both cooing and heating. Cooling side is the compressor and evap, slow the CFM and the evap can freeze/ice over which is a death spin. More frost less air moving through it which = more frost/ice. Continue and liquid refrigerant can get to compressor which isn't what you want. To high CFM and it can affect the efficiency of the evap to remove heat. All components are designed to match each other. Experiment but monitor. Check all air duct and passageways prior to ensure all is right before. Same on heating side. If furnace, to high cfm and the airflow doesn't match the heat exchanger so it can either trip off on high limit or you get more cfm but register outlet temps are lower. In winter it can feel drafty. Find your desired register outlet temps and experiment.
@realSamAndrew
@realSamAndrew Жыл бұрын
@@RM-np1gm if you move air across the heat exchanger too fast, wouldn't that lower the possibility of high limit, since you are pushing the heat away from the unit quicker? When limit trips, fan stays on to cool it down.
@jorgeuribe4512
@jorgeuribe4512 Жыл бұрын
How come you didn’t use one of those boards? That you just connects the old plugs into it ?
@johntrauger68
@johntrauger68 6 жыл бұрын
Chicken in a car, and the car won't go. That's how you say Chi-car-go.
@liberaltearsaredrowningme7049
@liberaltearsaredrowningme7049 6 жыл бұрын
john t do you by chance work at walmart as a cart checker? What size bus did you ride in?
@johntrauger68
@johntrauger68 6 жыл бұрын
Actually. no. I was "fucking around." I'm at this channel curious as to why industry found it necessary to upgrade from a relatively easy and cheap to maintain capacitor motors, to complicated, expensive 12-pole/with built in inverters to move air. After all, I'm not sure many service tech's out there are versed in pulse width modulation or phase control techniques in controlling induction motors. So how does industry get around that? Create more parts changers. Now I see there is a push back to switch to old school. Bravo!
@acrepairnearme
@acrepairnearme 7 жыл бұрын
Coooool!!! Very interesting)!
@bigdaddy5948
@bigdaddy5948 11 ай бұрын
Nice
@robertspadezhinton
@robertspadezhinton 6 жыл бұрын
I'm new to the field...I was told to buy leather gloves....your not wearing leather gloves...do it matter
@iskoos
@iskoos 5 жыл бұрын
Hey Zack, Thanks for the great video. Could you please explain the reason behind selecting lower blower rpm on heat and higher on cooling mode? Is higher rpm on cooling mode simply to prevent a possible freeze up on evaporator coil? Or something else? Thanks
@Ed-gc6ln
@Ed-gc6ln 4 жыл бұрын
iskoos low speed for heat slows the air to pick up more heat from the exchanger. Cooling needs higher air flow to remove moisture from the air, with out it freezing to the coil
@willys7974
@willys7974 Жыл бұрын
Colder air is more dense and requires more rpm to move.
@galigalindo6839
@galigalindo6839 7 жыл бұрын
Hello sir. How can i get in touch with u asap
@rudyrangel5910
@rudyrangel5910 3 жыл бұрын
Gemaire is the shit
@raybosflorida4928
@raybosflorida4928 5 жыл бұрын
hi,,CAN ANYONE HELP??,,got blower motor only comes on when t-stat is set to ON,,does not come on in AUTO,,just hear a click,,,TRANE;;;mod;;4teh3f36b1000ab,,,,everything works fine but airhandler fan on ly comes on ,,in ON
@BestHVAC
@BestHVAC 4 жыл бұрын
Most likely the air handler circuit board is bad. Seen a few like that.
@joeydelmarsjr.646
@joeydelmarsjr.646 5 жыл бұрын
are the bastard child x13 worth it or just get psc for my new ac unit furnace ??
@MarciaSilva-sv8jg
@MarciaSilva-sv8jg 5 жыл бұрын
Get psc. Ive seen these ecm modules fail after one year! Any power issues will kill the board in the module
@juantapia8079
@juantapia8079 8 жыл бұрын
how does that tester read cfm? i doesn't look familiar to me. Greetings
@zacksintheshop
@zacksintheshop 8 жыл бұрын
You input free area and the vane measures air speed across a return grill
@juantapia8079
@juantapia8079 8 жыл бұрын
Whats the name for the meter?
@zacksintheshop
@zacksintheshop 8 жыл бұрын
+Juan Tapia UEI DAFM3
@juiceybananas5489
@juiceybananas5489 4 жыл бұрын
As the ecm motors are trash for the most part and over priced to boot, switching to the psc motors is a no brainer.
@stephwaylonwells3218
@stephwaylonwells3218 2 жыл бұрын
👍
@qwikproduct
@qwikproduct 6 жыл бұрын
We have a universal ECM replacement that makes ECM to PSC conversion much easier. Check out this demo: kzbin.info/www/bejne/fJnYqmOqjK6jaJo
@russelllieser4226
@russelllieser4226 10 ай бұрын
Only a hack would do this.
@justdissin7340
@justdissin7340 5 жыл бұрын
Omg i didn't think this was possible to do,they charging me like $1,000 to change the ecm motor,i did just a standard motor cant afford ecm motor
@zacksintheshop
@zacksintheshop 5 жыл бұрын
You must size it properly for it to work.
@justdissin7340
@justdissin7340 5 жыл бұрын
@@zacksintheshop just size rpm & voltage?
@richh9904
@richh9904 3 жыл бұрын
Joe hack His still is more hi tech.
@rocker8692
@rocker8692 7 жыл бұрын
I like to party
@yepper1165
@yepper1165 3 жыл бұрын
I'm the stunt man. And I like to party.
@carlandrews6179
@carlandrews6179 5 жыл бұрын
Okay dude. The labels on the side of the unit are there for a reason. You just changed two things. You modified two. The UL label and the efficiency of the unit in one repair. UL label is no longer any good. If the house catches fire because of this system, you are the only one that will pay if sued. Manufacture is out of the picture because of your modification. You got great insurance? You should know ECM motors can deliver more air then PSC motors. If all things are equal, right unit for the house and duct work correct. The efficiency would be on track. Now it is lower and system failure is on track now. I work for a major company. It is our policy not to modify labels on a system of any brand of heating and air unit. Good luck with your modifications.
@zacksintheshop
@zacksintheshop 5 жыл бұрын
I got away with mine, I retired. I understand what you are saying. Does that apply to aftermarket ECMs as well? How far do you think that argument goes? This unit actually has the PSC stubs on the board. I realize it is a board used in multiple units. I did have insurance, yes. Liability is required here to be in business. Typically 1 - 2 million as a starting point.
@scotthsmith8635
@scotthsmith8635 5 жыл бұрын
Carl Andrews, although your points are somewhat valid, you are a bit extreme. I own an HVAC company and I appreciate your concerns however this man saved a 7-year-old unit from Death. There’s no way I’d put $1000 worth of motor into that machine. He did his customer a great service and thank God he had the knowledge and the ability to do so. He did everything correct and professionally. There’s no insurance play here
@HVACRat
@HVACRat 5 жыл бұрын
Field modifications do not "void" the UL Listed Mark as long as the modification is being used in it's intended manner. In this case, the tech has installed a UL Listed part (aftermarket PSC motor) and since neither the motor nor the equipment has been modified beyond it's intended use (manner) there is no liability outside of the UL Listed Mark. You are correct that an X-13 is more efficient in a perfect world, with perfect duct work but ultimately we are at the mercy of our customers. If they will not pay to upgrade the ductwork as needed a PSC is perfectly logical and acceptable modification to keep from needing to replace X-13 motors (or any ECM) due to high static. Not as efficient, true; but it will last much longer.
@rickl7024
@rickl7024 5 жыл бұрын
Don’t know if this applies but freightliner trucks have been doing this on the hvac blower motor on several models that were oem ecm controlled
@harrpp2220
@harrpp2220 Жыл бұрын
Smoke some weed & chill my boy
@toddolson573
@toddolson573 5 жыл бұрын
Pulling down because of gravity? What is gravity-really..? Newton couldn't even fully define it, as it's only theory. And fully nonsence. If one says this is nonsence, ask yourself, how is it that billions of gallons of rain stays floating above the earth. Not one drop should be up there if gravity were a real thing.
@tytig94
@tytig94 4 жыл бұрын
It has to do with atmospheric pressure. Different layers of atmosphere= different pressures. Standard atmospheric pressure is 29.9" of HG which differs at different atmospheres (stratosphere etc...). Also newton explained free fall of gravity is 9.8m/s squared. I only wanted some info on ECM to PSC motor but I'll debunk a flat earther while I'm at it. 😂😂😂
@Mike-ig2zq
@Mike-ig2zq 3 жыл бұрын
@@tytig94 Much appreciated.
@juliolopez9811
@juliolopez9811 5 жыл бұрын
👍
PSC Motor vs Constant Torque Motor vs Variable Speed Motor | Comparison Video
13:46
Fox Family Heating and Air Conditioning
Рет қаралды 95 М.
Replacing an X-13 ECM motor with a PSC (capacitor) motor.
25:29
Миллионер | 1 - серия
34:31
Million Show
Рет қаралды 2,4 МЛН
How do Cats Eat Watermelon? 🍉
00:21
One More
Рет қаралды 12 МЛН
ECM TO PSC BLOWER MOTOR CONVERSION
12:17
D2D NY Real World HVAC Simplified
Рет қаралды 6 М.
ECM to PSC Conversion/ Short Blog at The End
16:47
John Israel HVAC
Рет қаралды 42 М.
ECM TO PSC MOTOR CONVERSION Pt2
11:30
D2D NY Real World HVAC Simplified
Рет қаралды 1 М.
ECM Motor Troubleshooting
10:26
Enertech University
Рет қаралды 113 М.
TEF #156 | GE ECM 2.3 DG02 Teardown And Failure Investigation
53:04
That Electronics Fool
Рет қаралды 6 М.
Shop Fan out of old Furnace blowers
9:55
sixtyfiveford
Рет қаралды 283 М.
How to Swap ECM Motor with a PSC Motor? @qwikproduct
7:35
Taddy Digest
Рет қаралды 38 М.
Replace Your Outdoor ECM Motor with a PSC Motor in NO TIME!
16:55
Taddy Digest
Рет қаралды 13 М.