Brilliant tip I hope Andrew now knows how to deal with this issue in the future and keeps watching these great tips from your channel
@efixx3 жыл бұрын
Thanks 👍
@michaelbyrne71283 жыл бұрын
Love Gary’s subtle sarcasm
@efixx3 жыл бұрын
As do team eFIXX 😯
@slick0000 Жыл бұрын
Thank you for this video. Literally answered my question with regards to installing the transformer in the consumer unit. I don't want to see another housing on my wall to power a smart doorbell. Otherwise id fit it from my lighting circuit which would be a lot easier. Cheers
@darkdepth19913 жыл бұрын
Thank you Efixx for this update, the separation of voltages has certainly become more important with the smart technology. Showing a few practical tips is always very kind. 🤩🤩🤩
@jamesswinyard5303 жыл бұрын
I mount the transformer in a dedicated enclosure, and use 2core 0.75mm flex from the transformer to the doorbell. I crimp on a ring crimp at the doorbell end for ring doorbells - a nice installation.
@Chatterisdotbiz3 жыл бұрын
I use 0.75mm2 two core flex for the secondary side.
@dsesuk3 жыл бұрын
Regarding type-testing, Surge Protection Devices Ltd. say their SPD product can go into any CU because it's 'passive', i.e. not providing overcurrent or earth leakage protection. I wonder if bell transformers are largely considered in the same way?
@efixx3 жыл бұрын
Great comment - one to explore with the consumer unit manufacturers 👍
@tcpnetworks3 жыл бұрын
Install a door knocker. Brass ones are best. An alternative to that is a door bell that runs on POE. Run a data cable, use packets.
@oyleyhands13323 жыл бұрын
Well....Most electrical wholesaler still lists cable as T&E, twin & Earth or 2-core and earth....so I would not get too hung up on the description, the cable manufacturers are ahead of the cable suppliers with up to date cable description. Check out your favoured Doncaster Cables decription then look at say TLC or Expert Electrical, two well known suppliers.
@_______DR_______3 жыл бұрын
Although it should be obvious to anyone going in the consumer unit what the cable is, not sure I'd over-sleeve it with blue ;) I personally dislike solid core bell wire, and generally use the closest size stranded twin speaker wire. But I normally use an externally mounted transformer, and ensure adequate separation of voltage bands on new installations, unfortunately you never truly know whats going on behind the scenes in an old house though.
@efixx3 жыл бұрын
do you still oversleeve the speaker wire - or does it have a specified voltage rating?
@_______DR_______3 жыл бұрын
@@efixx The external transformers I fit have separate compartments for the LV and ELV terminations. I've not yet found myself needing to change one mounted inside a consumer unit, But if I were to need to I will admit applying sleeving is a good solution, Thankfully most of what I do is new work and I wire a lot of heating systems so I have quite a wide variety of sleeving colours and sizes 😂
@DoctorElectricYouTube2 жыл бұрын
I see bell wire or cat 5 cable inside consumer units loads, my preferred method is twin & Earth to a separate enclosure for the transformer and then bell wire to the unit. Lots to take in there, let's hope that Andrew manages to take it all in.
@kevinhancock4064 Жыл бұрын
I was thinking of doing it this way ..I have an enclosure for the transformer so could fit it on opp internal wall
@scouselive2 жыл бұрын
Have you had any issues with that transformer as its only rates at 8VA and most smart doorbells are asking for at least 10VA
@sidwainhouse3 жыл бұрын
FCU from a socket circuit near the DB, DIN rail enclosure for the transformer. Feeding it from a spur rather than it's own dedicated circuit saves a way and when the dreaded AFDDs do come in it saves a few quid. I also tend to wire using two core flex, the insulation has a better rating than bell wire and it's easier to fit the R clips without smashing your fingers with a hammer...
@DIMTips3 жыл бұрын
Excellent video guys. I ended up installing one in my cu. I used 1.0mm wire to help stop interference.
@TheChipmunk2008 Жыл бұрын
I know this is an old video, but if gary or gordon are watching... is sleeving actually insulation? I thought it was just identification. Heatshrink is different.
@thattoolguy94323 жыл бұрын
i tend to use 2 core flex .. but prefer to mount them externally just for the shear fact it takes up 2 ways that could be used in future
@efixx3 жыл бұрын
yes good point
@wired2thebrink Жыл бұрын
Could you just have a Wylex ESE2 enclosure close to the chime with a transformer inside running off a plug to socket or a switched fuse spur ? similar to what you said run it off the light circuit thus avoiding any difficult regs?
@jonathanbuzzard1376 Жыл бұрын
To make it easier to fit the sleeving you could use heatshrink, which when shrunk has the added advantage of not easily coming off. What I did is use some of that high temperature silicone fiberglass woven yarn sleeving. The stuff I used was allegedly rated for 1200V and pushes on much easier than normal sleeving.
@johnwaby43213 жыл бұрын
I sometimes wire it in flat twin double insulated flex about 0.5 mm
@paul756uk23 жыл бұрын
Good video but these transformers are a real throwback to the 60's. Things have moved on and 8 volts! What's that all about? Smart doorbells have different voltages so often these transformers are useless. I posted in a previous video of yours that I'm helping my son refurb his hall and he's put in wiring for a smart doorbell but as he doesn't know which one he wants we've fitted a socket in the understairs cupboard and taken the bell wire into there so a dedicated plug in psu can be plugged in.
@markrowland53933 жыл бұрын
You could use 240 volt rated two core flex.
@georgegeorgel7254 Жыл бұрын
I have a question.ive got a 24v video door bell transformer and when i tried to install it on the load side of the circuit breaker it keep tripping and when i connected to the in side no more trip and the neutral cable i connected to the neutral bar why it trips when its connected to the load side?
@GSMah3 жыл бұрын
Is is possible to use an enclosure to install the transformer outside of the consumer unit. That way only the mains wiring for the transformer are within the consumer unit
@efixx3 жыл бұрын
Yes that’s another option
@seandempsey93963 жыл бұрын
Excellent video thank you guys. I would just use twin and earth
@efixx3 жыл бұрын
Good call!
@seandempsey93963 жыл бұрын
@@efixx Gary just to let you know the CPD modules I got all six so thank you. And I recommend all your viewer's have a go at them.
@alexanderpuchkov4108 ай бұрын
I am wondering why the doorbell circuit is usually not protected. On line side the transformer is protected with a circuit breaker, but what is going to happen in case of short circuit on low voltage side? I mean, nobody places any overcurrent protection on low voltage side when connecting the doorbell, and I'm curious why.
@RichardHarvey19753 жыл бұрын
I hope Andrew is now technically satisfied and removed his moustache 😆🥇👍🏻
@kevinpickett72493 жыл бұрын
I give my customers a door knocker
@cj-rb8fz3 жыл бұрын
Is that a 13a arch fault device , never seen a breaker rated at 13a before
@efixx3 жыл бұрын
Yep - nice 👀
@AndrewCleversley2 жыл бұрын
Hi iv got a friedland doorbell with built in transformer its suddenly stopped working and the bell unit is making a lound buzzing noise im not sure what that could be
@ooslum3 жыл бұрын
Don't like the 1mm t&e, same wire different voltage? 2 core flat flex and some nicely printed label flags around it wouldn't add too much to a £200 smart bell install.
@zedman4423 жыл бұрын
Nice. Does solid core cable have problems with DC voltage?
@efixx3 жыл бұрын
Not at the low current required by a doorbell
@bryancarruthers11213 жыл бұрын
Different topic ,with an led ribbon of 5metres and the driver is sat 10metres away what cable should be used and size.Asking because some lighting designers say using cat 5 cable is ok,cheers
@efixx3 жыл бұрын
What voltage and watts per meter is the LED tape ?
@bryancarruthers11213 жыл бұрын
@@efixx 6watt per metre 12 volt
@oyleyhands13323 жыл бұрын
I have a question for you , as you have a training background, two questions actually. Scenario...a pump house in an industrial or comercial setting, inside, two diesel engines and two electrical three phase jockey pumps, all the associated piping for the sprinklers and of course a main electrical panel controlling everything. 1. Does the panel have to have local isolation adjacent the panel, or not ? 2. What qualifications would the 'fire pump engineer' have to have to work on any part of the system, including all the voltages present within the system, from sensor voltages to 415 AC ? and I dont just mean should have, I mean HAVE not SHOULD to remain with laws,regulations etc. -
@fanzalfernandes44603 жыл бұрын
Thanks it helped me
@AG-cg7lk2 жыл бұрын
Is it acceptable to add another DIN rail transformer (AC/DC) next to the AC/AC bell transformer to power a low voltage DC device that needs to be located near the bell power source? I'd like to install an AC relay and small wireless device near the consumer unit that gets triggered when the bell circuit is closed (for home automation purposes).
@efixx2 жыл бұрын
One of the great debates of our time. I’d put the transformer and relay in with your wireless stuff rather than the Consumer unit
@AG-cg7lk2 жыл бұрын
@@efixx thanks. Yes, it’s a tricky one as my gut instinct is to keep as much of the AC part of the setup in the consumer unit as possible, so that only the bell wire AC and DC need to come out to the relay etc. but that also puts DC in the consumer unit. Argh. If there’s no established convention, I might just throw in a meanwell 5v device I have in a spare slot and give it the ‘does it look like a bodge’ sense check.
@iandow99 Жыл бұрын
No power is going to my chime. Is there a fuse in the transformer that might need replaced?
@adriansharman24993 жыл бұрын
Isn't this an issue of band 2 inducing onto the band 1 cable? How about ferrite loop, and/or cross band 1 and band 2 at right angles where possible?
@earlyyearslearningisfun3 жыл бұрын
I love Gaz
@brianwood52203 жыл бұрын
Nice one guys 👍
@corkevans42173 жыл бұрын
How about 1mm T&E out from the CU to a local fused spur with a 5A quick-blow fuse fitted, and from that to the bell wire
@efixx3 жыл бұрын
good option
@johnflower86483 жыл бұрын
You could use spiroband wrapped round the bell wire.
@9plusinstalaciones3 жыл бұрын
3 Core 240mm warrabout dat?
@ChrisBrown-fd2xt3 жыл бұрын
I wpuld be more worried about induced voltages where band i and bamd 2 cables run in proximity
@barrieshepherd76943 жыл бұрын
At the currents, exposure lengths and (lack of) imbalance in a domestic situation induced voltages are insignificant.
@vievlogs5893 жыл бұрын
I hope Andrew has his answer now... 👍🦾
@wallbouncer96553 жыл бұрын
Andrew from Cambridge is no Artisan 🤣🤣🤣🤣
@sy0617343 жыл бұрын
Similar scenario is when a contactor is installed within consumer unit / distribution board and the unit is being replaced but the contactor is of a different brand
@jameshansing53963 жыл бұрын
WHo's the heavy breather @ 2 mins???
@efixx3 жыл бұрын
Me (Gaz) I have a medical issue (sorry)
@anthonybragg3 жыл бұрын
2 CORE 0.5 or 0.75 flex maybe?
@efixx3 жыл бұрын
🦾
@andysims49063 жыл бұрын
I don’t think it’s a good idea using T+E cable for a bell circuit. Reason being if it’s run under the floor it’s not obvious it’s for a bell circuit. What’s to say someone’s comes along and runs a mains cable next to it or share the same joists holes.. Incidentally when I was an apprentice in the late70s we never segregated bell wires from mains cables ,I don’t think many people did . Something we would never do now .
@ratsalive3 жыл бұрын
I assume that the higher rated insulation would prevent induced current interference. Would need a test to see though.
@JohnDundee-el2ro2 ай бұрын
Can you not just use cat 5 or 6 computer cable think it's up to 500 volts
@acespark13 жыл бұрын
Option 4 Fit a big brass door Knocker. No AFDD required
@efixx3 жыл бұрын
on a UVC door - someone could knock it off the hinges in a new build !
@johnbower10 ай бұрын
To my knowledge I don't think that would take a video
@paultipton7433 жыл бұрын
Could use a wireless battery door bell kit 😅
@efixx3 жыл бұрын
They don't so smart ones with big enough batteries yet !
@AndyK.13 жыл бұрын
They don’t make bell wire like they used to
@efixx3 жыл бұрын
The bell wire was pathetic. Thanks for commenting 👍
@Cleofizoid3 жыл бұрын
POE switch & smart doorbell?
@scottsparky13 жыл бұрын
2 core flex.
@efixx3 жыл бұрын
100% 🦾👍
@besafelondonelectrical91983 жыл бұрын
I just ask have you a wife? If they answer yes I just say “trust me they’ll let you know when someone’s at the door”
@AndyK.13 жыл бұрын
I thought there was a regulation that the transformer had to be near CU