Electrical room tour at my high school

  Рет қаралды 6,586

NIC’S - SYSTEMS & ELECTRIC

NIC’S - SYSTEMS & ELECTRIC

Күн бұрын

Пікірлер: 63
@topher8634
@topher8634 Жыл бұрын
If that transformer secondary is carrying 75 amps continuously, it is overloaded. A 30 kVA TX Secondary @ 208 is 83.4 amps [30,000 ÷ 208 ÷ 1.73] You don't want to exceed more than 80% (66 amps) of the full load capacity continuously. That is why you're smelling the hot electrical odor and having the overheating issue. The insulation on the transformers windings is breaking down. They should consider either shedding some of the load if possible or installing a larger transformer if the main switchgear can handle it.
@nics-systems-electric
@nics-systems-electric Жыл бұрын
Exactly that's what I've tried to say the switchgear can definitely handle it as there was a larger transformer that was there temporarily for construction power which was larger
@topher8634
@topher8634 Жыл бұрын
@@nics-systems-electric they might listen to you when the school burns down. Between that and the Christmas decorations it looks like they're trying to torch it!
@2901er
@2901er 2 жыл бұрын
Looks nice
@agreniers
@agreniers 2 жыл бұрын
This is the sickest electrical room ever! btw how in the world did you gain their trust? It looks like you can do all you want, how did it all start? I love your videos btw
@nics-systems-electric
@nics-systems-electric 2 жыл бұрын
I started working with them four years ago when I got the chance to go to one of the schools during fire alarm testing for the summer and then just got to know all the electricians
@noxious_nights
@noxious_nights 2 жыл бұрын
among us memes aside this is actually really cool
@franklinjames7030
@franklinjames7030 2 жыл бұрын
Holy crap! Who did the cable management for those ethernet cables? That is a nightmare! I have seen WAY worse though.
@nics-systems-electric
@nics-systems-electric 2 жыл бұрын
Yeah it’s terrible The IT guys went through and redid The biggest data room and really cleaned it up a lot this one needs it to
@SytenixRBX
@SytenixRBX 2 жыл бұрын
Cool
@Roxxofoxxo
@Roxxofoxxo 2 жыл бұрын
Thats an amazinf and interesting setup! Awesome vid!
@windows74001
@windows74001 2 жыл бұрын
That's awesome! Reminds me of sneaking into electrical rooms back in my school days; unfortunately I wasn't an electrician so I didn't get to deal with any of the equipment haha On your meter that W/VAR/PF menu is showing the school's real power consumption, reactive power consumption, and power factor (if you care about math things, you can make a right triangle with the two shorter sides representing your W and VAR, the cosine of the angle between the W and the hypotenuse of the triangle [your VA] is the power factor). The VA/Hz menu shows the apparent power (if you do the "pythagorean theorem" with reactive power and real power), and the grid frequency. Then you got energy meters below that. Wanna keep that VAR low because that makes the VA larger, and industrial customers have to pay by the VA rather than the watt. (Residential customers pay by the watt only, at least in Saskatchewan)
@WhiteBloggerBlackSpecs
@WhiteBloggerBlackSpecs 2 жыл бұрын
Sus 🙃
@sebastianasebastian373
@sebastianasebastian373 2 жыл бұрын
Nice
@jeffmoss26
@jeffmoss26 2 жыл бұрын
Impressive
@SillyRock4
@SillyRock4 2 жыл бұрын
Niccee
@milesra22
@milesra22 2 жыл бұрын
Your High School is much nicer then my high school in Massachusetts 😂
@nics-systems-electric
@nics-systems-electric 2 жыл бұрын
Yeah it’s pretty new give it 50-60 years it might not seem as nice anymore lol
@danielelise7348
@danielelise7348 Жыл бұрын
The TX with the heating problem,shouldn't be that hot,it may have some issues that need addressing🤔
@nics-systems-electric
@nics-systems-electric Жыл бұрын
I’d say so
@IanGSully
@IanGSully Жыл бұрын
Will the generator run the elevators in this building as well?
@nics-systems-electric
@nics-systems-electric Жыл бұрын
No not this school
@jaedenspider877
@jaedenspider877 Жыл бұрын
Video of the air conditioning???
@nics-systems-electric
@nics-systems-electric Жыл бұрын
I'm not knowledgable enough on the heating and cooling systems in this building
@Peter_Yachymczyk
@Peter_Yachymczyk 2 жыл бұрын
You're in Canada? as I'm pretty sure 347V is a Canadian thing only. It's 277VAC in the USA (NEC) and Canada (CEC) have some of the same stuff but also some very different stuff as well. For instance the 347 vs 277V. Those transformers are very loud never been allowed in a school electrical room or elevator machine room both of which I was curious about in my high school years. I graduated in 2002 at 17 so things were different in both rooms. They did allow me to work on their school vehicles though the ones that were used as student transport (small private school). Do you have any interest in cars? Also in residential settings the meter base is not allowed inside the house anymore even with the newer digital meters as they want it to be in sight for in the house is an easy target for tampering and theft of service. @6:07 "ASHP1" might be the HVAC as it usually means air source heat pump AKA an AC that can run in reverse cycle to heat instead of cool @8:31 what are those red dials for to the left of the breakers? Sorry I should really watch the whole video before I comment LoL!
@nics-systems-electric
@nics-systems-electric 2 жыл бұрын
Yes I am in Canada and 347/600 V is I think only Canadian or mostly Canadian And yes the ASHP1 is an air source heat pump the red dials are to adjust the trip curve
@windows74001
@windows74001 2 жыл бұрын
I think some places in Canada will give you 480V l-l as an industrial service; I've seen some 480V but most of the traditional stuff is 600V
@nathanbirnofficial
@nathanbirnofficial 2 жыл бұрын
Did I see some extra fluorescent lights in the room too?
@nics-systems-electric
@nics-systems-electric 2 жыл бұрын
Those were some dead LED fixtures
@nathanbirnofficial
@nathanbirnofficial 2 жыл бұрын
@@nics-systems-electric even better It’s good to have spares around
@nics-systems-electric
@nics-systems-electric 2 жыл бұрын
@@nathanbirnofficial we’re running out of spares These led are supposed to last 20 years but are going after four years we’ve had lots of problems with LED at schools i’m starting to think fluorescent was just as good
@cussmustard4748
@cussmustard4748 2 жыл бұрын
I did not see any roof top equipment on that building. Does that school use a central chiller system for the hvac? It would seem overkill for up north. (Idk where that is but it looks northern.)
@nics-systems-electric
@nics-systems-electric 2 жыл бұрын
@@cussmustard4748 there are three air source heat pump’s on the roof but they are hidden sort of that provide heating and cooling
@Random_Emergency_Light
@Random_Emergency_Light 2 жыл бұрын
Can you make a video of testing the geneator?
@nics-systems-electric
@nics-systems-electric 2 жыл бұрын
I have one
@ElPasoTexasRailfan639
@ElPasoTexasRailfan639 2 жыл бұрын
Once my high school i graduated system wen't into trouble because a power outage cused the system to go into trouble so my classmates and i were so scared im the one that freaks out with everything LOL and nice little tour what system do thay have
@nics-systems-electric
@nics-systems-electric 2 жыл бұрын
Notifier I have a video on testing it
@ElPasoTexasRailfan639
@ElPasoTexasRailfan639 2 жыл бұрын
PICKLE I LOVE UR VIDEOS IT'S SO COOL WHY U HAVE TO COVER THE NAME OF THE SCHOOLWS IS I T BECAUSE OF PRIVACY PERMOSIES
@nics-systems-electric
@nics-systems-electric 2 жыл бұрын
@@ElPasoTexasRailfan639 Yes it’s for my privacy
@leafmk
@leafmk Жыл бұрын
i already know where your school is
@nics-systems-electric
@nics-systems-electric Жыл бұрын
Yes it is possible to fine it but I try to keep my location private
@leafmk
@leafmk Жыл бұрын
@@nics-systems-electric oh ok
@SassafrasSapling
@SassafrasSapling 5 ай бұрын
What will happen if you bypass the transformer that feeds the emergency lighting panel?
@nics-systems-electric
@nics-systems-electric 5 ай бұрын
That's not possible the feed comes from the transfer switch at 600 V in into a 600 V panel and then feeds to a transformer then into a 120/208 panel
@SassafrasSapling
@SassafrasSapling 5 ай бұрын
@@nics-systems-electric I’m taking about what happens if you feed the 120/280 lighting panel with 347/600 volts
@nics-systems-electric
@nics-systems-electric 5 ай бұрын
@@SassafrasSapling that's not something that's possible but if you were to hypothetically delete the transformer, you would kill likely almost every piece of equipment on the circuit. Some fluorescent ballast might be fine as they are dual voltage rated.
@SassafrasSapling
@SassafrasSapling 5 ай бұрын
@@nics-systems-electric So any 120 volt emergency light that runs off of that panel will fry up on 347 volts as it’s too much voltage for them.
@nics-systems-electric
@nics-systems-electric 5 ай бұрын
@@SassafrasSaplingmost are fluorescent, so they might be dual voltage rated the only LED corridor/stairwell emergency fixtures are in the addition which may also be dual voltage rated I'm not sure.
@TheJakeman789
@TheJakeman789 2 жыл бұрын
i take it the generator also powers the fire alarm?
@nics-systems-electric
@nics-systems-electric 2 жыл бұрын
8:47
@JessieMHadaller
@JessieMHadaller 2 жыл бұрын
Y’all’s server racks are messy. Maybe IT should organize it lol
@noxious_nights
@noxious_nights 2 жыл бұрын
How do you even get permission to do this type of thing?
@nics-systems-electric
@nics-systems-electric 2 жыл бұрын
I don’t really ask permission any more as I’ve been working in my school district for over four years now so I’m trusted pretty well
@tbiwog8336
@tbiwog8336 2 жыл бұрын
@@nics-systems-electric Soooo like you have keys to the school and can just kinda come in? Also do they know that you film?
@nics-systems-electric
@nics-systems-electric 2 жыл бұрын
@@tbiwog8336 Well not exactly no one is allowed in the schools whatever they want whether they have physical access or not and yes pretty much all the electricians know I make videos and some of the other trades and some other staff
@thetwinstakeoverYT
@thetwinstakeoverYT 2 жыл бұрын
Hiii
school maintenance electrical work
27:22
NIC’S - SYSTEMS & ELECTRIC
Рет қаралды 6 М.
Elevators at my high school machine room and elevator tour
13:31
NIC’S - SYSTEMS & ELECTRIC
Рет қаралды 10 М.
Ik Heb Aardbeien Gemaakt Van Kip🍓🐔😋
00:41
Cool Tool SHORTS Netherlands
Рет қаралды 9 МЛН
Before VS during the CONCERT 🔥 "Aliby" | Andra Gogan
00:13
Andra Gogan
Рет қаралды 8 МЛН
❌Разве такое возможно? #story
01:00
Кэри Найс
Рет қаралды 2,6 МЛН
Electrical Room Inspection
17:24
CCPIA
Рет қаралды 344
fire drill #1 at my high school
19:25
NIC’S - SYSTEMS & ELECTRIC
Рет қаралды 6 М.
My House Lost Power Again! Generator has More Problems During Power Outage.
21:43
NIC’S - SYSTEMS & ELECTRIC
Рет қаралды 18 М.
Take a Virtual Tour of the High School Campus in Middleton, FL
10:22
The Villages Florida
Рет қаралды 31 М.
Fault Finding Electrical Circuits - Electrician Life
24:57
Artisan Electrics
Рет қаралды 381 М.
Inside a smart meter, and the REAL problem with them.
16:45
bigclivedotcom
Рет қаралды 1,5 МЛН
Ik Heb Aardbeien Gemaakt Van Kip🍓🐔😋
00:41
Cool Tool SHORTS Netherlands
Рет қаралды 9 МЛН