Generator lockout due to multiple alarms without fixing now in this v'log we are going to talk about it how we make it correct trough program and simple explanation.

Пікірлер: 243
@inocenelson1943
@inocenelson1943 2 жыл бұрын
I find your presentation very constructive and helpfull👍
@mohameddeik9556
@mohameddeik9556 3 жыл бұрын
thank you eng for your explaining the best way.. please make us video how to do schedule perventive maintenance for generators in order to protect them
@benzblogsVlogs
@benzblogsVlogs 3 жыл бұрын
Ok sir copy
@benzblogsVlogs
@benzblogsVlogs 2 жыл бұрын
Preventive maintainance should be first 250 running hours and thin 500 for prome generator id standby it should be 1000-1500running hrs
@kookiddi3662
@kookiddi3662 Жыл бұрын
Thanks for your valuable information. The video is really very helpful.
@orimtonoi154
@orimtonoi154 6 ай бұрын
thank you very much .I'm watching from Papua new Guinea.
@benzblogsVlogs
@benzblogsVlogs 6 ай бұрын
welcome
@larzvlogag5027
@larzvlogag5027 3 жыл бұрын
Very interesting, i learned more from this clip! Thanks for sharing master.. Replay ko uli ito sa ibang araw para makabisado ko..
@benzblogsVlogs
@benzblogsVlogs 3 жыл бұрын
Bless you for having time with
@arifzafar9026
@arifzafar9026 8 ай бұрын
Thanks buddy for sharing such good knowledge for generator troubleshooting but you are congratulations these things can't seen due shadow..
@arifzafar9026
@arifzafar9026 8 ай бұрын
Dear may I know you where are you working?
@benzblogsVlogs
@benzblogsVlogs 8 ай бұрын
Im working in dubai how about you?
@arifzafar9026
@arifzafar9026 8 ай бұрын
@@benzblogsVlogs I'm good working in Dubai.. right now I'm looking your video low and under frequency but I can't see how to congratulation..
@benzblogsVlogs
@benzblogsVlogs 8 ай бұрын
@@arifzafar9026 ok thank you
@benzblogsVlogs
@benzblogsVlogs 8 ай бұрын
If you have under frequency this ither voltage is love just adjust in avr
@bismilkhan3149
@bismilkhan3149 3 жыл бұрын
Super my friend I leaned something every day from you.. I chat with you last week in Facebook..
@benzblogsVlogs
@benzblogsVlogs 3 жыл бұрын
Thabk bro bless and keep safe okay
@jaykesapalaran5434
@jaykesapalaran5434 2 жыл бұрын
Salamat sa PAG share ng knowledge mo Po sir.
@benzblogsVlogs
@benzblogsVlogs 2 жыл бұрын
Bless u sir
@nonoytv1740
@nonoytv1740 3 жыл бұрын
thanks for idea sir, baka pwd ka request sir video for correct PMS for genrators..thanks in advance.
@benzblogsVlogs
@benzblogsVlogs 3 жыл бұрын
No worries sir salamat din keep safe
@jrabot2035
@jrabot2035 3 жыл бұрын
Salamat sir very informative tutorial videos
@benzblogsVlogs
@benzblogsVlogs 3 жыл бұрын
Bless you sir
@geoffreyjahooksiraba7704
@geoffreyjahooksiraba7704 Жыл бұрын
Thanks, very informative. I also have a problem with a 200kva Cummins, where I keep getting a low coolant level shutdown alarm. So far I replaced the sensor but the alarm comes on after about 2 hours running on full load?
@benzblogsVlogs
@benzblogsVlogs Жыл бұрын
Did you install low coolant level sensor or sw only?
@benzblogsVlogs
@benzblogsVlogs Жыл бұрын
Make it sure so we can solve the problem
@armbangs
@armbangs 3 жыл бұрын
Appreciate your video, can you make also video about programming a harsen controller..
@rhodlomboydubailife7871
@rhodlomboydubailife7871 3 жыл бұрын
here my support benz vlog tamsak done.. keep it up..
@benzblogsVlogs
@benzblogsVlogs 3 жыл бұрын
Big thanks
@htcofficial8788
@htcofficial8788 3 жыл бұрын
thank you for the videos godbless
@benzblogsVlogs
@benzblogsVlogs 3 жыл бұрын
Salamat din sayo sir
@lisaloprestodehart1606
@lisaloprestodehart1606 2 жыл бұрын
Any clue on 2013 kohler 20resa rotor lockout. Cranked ran a min then tried again it click then throws code. It's not battery or wires. Cant get anyone up on the mountain.
@benzblogsVlogs
@benzblogsVlogs 2 жыл бұрын
In this case repalce oil sensore and sw may this the problem thanks
@lisaloprestodehart1606
@lisaloprestodehart1606 2 жыл бұрын
@@benzblogsVlogs will those make the rotor not turn or do they not turn freely when off? I cant find anything on rotor lockout fault only says check battery lol
@benzblogsVlogs
@benzblogsVlogs 2 жыл бұрын
If battery problem use multi meter to check thank
@lisaloprestodehart1606
@lisaloprestodehart1606 2 жыл бұрын
@@benzblogsVlogs no I put new battery just incase. The fault is rotor lockout it will click only not start
@benzblogsVlogs
@benzblogsVlogs 2 жыл бұрын
Show me the alrm posible what kva your generator
@thunderman7505
@thunderman7505 Жыл бұрын
Mr Benzblog, I have a 6120 Mii with brand new Perkins Diesel engine and all the sudden it shows Emergency lock out. So, I have changed all the Controller but still it is a same and Also, the oil and fuel sensor has been replaced and nothing has changed. So, I'm wondering what this could be.? Thank you
@benzblogsVlogs
@benzblogsVlogs Жыл бұрын
If you look the wiring of emegency stop there are two emegency stop make sure the connection is good ang the push button have a contact sw inside of it take a look if still good condation ang measure it from the module dc boltage if there is if not means ither lose connection or faulty push button contact ither one if it
@benzblogsVlogs
@benzblogsVlogs Жыл бұрын
kzbin.info/www/bejne/aZ64p2Opjt1qfpo
@shakadelpeche261
@shakadelpeche261 3 жыл бұрын
Very detailed video, thanks for sharing. I'm having very similar issues, generator not cranking, oil pressure alarm, engine not reaching require speed and generator lock out. This is on a FG Wilson P16.5-6S using a Deep Sea 7410 MK11 controller. Do you have any similar videos using the Deep Sea 7410 MK11 or can you advise on fixing the oil pressure issue.
@benzblogsVlogs
@benzblogsVlogs 3 жыл бұрын
Oi pressure most common alrm you need to double check your connection and your sensor and level of your oil ither faulty already
@shakadelpeche261
@shakadelpeche261 3 жыл бұрын
@@benzblogsVlogs Thanks for your response. I’ve made the necessary checks and everything seem OK all connection are intact, Filter are OK, oil level OK. It’s a new generator, all attempts to crank it over failed. Keep getting a LOW OIL PRESSURE ALARM.
@benzblogsVlogs
@benzblogsVlogs 3 жыл бұрын
@@shakadelpeche261 ok if still same problem thin replace the oil sensor and check the oil viscusity is in the good condation my be need to change oil
@T.R.U.M.P.
@T.R.U.M.P. 4 ай бұрын
Dud you ever figure your issues out? Im having the exact same issue as you with basically brand-new generator ​@@shakadelpeche261
@obasekipaul7529
@obasekipaul7529 Жыл бұрын
This is great thanks, please what is the fault when the generator running for a short time and then shout down on generator looked out?.
@benzblogsVlogs
@benzblogsVlogs Жыл бұрын
Sir double check the alarms thin their your can find what really in the problem just scroll the screen to alarms use the push botton to scroll
@aklilA
@aklilA 2 жыл бұрын
Thanks for your helpful videos. can you please tell me the reason why air-cooled engine is overheating after the overhaul? All timing and valve adjustment are correct and also the cooling fan is well working, there is good oil circulation. Can it have other issues to see?
@benzblogsVlogs
@benzblogsVlogs 2 жыл бұрын
Air cold engine is higher temp than the water cooled engine just make sire the correct passage of the and the oil and the air t avoid overheat sometime overfueling leads to this problem too
@generemaxfernandez5878
@generemaxfernandez5878 2 жыл бұрын
Ty for your sharing sir merry xmas
@benzblogsVlogs
@benzblogsVlogs 2 жыл бұрын
Happy new year too
@elporky6420
@elporky6420 Жыл бұрын
I have a natural gas generator with an 8610 MK2. I press the button to start and it doesn't crank at all, but the countdown timer counts down as if it was cranking. Fuel on, then cranking 10,9, etc. Any idea what it might be? Thank you in advance
@benzblogsVlogs
@benzblogsVlogs Жыл бұрын
Check battery supply fuse from suply from relay and check starter itself if working of faulty
@elporky6420
@elporky6420 Жыл бұрын
I checked fuses and relays and they look good. Starter is also good. When I disconnect and reconnect battery. I only get one crank first attempt. 2nd attempt, only countown timer no crank.
@benzblogsVlogs
@benzblogsVlogs Жыл бұрын
@@elporky6420 check how much drop down voltage duting crank coz this i think battery is the issue
@elporky6420
@elporky6420 Жыл бұрын
They are brand new batteries. Thank you for your time. I appreciate your replying.
@benzblogsVlogs
@benzblogsVlogs Жыл бұрын
@@elporky6420 only one thing you can check is the voltage drop and current drwn during crank time
@Mhasso-gs7lr
@Mhasso-gs7lr Жыл бұрын
Hello ! Thanks for a great video. I have a generator that starts in a few seconds then shuts down due a low oil pressure. What is the issue in your opinion and what parameter should I adjust ? Where can I download the software from ? Thanks i hope you reply.
@benzblogsVlogs
@benzblogsVlogs Жыл бұрын
My openion is check whin this engine maintinance and if no do the meantainance change oil filter fuel filter this. After that if still same remove the sensor oil and double check the wiring okay
@Mhasso-gs7lr
@Mhasso-gs7lr Жыл бұрын
@@benzblogsVlogs I’m getting around 2,5 bar of oil pressure and recently changed the oil filter as well . Thanks again
@benzblogsVlogs
@benzblogsVlogs Жыл бұрын
Replace oil sensor
@Mhasso-gs7lr
@Mhasso-gs7lr Жыл бұрын
@@benzblogsVlogs okay ! Thank you 🙏
@Mhasso-gs7lr
@Mhasso-gs7lr Жыл бұрын
@@benzblogsVlogs The display shows that there is oil pressure and it should shut down at 1.3 bar and I have 2.5 bar . But it still shuts down due generator locked out (oil pressure low )
@sharikhussain5817
@sharikhussain5817 3 жыл бұрын
Very Nice information 👌
@benzblogsVlogs
@benzblogsVlogs 3 жыл бұрын
Thank bro
@SeigfredWall
@SeigfredWall 3 жыл бұрын
Nice content... Master..
@samuelkahiga-sx4wd
@samuelkahiga-sx4wd 3 ай бұрын
Sir how do you go about a 7320 deep sea that shows engine failed to stop while already in rest mode or not learning.,kindly explain this
@benzblogsVlogs
@benzblogsVlogs 3 ай бұрын
Due to you oil sensor or sw
@samuelkahiga-sx4wd
@samuelkahiga-sx4wd 3 ай бұрын
@@benzblogsVlogs thank you for the reply....have tried to replace it several times but the issue persists...is there in any way you can adjust it in terms of setting to make it work ...
@520-b2v
@520-b2v 3 жыл бұрын
Nice jie goodjob😊
@jaykesapalaran5434
@jaykesapalaran5434 2 жыл бұрын
Sir sana magka roon ka po ng trade school sa pilipinas para ma I share mo lahat ng experience mo bilang maging Isang MAGALING na technician ng generator.
@benzblogsVlogs
@benzblogsVlogs 2 жыл бұрын
Inshallah sir salamat
@AsgarKhan-uk1kp
@AsgarKhan-uk1kp 2 жыл бұрын
Nice information sir
@benzblogsVlogs
@benzblogsVlogs 2 жыл бұрын
💗
@SeigfredWall
@SeigfredWall 3 жыл бұрын
Halimbawa master... Kung wla kang laptop pwde parin ba i reset yan sa module..or control panel?
@benzblogsVlogs
@benzblogsVlogs 3 жыл бұрын
Yes sir pwedi g pwedi my designated na reset botton sir sa module pwedi morin switch off para totally reset unless kongmay alarm kailangan mo talagang resolve ang problima bago mawala ang alarm
@jaykesapalaran5434
@jaykesapalaran5434 2 жыл бұрын
Sir may nagawa ka na ba na libro para sa generator??? Mga basic troubleshooting at mga does and don't na pag PM ng generator???
@benzblogsVlogs
@benzblogsVlogs 2 жыл бұрын
I think wala pa sir sa mga company lang rule nila sa pg ppm ng mga generators
@jaykesapalaran5434
@jaykesapalaran5434 2 жыл бұрын
By the way sir may trade school ba sa pilipinas para sa generator technician??? If Meron mag kano Po pag mag enroll??
@inocenelson1943
@inocenelson1943 2 жыл бұрын
Sir,I watched how you flush and reprogrammed a deepsea controller that showed blank on the deepsea controller.please advice me how I can purchase this deepsea controller flush kit
@benzblogsVlogs
@benzblogsVlogs 2 жыл бұрын
Bro just follow what i said go to deepsa config and find firmware update no need flash same update the lataste version and follow what instruction give to you by the configurate and done ok
@jaycabalu911
@jaycabalu911 2 жыл бұрын
Sir what is the possible fault alarm of this? DSE6020 indicate crank fault. Starting motor no power.
@benzblogsVlogs
@benzblogsVlogs 2 жыл бұрын
Ganito gawin mo bypass mo mona para malamn mong ok pa ang starter moter mo baka mga relay lang ang defective or walang supply
@generemaxfernandez5878
@generemaxfernandez5878 2 жыл бұрын
Ty sir for ur sharing your talent god bless u
@benzblogsVlogs
@benzblogsVlogs 2 жыл бұрын
Bless u too sir
@AuduEmmanuel1
@AuduEmmanuel1 2 жыл бұрын
My P20 julaili Bros Genset is running on Auto but always failing with generator locked out alarm, I don't have the software for the program as explained on this video, what do I do please.
@benzblogsVlogs
@benzblogsVlogs 2 жыл бұрын
Look the alarm list so we can identify easily what is the real problem why
@reldhenielniadas5669
@reldhenielniadas5669 3 жыл бұрын
Good eve. Sir' Can i ask regarding DSE 8610 memory corruption alarm display how i can recover the normal display of controller?
@hasnain3963
@hasnain3963 2 жыл бұрын
Problem solved thanks.
@benzblogsVlogs
@benzblogsVlogs 2 жыл бұрын
Welcome dear
@weetv69
@weetv69 3 жыл бұрын
Sir, flushing and excite of generator sir to check if alternator or exciter is in good condition sir. Next in line po sir. Thanks. Medyo kinakabahan lang dahil hnd pa nakasubok at 1000 kVA yung generator.
@benzblogsVlogs
@benzblogsVlogs 3 жыл бұрын
No issue sir same small to big
@benzblogsVlogs
@benzblogsVlogs 3 жыл бұрын
Juat make sure that all on correct and safety ok pag nag flashing tayo always used 12vdc volt and remove ac sensing to the avr
@dennisducalang3112
@dennisducalang3112 3 жыл бұрын
@@benzblogsVlogs sir San po kita pwede makontak? Salamat, sa, mga, blogs mo sir malaking tulong Lalo na, sa mga ofw na electricians..
@benzblogsVlogs
@benzblogsVlogs 3 жыл бұрын
@@dennisducalang3112 sir dito po
@benzblogsVlogs
@benzblogsVlogs 3 жыл бұрын
@@dennisducalang3112 facebook.com/groups/1581429425388674/
@eggycoolteknik5897
@eggycoolteknik5897 Жыл бұрын
Good job broo
@benzblogsVlogs
@benzblogsVlogs Жыл бұрын
Thabk u
@richieuntaran8530
@richieuntaran8530 3 жыл бұрын
Sir can you teach me how to wiring from speed controller governor esd5500 going dse 5110. Thanks and good day sir
@benzblogsVlogs
@benzblogsVlogs 3 жыл бұрын
Sir juat til me what speed controller and for single dz or synch
@richieuntaran8530
@richieuntaran8530 3 жыл бұрын
@@benzblogsVlogs not for syncronizing sir, just only like cummins or volvo generator, they have actuator, mpu and battery in speed controller
@vicgonzales1326
@vicgonzales1326 5 ай бұрын
boss lodi any idea bk mtulungan mko dko kc mkuha ung sofware pra sa 7310mk2 thnx in advance
@benzblogsVlogs
@benzblogsVlogs 5 ай бұрын
Sir free lng yan sir ponta klng sa website nila sign up ka its full free
@carlosochoa4058
@carlosochoa4058 3 жыл бұрын
Hi, we have a problem with a Perkins plant. Sometimes when it starts up with low oil pressure, other times it starts up but makes a noise when it starts like a gurgling, acpm filter pressure sensor was changed, the oil in the fuel filter was changed and the fault continues What can be
@benzblogsVlogs
@benzblogsVlogs 3 жыл бұрын
Sir bith you change the sw snd sensor anong kva po sif sorry laye reply
@benzblogsVlogs
@benzblogsVlogs 3 жыл бұрын
If electronic enegine you need EST to troubleshoot such problem but if conventional just sure the you replace both sw and sensor and make sure po do the propper change oil and config.
@carlosochoa4058
@carlosochoa4058 3 жыл бұрын
@@benzblogsVlogs everything was changed and it was no use
@maryamabbaslawal1979
@maryamabbaslawal1979 2 жыл бұрын
Hello sir. i have the DSE6120 MODULE AND THE ALARM SOUND KEEPS ON AND THE GEN KEEPS SAYING "FAILED TO STOP" AND IT WONT SAID ALSO IT DOES NOT CRANKING ANYMORE. PLEASE CAN YOU HELP ME. THANK YOU
@benzblogsVlogs
@benzblogsVlogs 2 жыл бұрын
Rwplace your battery
@powerengineering1913
@powerengineering1913 2 жыл бұрын
Hello sir. What would be the cause of generator locked out on deepsea 6120mkiii
@benzblogsVlogs
@benzblogsVlogs 2 жыл бұрын
Sir if you mean lock out there alarm should be ither emegency stop , high temp its depend on juat take a look on the alrms list you can see there why its lock because duting alarm it is not rectify as a gevin time now module outomaticaly lock out to avoid any failure in your engine
@benzblogsVlogs
@benzblogsVlogs 2 жыл бұрын
Send me the alarm so i can guide you to the next thing to do
@jemiesanpedro4481
@jemiesanpedro4481 3 жыл бұрын
God bless po.. Sau boss
@benzblogsVlogs
@benzblogsVlogs 3 жыл бұрын
Salamat sir
@ssemassem8838
@ssemassem8838 Жыл бұрын
What dose ECU amber alram mean on deep sea
@benzblogsVlogs
@benzblogsVlogs Жыл бұрын
Alarm amber meaning not mijor alrm mostly causing wayer in fuel or air mixture in fuel filter
@leonardygrobay1153
@leonardygrobay1153 2 жыл бұрын
Sir i had a trouble with our company smart gen 25kva generator.. the touble was pressure low alarm.. i watch on youtube..try to solve it..I try to replaced the oil pressure sensor.. but its still there the problem.. its same apear on panel board..LOW PRESSURE ALARM.. can u help me.. what should I do..tnx in advance
@benzblogsVlogs
@benzblogsVlogs 2 жыл бұрын
If not remove in reset thin check the wiring and thin if same replace it check also the oil viscosity and level
@JasperFSaludes08
@JasperFSaludes08 2 жыл бұрын
Boss my tanong po ako about sa generator nmin volvo dse7310 mkii, baka my idea po kau, Problem Ayaw po magstart,ayaw umandar ang starter as in,pro pag dinadirect nmin gumagana nman starter good condition sya, ano po kaya ppsible problem bkit parang di po nagbibigay ng power papubta sa starter, my connect po ba ang fuel solinoid sa pagstart or ano po ung posible na solinoid na koniktado before start.
@benzblogsVlogs
@benzblogsVlogs 2 жыл бұрын
Sir nka ecm yan if my ecm check mo yong main positive supply my fuse yan sa wire check mo if busted
@JasperFSaludes08
@JasperFSaludes08 2 жыл бұрын
Yes sir nka ecm, ung fuse po ba is yung dalawa sa my ecm nia,, if yun po ai ok nman
@benzblogsVlogs
@benzblogsVlogs 2 жыл бұрын
@@JasperFSaludes08 complito ng supply
@benzblogsVlogs
@benzblogsVlogs 2 жыл бұрын
Ecm kc ng bibigay commang ng start sa starter kaya kong walang fuel on di yan magstart
@mohammedal-qadi104
@mohammedal-qadi104 9 ай бұрын
Sir I do have emergency stop alarm though the emergency stop push button is open what is the reason??
@benzblogsVlogs
@benzblogsVlogs 9 ай бұрын
Check ither contact is open or no positive supply going back tobyour module check using mukti mter
@williamvillaruel2066
@williamvillaruel2066 2 жыл бұрын
Hello sir Ask klng paano e troubleshot generator automatic start but goes off once din e switch ko ulit generator switch button para mag auto cya ulit
@benzblogsVlogs
@benzblogsVlogs 2 жыл бұрын
Ano yan maam naka AMF or nka ATS
@agent70vids3
@agent70vids3 3 жыл бұрын
Tumatakbo ung cummins KTA38 with DSE 8610 MKII, bigla nalang nagshutdown, may alarm na Generator Locked out. Ayaw mareset, sa alarm ang nakalagay, emergency stop. Ok naman contact ng emergency stop. Ano possible reasons?
@benzblogsVlogs
@benzblogsVlogs 3 жыл бұрын
Pwedi dalawang source ng emergency stop sir isa main ang isa ay connected sa digital input at naka config ng emergency stop din pero magkaiba ng suply ngayun first gawin mo double check mo lang yjng pinangalingan ng supply my fuse or breaker yan baka busted or trip lang sir
@benzblogsVlogs
@benzblogsVlogs 3 жыл бұрын
Kc kong may supply dapat wala na yung alarm sir ganito din gawin mo sir pilonta sa sa module tingnan mo ang alarms list makikta mo doon lahat ng alrm baka di lang emergency stop pwedi vediohan mo para makita natin paano nag shudown
@benzblogsVlogs
@benzblogsVlogs 3 жыл бұрын
Minsan pag lockout ang module ibigsabihin yung alarm ay dipa natangal kaya naglockout sya mawawa lng yan lockout if na rectify na yung alarm
@agent70vids3
@agent70vids3 3 жыл бұрын
@@benzblogsVlogs emergency stop nakalagay sa event log, pero ok naman emergency stop. Yung inoff ko power tapos ON ko ulit, ang lumabas sa display "Memory Corruption refer to Manual" yung sinubukan redownload ng program ayaw na, sira na daw yung deepsea controller. Tama po ba findings? Ano kaya posibilidan nun bakit nag Memory corruption sya at hindi na po ba maayos yun?
@benzblogsVlogs
@benzblogsVlogs 3 жыл бұрын
Ok sir nx blog ko gagawin ko yan pano e recover
@AGeorge6170
@AGeorge6170 5 ай бұрын
Why maintenence alam 1 and lock out signs on in my Genset.
@benzblogsVlogs
@benzblogsVlogs 5 ай бұрын
Meaning need to do maintainance and thin reaet it after the work so nit give you an alarm and generator will start
@iepdcpower3343
@iepdcpower3343 2 жыл бұрын
Sir can please teach us how to program it like Deif and DSE
@benzblogsVlogs
@benzblogsVlogs 2 жыл бұрын
First thing sir you need the app and its should be just follow in my yt there is how to do it
@ahmedsallam5228
@ahmedsallam5228 2 жыл бұрын
How can I contact with you? If you have time ?
@benzblogsVlogs
@benzblogsVlogs 2 жыл бұрын
Just comment here or message me in my facebook account thabk you
@JUNCOSTILLASVLOG47
@JUNCOSTILLASVLOG47 3 жыл бұрын
Black out video mo Jie😁
@benzblogsVlogs
@benzblogsVlogs 3 жыл бұрын
Di nga nbubuksan ko naman
@umehmmaduabuchi7879
@umehmmaduabuchi7879 Жыл бұрын
Sir I think you can reset that in the module directly instead of using your laptop. Please explain better or show how to reset direct from module
@benzblogsVlogs
@benzblogsVlogs Жыл бұрын
What reset u want alrms? Pls clarify your questions
@gilbertcornerstv792
@gilbertcornerstv792 3 жыл бұрын
Sir ask ko lng kung problema sa genset namin shutdown voltage up lumalabas thanks God bless...
@benzblogsVlogs
@benzblogsVlogs 3 жыл бұрын
Meaning di naabot or sobrang taas yung numinal adjust to the voltage accodingly kong ano man ang settings sa program ither 240 or 440
@benzblogsVlogs
@benzblogsVlogs 3 жыл бұрын
Ang alarm nyan ither over or under voltage to para makacguro gamitan mo ng votage meter para masure
@gilbertcornerstv792
@gilbertcornerstv792 3 жыл бұрын
Kei sir maraming salamat
@benzblogsVlogs
@benzblogsVlogs 3 жыл бұрын
Salamat din sir bless you
@olusanyaabisoye3138
@olusanyaabisoye3138 2 жыл бұрын
Am having issue with my generator, the DSE 7210 is displaying ECU RED. How do i fix this?
@benzblogsVlogs
@benzblogsVlogs 2 жыл бұрын
Ecu red means you have problem of your engine if you have est tool kit there you can check
@olusanyaabisoye3138
@olusanyaabisoye3138 2 жыл бұрын
@@benzblogsVlogs thank you sir,but I didn't have est tool kit with me
@mystery7310
@mystery7310 2 жыл бұрын
Sir tanung ko lang po ano Ba possibilidad bakit Hindi maka takbu to generator n inooperate ko nagana yung starter motor nya pero Hindi siya sumasabit sa flywheel or ringer.. hindi po kayo sira ang starter solenoid nito?
@benzblogsVlogs
@benzblogsVlogs 2 жыл бұрын
Pag ganyan sir ither sira na ang ngipon or dina natulak yung soleniod ng starter mo
@benzblogsVlogs
@benzblogsVlogs 2 жыл бұрын
Try to remove and try to give supply to check if your starter condation is maayus pa
@mystery7310
@mystery7310 2 жыл бұрын
@@benzblogsVlogs salamat sir. Baka po sira n nga yung solenoid kasi di na siya mag tulak pero nagana ang starter motor nya.request ko na Lang siguro ng michaniko para mas check.
@shajeemonjohany5645
@shajeemonjohany5645 3 жыл бұрын
Nice bro
@benzblogsVlogs
@benzblogsVlogs 3 жыл бұрын
Thanks bro bless you keep safe
@jagjeetsingh-ih3zv
@jagjeetsingh-ih3zv 2 жыл бұрын
🌷
@benzblogsVlogs
@benzblogsVlogs 2 жыл бұрын
Thank
@subhadeepsahu3996
@subhadeepsahu3996 2 жыл бұрын
Sir Mera Dg generator ka display mey-"ENGING STARUS WARNING OILP LOCK OUT MANUAL" -yahi likha so ho raha hai or koi display me Kam nahin ho raha hai..start button kharab ho gaya hay.
@benzblogsVlogs
@benzblogsVlogs 2 жыл бұрын
Do one one thing fix first the problem before you can reset in the module that kind of alarm
@lahiruwajira3905
@lahiruwajira3905 8 ай бұрын
Why does Crank Attempt1 fail here?
@benzblogsVlogs
@benzblogsVlogs 8 ай бұрын
There is more reason behind it some are battery low some are fuel is not present in the emjector,
@jimnahmananap2128
@jimnahmananap2128 2 жыл бұрын
sir what if all light indicator on the buttons of controller is on.. what is the cause ??
@benzblogsVlogs
@benzblogsVlogs 2 жыл бұрын
All the light indicator is on thin make sure your configuration is in correct
@jimnahmananap2128
@jimnahmananap2128 2 жыл бұрын
@@benzblogsVlogs thank you sir
@brucelimbago7861
@brucelimbago7861 3 жыл бұрын
Sir magandang gabi or araw tanong lang kung pano maka kuha ng DSE sytem para maka pag load or makapag palit ng settings sa mga DSE monitoring or engine controll pannel salamat po sa sagot...
@benzblogsVlogs
@benzblogsVlogs 3 жыл бұрын
DSE APP you mean ponta kalang sa website nila sir mag resgister ka doon tapos magpadala sila confermation at pagkatapos noon pwedi kna magupload ng sofware nila www.deepsea.com
@brucelimbago7861
@brucelimbago7861 3 жыл бұрын
@@benzblogsVlogs okey sir salamat po
@kiboytv7756
@kiboytv7756 3 жыл бұрын
what if you dont have laptap to set the parameter
@benzblogsVlogs
@benzblogsVlogs 3 жыл бұрын
You can not if its a synch
@benzblogsVlogs
@benzblogsVlogs 3 жыл бұрын
But if only standard ot stand alone you can do it manualy in the module but limited
@babikiradam6256
@babikiradam6256 2 жыл бұрын
What is the Crank Attempt 1
@benzblogsVlogs
@benzblogsVlogs 2 жыл бұрын
Crank attemp means module is trying again to crank depend on your configuration but standrard is 3 times only so the engine will crank 3 time until generation will run.
@pinoytechelectrical
@pinoytechelectrical 2 жыл бұрын
Sir ganda araw po my generator it won't run the warning is DIGITAL INPUT C what is the cause how i will fix it. Thanks
@benzblogsVlogs
@benzblogsVlogs 2 жыл бұрын
Sir take a look with the digital input and check the wire and the confige why its not program propperly
@delvinewynzam2292
@delvinewynzam2292 29 күн бұрын
Loss of Mag- PU what does it mean?
@benzblogsVlogs
@benzblogsVlogs 28 күн бұрын
Meaning there is connection between you magnitic pickup or defective
@edmarvillar
@edmarvillar Жыл бұрын
good day po sir, ask lang po why my generator faild to start even crank would not,baterry is good and starter alternator, ano po pwede ko gawin salamat sa sagot..more power sir
@benzblogsVlogs
@benzblogsVlogs Жыл бұрын
Posible yes or relay or starter somtimes module
@benzblogsVlogs
@benzblogsVlogs Жыл бұрын
Use multimeter to check if any volyage out from module to starter telay
@mechanicdodz
@mechanicdodz 3 жыл бұрын
Sir. Pwedi koba malaman massenger MO Kong pwedi sana. Patulong Sana ako sa unit ko dto Perkins.
@benzblogsVlogs
@benzblogsVlogs 3 жыл бұрын
facebook.com/groups/1581429425388674/
@mechanicdodz
@mechanicdodz 3 жыл бұрын
@@benzblogsVlogs sir Yong Perkins ko dto nag over speed sya... Tapos may Naka lagay monitor fail stop. Kaya ba reset ito sir. Salamat.
@benzblogsVlogs
@benzblogsVlogs 3 жыл бұрын
Ok sir no problem ilang kva sir message mo ako sir hanapin mo lang Benjie mosquite sa facbook
@viswanathan.g4567
@viswanathan.g4567 Жыл бұрын
How do solve the a s lock out
@benzblogsVlogs
@benzblogsVlogs Жыл бұрын
Lock out meaning the alarms that not reset or rectifiy go to the alarm list there you can see thin try to rectify what alarm of the generator you have thin reaet it after tht it gone
@kiboytv7756
@kiboytv7756 3 жыл бұрын
how to download the sofwer
@benzblogsVlogs
@benzblogsVlogs 3 жыл бұрын
Just go the there sire regester there
@benzblogsVlogs
@benzblogsVlogs 3 жыл бұрын
Go www.deepsea.com its free just registered there
@520-b2v
@520-b2v 3 жыл бұрын
Pa shoutout and subscribe narin si kalokongjho😊salamat
@benzblogsVlogs
@benzblogsVlogs 3 жыл бұрын
Done sir
@benzblogsVlogs
@benzblogsVlogs 3 жыл бұрын
No prob nextblog sir
@transientmatter6088
@transientmatter6088 2 жыл бұрын
Can you give securty pin to deepsea controllers to avoid people access it in front panel?
@benzblogsVlogs
@benzblogsVlogs 2 жыл бұрын
0000-1234
@indrajitbiswas9647
@indrajitbiswas9647 2 жыл бұрын
hi sir GENERATOR OF DISPLAY is just being RAIDING locked out. How to solve. I saw your video. I have done it that way but it is not happening. DISPLAY NO. 6120 MKIII Please help me....  Please help me
@benzblogsVlogs
@benzblogsVlogs 2 жыл бұрын
Ok if lock there is alarm for that check the module what is the alarm list this if found it rectify the problem my nit only one make that all you rectify first before you can reaet it from the module stop botton double click it to reset
@indrajitbiswas9647
@indrajitbiswas9647 2 жыл бұрын
Oil engine fult
@indrajitbiswas9647
@indrajitbiswas9647 2 жыл бұрын
Thank you for reply sir... I well try
@indrajitbiswas9647
@indrajitbiswas9647 2 жыл бұрын
Sorry, oil sensor fult showing
@benzblogsVlogs
@benzblogsVlogs 2 жыл бұрын
@@indrajitbiswas9647 thanks too
@naveedahmad4103
@naveedahmad4103 2 жыл бұрын
hi dear
@benzblogsVlogs
@benzblogsVlogs 2 жыл бұрын
Yes sir
@arunarashidsheriff6623
@arunarashidsheriff6623 2 жыл бұрын
What cause trubocharger is Red
@benzblogsVlogs
@benzblogsVlogs 2 жыл бұрын
Depend on the engine some time you have to check enjector ,injextor calebration, airpressure , intercooler
@henrybugtong8488
@henrybugtong8488 3 жыл бұрын
Boss ano dapat gawin pag ang alarm ay Failed to stop.
@benzblogsVlogs
@benzblogsVlogs 3 жыл бұрын
Sir ganito ang pwedi mong gawin faild to stop ibigsabihon my problima oil sensor mo check mo oil level if ok and vescusity thin if all ok replace mona oil sensor mo
@henrybugtong8488
@henrybugtong8488 3 жыл бұрын
Boss maraming salamat sa pag-sagot.....
@williamvillaruel2066
@williamvillaruel2066 2 жыл бұрын
And another thing po totally off and LCD monitor ng control board pero gumagana padin
@benzblogsVlogs
@benzblogsVlogs 2 жыл бұрын
No if you have other defective module take that lcd and transfer it to this module or else try to open and clean the rebon inside
@mobolajiadeniyi7875
@mobolajiadeniyi7875 Жыл бұрын
There was lock out alarm on a generator and it went down . Gen was restarted what can be the issue
@benzblogsVlogs
@benzblogsVlogs Жыл бұрын
You can see the problem in the alrm list
@kyoot_leah6973
@kyoot_leah6973 3 жыл бұрын
Sir paano e reset ang alarm sa module
@benzblogsVlogs
@benzblogsVlogs 3 жыл бұрын
If yu want to reset the alarm and if your using deepsea just pres stop and double click it to reset
@ssemassem8838
@ssemassem8838 Жыл бұрын
750 kva
@harleyarnado6538
@harleyarnado6538 3 жыл бұрын
good day sir, ano po ba ang posibling dahilan ng error na ito sa Generator namin Taylor Power system sir; *04/BOC L1 under *05/BOC L2 under *06/BOC L3 under *07/Underspeed *salamat po sa sagot in advance.
@benzblogsVlogs
@benzblogsVlogs 3 жыл бұрын
Sir nbalance load yan sir
@benzblogsVlogs
@benzblogsVlogs 3 жыл бұрын
Check mo sensing fuse nya sir yung pomonta ng module baka fuse lang ang my prblima minsan ngayn lang busted lang ang fuse or trip
@harleyarnado6538
@harleyarnado6538 3 жыл бұрын
@@benzblogsVlogs nag testing na kami sir na hindi namin nka contact/switch sa load, ganon pa rin. thanks sa reply
@harleyarnado6538
@harleyarnado6538 3 жыл бұрын
@@benzblogsVlogs cge sir, e check namin to.
@benzblogsVlogs
@benzblogsVlogs 3 жыл бұрын
@@harleyarnado6538 kong ganon double check nyo lang fuse check nyo din ang voltage if ilan an output double check the rpmilan inabot
@SeigfredWall
@SeigfredWall 3 жыл бұрын
Nice content... Master..
How to troubleshoot under frequency & over frequency benzblogs
25:50
benzblogs Vlogs
Рет қаралды 34 М.
How Strong Is Tape?
00:24
Stokes Twins
Рет қаралды 96 МЛН
Quando eu quero Sushi (sem desperdiçar) 🍣
00:26
Los Wagners
Рет қаралды 15 МЛН
Quando A Diferença De Altura É Muito Grande 😲😂
00:12
Mari Maria
Рет қаралды 45 МЛН
Help! My generator is Locked Out! - Here's what to do
2:18
Diesel generators - Americas Generators
Рет қаралды 16 М.
Engine failure to start due to a bad  Relay  #perkins
8:12
DIY & Fix it
Рет қаралды 13 М.
FAIL TO STOP how to troubleshoot in conventional engine benzblogs
13:10
benzblogs Vlogs
Рет қаралды 3,3 М.
How to troubleshoot low voltage in generators benzblogs
10:40
benzblogs Vlogs
Рет қаралды 29 М.
How Strong Is Tape?
00:24
Stokes Twins
Рет қаралды 96 МЛН