How I Replace an Air Conditioner Condenser Fan Motor

  Рет қаралды 118,001

Fox Family Heating and Air Conditioning

Fox Family Heating and Air Conditioning

Күн бұрын

This video shows you how I replace a condenser fan motor. Not one of the hardest repairs to make, but there are some good pointers I make. A condenser fan is responsible for removing the heat from the outdoor unit. We are removing heat from inside the house by sending it to the outdoor condenser. This fan motor removes that heat from the condenser.
I usually will just change the fan motor right at the unit. but in this video, I needed to come down off the roof, because the air conditioner was sitting on some angle iron which was on corrugated roofing. Lol! A bit precarious.
After I replace the condenser fan motor, I turned the system back on and the building started ccoling again.
Please visit our website @ www.foxfamilyhvac.com
If you'd like to book an appointment with Fox Family Heating and Air in Sacramento, El Dorado, or Placer County, CA book.housecallpro.com/book/Fo...
Visit us on our social media pages:
Facebook @ / foxfamilyheatingaircon...
Twitter @ / foxfamilyhvac
LinkedIn @ / greg-fox-46ab48110
Tumblr @ / foxfamilyhvac
0:00 Intro
0:55 Removing the blade
5:10 Removing the motor
7:20 Replacing the Condenser Fan Motor
11:43 Replacing the fan blade
13:35 Putting the top shroud back on
16:00 Tucking the wires

Пікірлер: 161
@mrsturner8532
@mrsturner8532 6 жыл бұрын
Thanks for uploading this. Just what I needed.
@d.vaughn8990
@d.vaughn8990 Жыл бұрын
Cracks me up, watching people in other trades work! I am a former auto/diesel mechanic. I own (and use) every tool imaginable. This guy seems to fix everything with a pair of vice grips and adjustable wrench! The plumber that came to my house, fixed everything with a pair of channel locks! For years, I owed $$$ to every tool truck guy in town! Man, was I dumb! I guess I picked the wrong trade!
@jfinick
@jfinick 6 жыл бұрын
Out of all the videos I've watched on this subject, you are the only one that mentioned the drain plug. Thanks for being so thorough.
@dwiganstube
@dwiganstube 5 жыл бұрын
So many "experts" in the comment section. My a/c started screeching yesterday so I will have to make this repair. Thanks for the tips.
@ChuckD351
@ChuckD351 5 жыл бұрын
Your videos have saved me about a thousand dollars over time.. I’ve changed everything but the compressor. I keep a contactor and a capacitor on hand. It has saved me from having to wait until the next day to get my unit running on a hot afternoon.
@gordonanyhowe3081
@gordonanyhowe3081 5 жыл бұрын
First off I never wear a watch or ring nor does anyone else I know in the field when on the job. I started carrying a pocket watch many years ago but that's just me. Second, to make my repair look clean and hold up longer, I don't use wire nuts and electrical tape. There is room inside the wireway to splice into the original wiring with butt connectors covered with adhesive heat shrink tubing and it takes little or no more time to do. Same for the rotation wiring. And btw, the motor is labeled how to wire it for cw or ccw rotation. Looking at the blade tells me which way to wire it - before I have it completely reassembled. Third, cable ties will get brittle over time, especially when they are tightened to a sharp edge like what is on the louvers of the cover. Cable tie snaps, wires fall into the fan and bad things happen. A piece of conduit or pvc pipe with a stainless steel cable tie is better or a large tie that secures the rotation wires to the body of the motor. I use a replacement motor with the rotation wires in the same outlet of the motor case as the line wires and wire them inside the wireway as well.
@Firemandave911
@Firemandave911 6 жыл бұрын
Don't be that guy but use visegrips insted of sockets or wrenches LOL
@gordonanyhowe3081
@gordonanyhowe3081 5 жыл бұрын
But how else you gonna get that "holding pin" out?
@jeremysummers7196
@jeremysummers7196 5 жыл бұрын
Im super surprised to see you wireing in an extra cap instead of useing a dual run. You only need 3 wires to hook up a condencer fan motor. The white (or yellow) common wire and the brown/white are connected inside the motor. So you dont need one of them. Check the continuity to see what im talking about. An example of wireing would be black to L1, white to L2 (or to common on the cap) and then brown to fan on cap. All other wires are nutted off and zip tied up in place. I see allot of guys doing this. Hell i use to do it till i started reading into motors more. Keep up the good work! =D
@124manr
@124manr 5 жыл бұрын
Lol.. 14:50 the moment you realized you forgot to feed the wires before sealing the lid. Lol It happens, great vid.
@efman2k3
@efman2k3 8 жыл бұрын
Great video. Not the safest conditions to be working in. Glad you got it fixed. Thanks for posting!
@foxfamilyheatingandaircond4696
@foxfamilyheatingandaircond4696 8 жыл бұрын
all good. that's what we do
@randiyoung1993
@randiyoung1993 5 жыл бұрын
Thank you for the video! Yours showed me where the conduit went.
@obus4186
@obus4186 6 жыл бұрын
Excellent video, covers the whole process.
@vickjones4073
@vickjones4073 6 жыл бұрын
I really appreciate your videos very motivational. Your helping me make my mind up on becoming a hvac tech thanks man keep em coming
@jesusfelix2605
@jesusfelix2605 4 жыл бұрын
Thanks for uploading brother. Greeting from Modesto !
@philltafolla
@philltafolla 7 жыл бұрын
Nice repair , just my tough and the way I easily remove those stubborn fan blades, just put a 3/4 socket on that beautiful makita impact you have sitting pretty next to you and, booom , baaam 5 seconds done ! :-) great repair....
@ChrisJohnson-cq5ky
@ChrisJohnson-cq5ky 6 жыл бұрын
Thnk u sir for posting this video it most certainly helped...
@ilovecubes8598
@ilovecubes8598 4 жыл бұрын
Good video, thanks. Did not think I may ever need a fan puller--but likely I do!
@joeykohout8710
@joeykohout8710 8 жыл бұрын
What I do with the direction wires is put them inside a piece of 3/4 pvc pipe before I put the lid on the unit. So I find out my direction first by looking at the blade and seeing if it needs to be ccw or cw rotation. Then that way it's all tightened up and the sun won't make them brittle over time and cause a short. I also see that you use a separate capacitor for the fan. I just switch it to a 3 wire set up and use the duel capacitor. That's if it is the same as what I need. I do that to save on wasting another capacitor and less components stuffed in the compartment. But that's just what I do . Everyone is different. Nice video. P.s. Use ur impact on the puller next time with a 3/4 socket , it cuts down on time and a lot easier for you. Now sometimes u have to use wrench due to it being so tight. But 95% of the time I get away with the impact.
@mtsaz100
@mtsaz100 5 жыл бұрын
EXCELLENT---this is how its done PROPERLY.
@rud8051
@rud8051 4 жыл бұрын
should he have cut the motor shaft to shorten it? does it matter?
@ALZ2526
@ALZ2526 8 жыл бұрын
I have had that puller for about 15 years it's great.
@kolochodelrio1234
@kolochodelrio1234 8 жыл бұрын
You are a beast! Thank you for sharing your knowledge. God bless
@foxfamilyheatingandaircond4696
@foxfamilyheatingandaircond4696 8 жыл бұрын
thanks so much!
@bretmaxwell1892
@bretmaxwell1892 3 жыл бұрын
Thanks for the video! The use of zip ties is a bad idea. Within a year, the UV rays will rot them to brittle pieces of plastic and will fail with your wires falling back into the fan blade.
@4skully
@4skully 4 жыл бұрын
My neighbor and I will be replacing my fan this Monday. Its not fried but its old and the plugs you mention THANK YOU! I bet that is the reason why my fan looks so rusted they never took the plugs out. I hope the balance comes off easier then the one you had arrg I do not have those tools. I have to put a new contacter in too. Doing a rebuild.
@michaelmiller3183
@michaelmiller3183 8 жыл бұрын
Greg you should use a 3/4 grey pvc pipe to hide the additional wires for the rotation wires. I keeps the wires from drying out and fading and make a much neater job.
@foxfamilyheatingandaircond4696
@foxfamilyheatingandaircond4696 8 жыл бұрын
I like it. good point. I'll try it
@xiradio
@xiradio 3 жыл бұрын
I did just this the other day. I also heat-shrink the insulated connectors before I insert them into the conduit. Stainless wire ties are also a must as mentioned in some of the comments. Makes for a much cleaner and safer install.
@axxxxman
@axxxxman 4 жыл бұрын
Great video, I installed that "universal fit" motor on my RUUD last weekend, the big shaft wasn't a problem, but the new motor was "taller" so I could not get the fan to line up with the cowling. I am about an inch low so I think I may be losing efficiency. I wired up for 1/3hp with a 3 blade fan the old one was 2. Only thing I did not like in the video was the use of plastic zip ties to hold those wires. Zip ties degrade in sunlight and heat so I would not be surprised if it broke and dropped the wire down.
@kolochodelrio1234
@kolochodelrio1234 8 жыл бұрын
These are the kind o vids I enjoy. When I see you in action
@erics9213
@erics9213 7 жыл бұрын
Greg, couldn't agree with you more. This is the mark of a conscientious tech. Was wondering why you use vice grips so much.
@foxfamilyheatingandaircond4696
@foxfamilyheatingandaircond4696 7 жыл бұрын
Lol. Just habit...
@copelli3
@copelli3 7 жыл бұрын
great videos, I'm your new enrollee cooling to work here in Brazil, I love your videos ,, make videos showing the tools, ease from then tools is absurd, parabens!
@foxfamilyheatingandaircond4696
@foxfamilyheatingandaircond4696 7 жыл бұрын
Thank you!
@airmechanical7163
@airmechanical7163 8 жыл бұрын
Those fractional horsepower condenser and blower motors are mostly wired clockwise shaft end from the factory.Good video.
@foxfamilyheatingandaircond4696
@foxfamilyheatingandaircond4696 8 жыл бұрын
thanks... coming from the guy who still doesn't have it down which heat pump systems come wired for changeover in heating or cooling. aome things i just will not remember as long as there is a change i can make at the wires or thermostat. hahahah.
@jimbola77
@jimbola77 8 жыл бұрын
excellent job!!!!!
@paulm.7422
@paulm.7422 5 жыл бұрын
I just found this video, but I recently replaced the outside compressor fan motor on my Carrier heat pump. The bearing had gone and it was very noisy/whiney. (With heat pumps, the outside unit also runs in the winter, so the motors wear out faster). I bought the motor online via Amazon. It arrived in a few days and took me less than an hour to replace. What a difference - the outside unit now runs so quietly and the inside handler is now putting out more heat (... which I don't quite understand!) With any electric motor, you just match the specs and the "stud pattern" ... those mounting bolts on the rear of the unit. (CAUTION: Some suppliers specify a motor's stud pattern measured as diagonals ... from stud to stud ... across the center of the motor, but others specify it as two sides of the square pattern).
@hvacrcole
@hvacrcole 8 жыл бұрын
Hey Greg that ground wire on the motor is a case ground and be cut off in that application. If you are using the through bolts of the motor to mount the motor then they will act as your case ground. So next time cut it off.
@foxfamilyheatingandaircond4696
@foxfamilyheatingandaircond4696 8 жыл бұрын
right on Larry. that makes sense.
@matthewmanri3884
@matthewmanri3884 6 жыл бұрын
re
@chupalia
@chupalia 8 жыл бұрын
Good work.
@farooqishaq6974
@farooqishaq6974 7 жыл бұрын
neat job
@BNM0826
@BNM0826 4 жыл бұрын
Great job!
@sanarhkumara3860
@sanarhkumara3860 5 жыл бұрын
Nice work dear
@JCOOK33440
@JCOOK33440 5 жыл бұрын
Not sure I can take a guy serious who uses just vice grips...
@foxfamilyheatingandaircond4696
@foxfamilyheatingandaircond4696 5 жыл бұрын
Haha I get it! We all have our ways right? Lol!
@jacobpryor1310
@jacobpryor1310 4 жыл бұрын
Josh, your soft
@ndown
@ndown 4 жыл бұрын
My thought exactly
@agustiawanwidjaja1261
@agustiawanwidjaja1261 3 жыл бұрын
@@ndown ..××× ,, ×@×× and y... wwwwwwww
@JP-zz5rm
@JP-zz5rm 3 жыл бұрын
But I use vise grips...
@bettershooter
@bettershooter 3 жыл бұрын
Hi, Fox, how you connect those open end wires from motor ?
@abrahamo8934
@abrahamo8934 6 жыл бұрын
could try heat wrench, i.e. apply some heat to the fixture with a torch, before taking it off or any reason not to?
@lajshgddshhdge1579
@lajshgddshhdge1579 3 жыл бұрын
i have fan blade 24" cw i want to know that. how much rpm required for perfect air of 24" fan
@cubanito725
@cubanito725 7 жыл бұрын
nice job...!!!
@bigrollin
@bigrollin 2 жыл бұрын
does the blade have to be all the way against the motor ? when you removed it was at the tip of the pole
@richardme5438
@richardme5438 6 жыл бұрын
1. Do you install the run capacitor with the terminals facing up or down.2. Does it matter how you place the wiring for the fan motor run capacitor.
@davidpetersen5313
@davidpetersen5313 8 жыл бұрын
nice work but that roof little sketchy keep up you do good work
@av8tore71
@av8tore71 4 жыл бұрын
Should have shown how to hook up the wires for someone like me who probably has to take pictures of the wires as to put them back where it originally were. Good video, thanks for sharing
@obus4186
@obus4186 6 жыл бұрын
A couple things: I don't have that fan remover tool so I just did without it - is that okay? When I took my AC unit apart, there was a green grounding wire running from the wiring box to somewhere near the fan motor. So it was screwed into the chassis wall near where the contacter/capacitor is located and the other end I found to be free and unattached near the motor. I think it was either never attached or it became loose as I removed the screws from the top of the unit. Should this be attached to the motor casing?
@hectormonsalve662
@hectormonsalve662 3 жыл бұрын
That is some cool tools
@justin0957
@justin0957 8 жыл бұрын
Word on the streets Greg is still trying to get the blade off..lol
@joeshearer1247
@joeshearer1247 8 жыл бұрын
Ha ha good one
@foxfamilyheatingandaircond4696
@foxfamilyheatingandaircond4696 8 жыл бұрын
hey!! lol!
@scrambler350
@scrambler350 8 жыл бұрын
XD
@TerryDowell
@TerryDowell 8 жыл бұрын
Next time use a 3/4 impact socket and 1/2 in.ratchet works a lot better ...Great video !!
@foxfamilyheatingandaircond4696
@foxfamilyheatingandaircond4696 8 жыл бұрын
I like it!
@poncedeleonrefrigeration9197
@poncedeleonrefrigeration9197 8 жыл бұрын
Man, you are brave, getting on top of that roof
@foxfamilyheatingandaircond4696
@foxfamilyheatingandaircond4696 8 жыл бұрын
all good. that's what we do huh?
@jimbola77
@jimbola77 8 жыл бұрын
I hear u man I'm that way even if it take's me an xtra 15 20 minuites I will figure something out put a track or pvc pipe....
@pareshpatel7343
@pareshpatel7343 5 жыл бұрын
Fan won't move in the unit. I push fan with wire and it will work. I replaced capacitor and fan motor. Still fan won't start it self. Need help to understand what is the problem.
@JerzyBoy973
@JerzyBoy973 5 жыл бұрын
You didn’t cut the excess shaft. That can lead to premature wear. 🤦🏾‍♂️
@rud8051
@rud8051 4 жыл бұрын
well is it neccesary fox ac?
@truckinforever985
@truckinforever985 6 жыл бұрын
Good Job but I was told to cut the shaft of the motor down, because if you do not it will cause premature bearing failure. Correct me if I am wrong
@ultrafaga1947
@ultrafaga1947 5 жыл бұрын
You are correct 👍
@xiradio
@xiradio 3 жыл бұрын
How so?
@joeshearer1247
@joeshearer1247 8 жыл бұрын
I love the way cars sound like nascar when in fast forward
@Gearboxrb00017
@Gearboxrb00017 6 жыл бұрын
Great job on the video and instructions. The only thing unclear to me is the wiring. On this job the old condensor fan motor had three wires. The new motor (possibly a generic brand) had 4 main wires and a green ground wire. I only saw what you did with the ground wire. I believe you attached two wires (two brown wires) to a new condensor fan motor capacitor then attached the yellow to constant and black to fan??? My Old Lennox fan motor had three wires like the old fan motor in the video. The new fan motor had 4 wires like the new motor in your video. I put two of them to the new fan motor condensor and then put yellow to constant and black to fan on the mother board. Your thoughts.
@Garth2011
@Garth2011 Жыл бұрын
Universal motors vs exact fit or OEM.
@dannycedeno8142
@dannycedeno8142 4 жыл бұрын
MAN THAT WAS GREAT
@xiaosun9111
@xiaosun9111 4 жыл бұрын
nice video
@muniznick
@muniznick 8 жыл бұрын
I also cut the ground wire, same puller but carry an extra, stripped one once, on directional wires I note the orig mtr direction on nameplate & conn univ mtr wire accordingly but cut them short and use those translucent pigtail wire connectors and saves me any extra add on tubing/tie wraps & they are out of way/sight. Nice alley, around you need an armed guard at truck.
@anglergoff
@anglergoff 8 жыл бұрын
What brand is that puller? That thing is sweet, better then using a bench vise, 3/4 black pipe, a punch and a hammer. Love the videos keep up the good work. Keep them 🔧 turning.
@3beltwesty
@3beltwesty 8 жыл бұрын
That puller is a Sensible Products UP-1 . The one here I got in 1998.
@anglergoff
@anglergoff 8 жыл бұрын
+3beltwesty thanks for the information, might have to get one
@MrShawnphilip
@MrShawnphilip 5 жыл бұрын
Any advice on how to cut that Rod after the fans installed, I wasn't able to get the grill on because the rod is too long.
@ultrafaga1947
@ultrafaga1947 5 жыл бұрын
Hacksaw
@axxxxman
@axxxxman 4 жыл бұрын
Grinder, but make sure you cover up the motor, the metal shavings will end up in the motor (magnets) and damage it.
@solarpowerelectricityandel2915
@solarpowerelectricityandel2915 7 жыл бұрын
the word your looking for is set screw
@greatpharoh0303
@greatpharoh0303 5 жыл бұрын
Another Awesome video! Incredible! Thank you
@truckinforever985
@truckinforever985 5 жыл бұрын
You could have cut the ground off due to being mounted on the top of the condenser which is grounded when you bolt it on
@aircooledtx
@aircooledtx 7 жыл бұрын
Tip, refer/wrench will loosen blade nut, York-3/8 " nuts, rescue 11/32" ,look at blade curve facing U CW so purple.orange, clip wires in.term cap connector then no wire to hang, no ground need, as motor nuts ground unit. Also stick 1/4 nut driver in extra length bolts back forth snap right off.Save wire ties and look much better. Also black tape wires along channel keeps them together and weather better.
@aircooledtx
@aircooledtx 7 жыл бұрын
Also, on unit cover plate/mtr 8/16 ..Helps
@hediervarelamedina987
@hediervarelamedina987 3 жыл бұрын
the explanation is really good. but by logical rules of forgiveness security, you should not carry out tasks of this type with rings on the fingers of the hand, much less have a watch on. They are elements that even if they do not believe they are suitable for an accident. I see that in that aspect he does not have a self-care. and in relation to the blade extractor, to do the job well and take care of it, the captive screws can be secured with a 13mm cup and 3/8 slot and the screw that makes the pressure to extract the blade with a glass of 19 mm or 3/4 to take care of the quadrant and for the bolt that secures the blade to the shaft, it is good to use an 8mm open-end wrench so as not to sweep it because for a later repair there may be drawbacks. For the most part, the video is good.
@mhbarillas9187
@mhbarillas9187 5 жыл бұрын
lol don’t be that guy, appreciate the tutorials 👍🏽
@edca8114
@edca8114 4 жыл бұрын
whats the " correct way" for a fan to run from your point of view ?
@axxxxman
@axxxxman 4 жыл бұрын
The blade will usually have an indicator of "clockwise" for the correct rotation
@debraparker833
@debraparker833 4 жыл бұрын
Good video, too bad on the roof ( I bet HVAC Techs hate systems on the roof- does that increase labor cost?)there was no audio. I like your sound effects when you were struggling to get that shaft from the fan - sounded like Mickey Mouse, lol. It's nice to know Techs like you take pride in their work. Hardworking folks don't want their money wasted on sloppy and substandard work. How much is it to replace a Condenser Motor Fan on a 14 year old Carrier Heat Pump (2 speed, 14 seer - 2 ton unit)? Thanks again for the video - you have a great sense of humor.
@buddyrye9190
@buddyrye9190 3 жыл бұрын
My holding pin is out but the fan blades are resting with wd40 overnight and gonna try tomorrow. How is it that rust is like a freaking weld?
@foxfamilyheatingandaircond4696
@foxfamilyheatingandaircond4696 3 жыл бұрын
Yeah it happens. Sometimes you end up needing to get a new blade (has to be exact replacement) and fan motor. Good luck man
@buddyrye9190
@buddyrye9190 3 жыл бұрын
Thank you sir. Your content is top notch.
@dosduce
@dosduce 6 жыл бұрын
Always wear safety glasses!
@jimbola77
@jimbola77 8 жыл бұрын
yes I totally agree I worked with a guy I could never give him advice, he claimed to know everything! sloppy worker no nitrogen while brazing never recovered I split way's with him.
@Garth2011
@Garth2011 Жыл бұрын
A couple of questions. Why don't supply folks carry the correct motors with the 3 wires and correct rotation vs "universal" ? Aren't the jobs to match what was there and look like it was with USA made motors ? Second, these condenser motors are in vast supply from vast makers and come with ball or sleeve bearings. With all else equal, which bearing is most dependable and to last longest, ball or sleeve?
@77.88.
@77.88. 5 жыл бұрын
It appears you have a impact cordless gun why not fit a socket to it and hold onto the tool with a wrench and apply slight pressure til the puller starts moving, what's with the vise grips, its so much easier with the right tools. You could probably preheat the fan bushing with a propane torch and the fan may just slip off the shaft?
@wwjd3d
@wwjd3d 2 жыл бұрын
This guy definitely gets paid by the hour
@foxfamilyheatingandaircond4696
@foxfamilyheatingandaircond4696 2 жыл бұрын
Ha. That's funny. 🤣
@Garth2011
@Garth2011 Жыл бұрын
Likely it was a quoted price unless he told them time and material.
@kevinlogan2306
@kevinlogan2306 7 жыл бұрын
Might as well rip the ground wire off because it isn't doing anything in that application
@acservicedaytona386portora3
@acservicedaytona386portora3 6 жыл бұрын
Don't Be That Guy.........Love It....😎
@khalidflorida2389
@khalidflorida2389 3 жыл бұрын
Why you don’t show wires where you put them ?
@hvacrjunky6119
@hvacrjunky6119 8 жыл бұрын
Looks like a sketchy roof. 😬👍
@foxfamilyheatingandaircond4696
@foxfamilyheatingandaircond4696 8 жыл бұрын
It really was. The angle iron was pretty stable though.
@compassioncampaigner3297
@compassioncampaigner3297 5 жыл бұрын
With all due respect, I think i know less now. I am a super novice so I need lots of help. I dont need video of turning bolts. I can do that. Wiring info...for mr.....nonecistant. Did he cut the shaft? The magic marker wire trail was good.
@ChrisJohnson-cq5ky
@ChrisJohnson-cq5ky 6 жыл бұрын
Need a new knock out kit bro...used up alot energy Gettin that fan blade from the motor
@MrLaffertyheating
@MrLaffertyheating 8 жыл бұрын
A precarious perch. At least it wasn't four stories up!
@liverdelove
@liverdelove 8 жыл бұрын
I always cut the motor shaft as close as possible. motor spins better and last longer.
@IshockO
@IshockO 7 жыл бұрын
liverdelove how do you know?
@liverdelove
@liverdelove 7 жыл бұрын
IMon from my experience as an ac tech. 15 yrs
@IshockO
@IshockO 7 жыл бұрын
liverdelove beats my one year experience, I'll believe you
@beertek22
@beertek22 4 жыл бұрын
How close should the blade be to the motor, is there any acceptable space in between or just anywhere, before cutting off the rest of the rod?
@toddac61
@toddac61 3 жыл бұрын
@@beertek22 Measure distance from lid to fan blades before removing and put blades at same distance from lid with new motor. Critical for correct airflow.
@vaccumme
@vaccumme 8 жыл бұрын
Acrobat Service Tech !!
@Kyle-jg1lv
@Kyle-jg1lv 4 жыл бұрын
That's folsom and 65th
@koldenrjk
@koldenrjk 5 жыл бұрын
I'd just at as soon buy a new blade as well.
@jordanfriar8732
@jordanfriar8732 8 жыл бұрын
#visegrips lol
@foxfamilyheatingandaircond4696
@foxfamilyheatingandaircond4696 8 жыл бұрын
hey! what do you use? lol...😀
@gerardomireles122
@gerardomireles122 8 жыл бұрын
A fox family and then you don't take it measurements where is the fan blades and the right place thanks.
@Garth2011
@Garth2011 Жыл бұрын
Not everything gets recorded on video...its not likely he wants a come back.
@mtsaz100
@mtsaz100 5 жыл бұрын
Big no no- KNOWING that wire will get cut up by condenser fan when that zip tie fails because of vibration and the sun. Are you serious? That will last a year or 2 and the zip tie will break. You need to tightly wrap those wires up- and enclose them in a piece of plastic conduit or something so that they are protected by sun and out of the way. ANd so what if you have to lift the motor up to change the (CW/CCW) direction the motor turns. That is no reason to leave wires exposed or accessible. That is for your convenience but not the way you do it. I wont even mention leaving 5-6" of extra shaft hanging down- or the vise grips---seriously- this is a half assed job- and will fail much quicker than it should- and then who pays? Sadly the customer pays again. Do it right. It just gives us all a bad name.
@Sal112350
@Sal112350 3 жыл бұрын
yes, that zip tie will get weather in less than a year with attachment to metal, fan will shred that wire in a year, bad workmanship.
@darinpugliese5103
@darinpugliese5103 7 жыл бұрын
That DustBuster just gives you a good headache
@DIZEMANPHOTO
@DIZEMANPHOTO 5 жыл бұрын
You attached the green wire/ground to one of the bolts between the motor and the fan shroud. isn't the fact that one boil is now further away from the fan shroud than the other three going to cause an offset in the mounting of the motor? I know the thickness of the ground wire EYE is not that thick, but any offset at all when the fan is up to speed could cause warble and vibration... YES? NO? Perhaps that is why the OTHER GUY attached his green/ground wire to the bolt on the outside, since doing so had no effect on the flush mounting of the motor to the shroud. ? ? ? screamcentral.net/misc.pics/groundwire.jpg
@scrambler350
@scrambler350 8 жыл бұрын
Another way to avoid being THAT GUY is to wrap the spade connectors for those reversing wires with electrical tape so that they are water-proof, much more important that hiding them for looks - I work on the coast and have seen those connections corrode and cause a failure...YMMV. A few extra seconds and some electrical tape go a long way,
@SuperJeremi10
@SuperJeremi10 7 жыл бұрын
mike_HVAC just hide theme in a small peace of pvc piping and zip tie that part to the underside of fan grill.
@krzysztofslomiany4090
@krzysztofslomiany4090 3 жыл бұрын
are the plugs for oil/lubrication? these cheap china motors have a tiny rubber cap on the shaft that probably allows rainwater in pretty easily. what if you fill it with oil and put the plugs in?
@eagletek1
@eagletek1 8 жыл бұрын
Don't show the homeowner everything! !Great video
@foxfamilyheatingandaircond4696
@foxfamilyheatingandaircond4696 8 жыл бұрын
haha.
@Rodzilla408
@Rodzilla408 5 жыл бұрын
We're going to be out of a job if you continue to show every step. LOL. But keep putting out good videos
@manoweb1
@manoweb1 2 жыл бұрын
go buy a damn small set of nut drivers dude.... it won't break the bank!
@derekobidowski3301
@derekobidowski3301 5 жыл бұрын
i wouldn't recommend changing the motor in these York units mainly the ones with the Microchannel coils they leak its recommended to change the entire outdoor unit
@angelslive1
@angelslive1 8 жыл бұрын
zip ties in las vegas not a good idea they will not last and the wire will later get caught in the blade
@douglaskahane141
@douglaskahane141 8 жыл бұрын
you can get metal zip ties from harbor Freight.
@darinpugliese5103
@darinpugliese5103 7 жыл бұрын
That's not a good replacement motor
@romesantos6026
@romesantos6026 3 жыл бұрын
To much struggle
@906lane
@906lane 3 жыл бұрын
Someone remind me not to hiring this company. I see they do sloppy work and the use of vise grips was killing me.
@sonicthehedshot9789
@sonicthehedshot9789 6 жыл бұрын
Directions unclear head stuck in toaster.
No Cooling/Bad Condenser Fan Motor
31:01
John Israel HVAC
Рет қаралды 4,4 М.
How To Replace Air Conditioner Condenser Fan Motor
25:30
Word of Advice TV
Рет қаралды 212 М.
World’s Largest Jello Pool
01:00
Mark Rober
Рет қаралды 63 МЛН
Clowns abuse children#Short #Officer Rabbit #angel
00:51
兔子警官
Рет қаралды 78 МЛН
Mama vs Son vs Daddy 😭🤣
00:13
DADDYSON SHOW
Рет қаралды 40 МЛН
Save Hundreds Doing The MOST COMMON Air Conditioner Repair YOURSELF.
10:38
2007 Dodge Ram 1500, AC Condenser Fan Replacement
27:44
Gerald Fensterer
Рет қаралды 2,1 М.
How To Check & Replace An Air Conditioner Capacitor
8:52
The DIY HVAC Guy
Рет қаралды 862 М.
Why Are My AC Registers Sweating?😰
10:53
Fox Family Heating and Air Conditioning
Рет қаралды 48 М.
How to Replace an AC Condensing Fan Motor
9:48
HVAC School
Рет қаралды 245 М.
Replacing a condenser fan motor on a Goodman
11:07
HVAC GUY
Рет қаралды 29 М.
How to Install a Condenser Fan Motor. Understanding The Electrical Wiring In An Air Conditioner.
22:21
Evolution of GunBrick 🤯
0:39
GunBrick
Рет қаралды 8 МЛН
Footballers Crazy Water Pool Challenge 🌊
0:27
Football Life
Рет қаралды 16 МЛН
Mummy naya le aayi 🥰
0:36
Cute Krashiv and Family
Рет қаралды 35 МЛН
Самодельное ухо?!? @zackdfilms - автор анимации.
0:31
Время знаний
Рет қаралды 7 МЛН
ToRung short film: 🤫pick up money💵🤑
0:26
ToRung
Рет қаралды 8 МЛН
Useful gadget for styling hair 🤩💖 #gadgets #hairstyle
0:20
FLIP FLOP Hacks
Рет қаралды 8 МЛН