Very nice explanation, Sir please prepare a video on trip block on inrush from micon P642 to C264 using goose communication.
@baranitech3 жыл бұрын
Will try for you
@somidiraj4 жыл бұрын
How to detect if there is any break in FO cable and loss of signal from IED to IED ( when in redundant system, IED still be abale to communicate through another cable)
@baranitech4 жыл бұрын
i don't know how to find but i will try to get solution for your ans soon.
@haribalankumar46575 жыл бұрын
Awesome.....Can you upload video regarding busbar concept..
@alial-shaibany75712 жыл бұрын
Thanks
@baranitech2 жыл бұрын
Welcome
@Vicky-xl7no3 жыл бұрын
Communication mode from micom to abb through fo cable are ethernet how to use that
@baranitech3 жыл бұрын
we can use fiber optical also.
@clintonthangaraj42504 жыл бұрын
You covered in all videos how the GOOSE message is send from ABB,Micom,Siemens relays and GOOSE message is received to ABB, Siemens but GOOSE receiving in Micom relay is not available in any other videos. If possible teach us how to receive GOOSE message in Micom relays.
@baranitech4 жыл бұрын
soon i will make
@jhonkevincardenasalva80564 жыл бұрын
El bloque lógico que une a los bloques "AND - CB Close enable logic" y al bloque lógico "NOT - P543_Block" mostrados en el min 16:22; debería ser un bloque lógico "AND" , no un bloque "OR" , esto debido a lo indicado en el min 1:43 - "block CB close enable".
@baranitech4 жыл бұрын
@16:22 it should be AND gate . i have done mistake
@CKP272 жыл бұрын
Sir make video for c264 GE make and use of CET software
@baranitech2 жыл бұрын
i will try
@CKP272 жыл бұрын
Make video of how can replace p444 relay with old relay mcl
@baranitech2 жыл бұрын
good topic i will study first and then i will try to make
@choskinwest4 жыл бұрын
How to do goose from ABB to micom ? ABB as publish and micom as subscriber?
@baranitech4 жыл бұрын
create IEC file on micom and import to ABB project file for doing Goose cofiguration
@choskinwest4 жыл бұрын
@@baranitech it’s for goose from micom to abb right? I mean how about goose from abb to micom, I’ve tried export cid file from pcm600 for abb and imported to s1 agile for micom subscriber, but it doesn’t work
@baranitech4 жыл бұрын
@@choskinwest First export micom CID file from mcl and import to IEC on ABB pcm600 do goose send and then export IEC file from abb . this export cid has to import to micom mcl
@choskinwest4 жыл бұрын
@@baranitech okay, I’ll try it, thanks
@vennapusavenkatesh55462 жыл бұрын
Sir I want to learn relay. Basic and all types relay training center please send me location are name of institute
@baranitech2 жыл бұрын
1. voltech 2.V EQUAL IR
@asgeirnilsen67525 жыл бұрын
Useful stuff!
@abhishekkalita935 жыл бұрын
It was really useful. But u have missed some parts where a proper explanation was required for proper understanding by new engineers. But those parts were ruined by the loud background music. Kindly stop the music and explain more things line by line
@mr.biplob37954 жыл бұрын
Sir how make CID file for micom relay and if i want comminicate all relay from ethernet switch how to ip address set please make one tutorial for us.
@465AP5 жыл бұрын
Plz don't add the background music... It's ruining the video