App aik aachy teacher ho app ko samjana bhout easy hai
@NeerajGupta-fb4mb3 жыл бұрын
sir starting current 5 to 6 times hta hai full load ka to only 1.5 times use krne se problem to resolve ni hga na...trip to ho hi jayega
@Mukesh.badgal2 жыл бұрын
Thanks bhaiya giving valueable information 🙏🙏🙏
@basuashish277 Жыл бұрын
To calculate full load current of the motor the correct formula is I= (KWx1000)/(√3 x V x Power factor) For 30 KW = 30000/(1.732 x 415 x 0.8) = 52.17. Taking 1.5% of HP is not correct in all cases. If MCCB is AC3 DUTY, it should take care of starting current. No need to take higher rating
@aflatoon51096 ай бұрын
Nop .... its an theory. But practle always. Opposit
@aflatoon51096 ай бұрын
Correct amp. 1.39 company data . But voltage dropage and more power loses issue we requird 1.5. Without power fector
@mathewkoshyvaidyansanu28184 жыл бұрын
Sirjiii... We are applying 1.5 times of starting current for the MCCB that connects to the Motor because of starting current. In residential building each MCCBs are connect to household DBs. If the incomer breaker for a particular apartment that is connected to the MCCB is 40A, then how we willl select MCCBs in the main panel ?
@amankaushik61264 жыл бұрын
If TPN is rated 63A does that mean it can carry 63A load/phase. If not then what does it indicate and how much load we can put per phase on 63A TPN. If there is any thumb rule or formula to calculate same, kindly let us know. Thank you :)
@Abhishek-pe2fw3 жыл бұрын
बहुत बढ़िया एक्सप्लेन करते हो
@SandeepSharma-xy3oj4 жыл бұрын
Thanks u very much sir very good information
@seenudehari5519 Жыл бұрын
Thank you sir for your great service
@Faizy_Ahmad2 жыл бұрын
Shandaar... Zabardast.. Zindabad
@iamakashpatil2 ай бұрын
63amp mccb konse company la best rahega ? 3phase meter hai .. solar system lagaya hain
@samvedna224 жыл бұрын
Very Well explained👍
@electricalwithabhishekjoshi4 жыл бұрын
Thank you Samvedna..
@ghulamalibhatti6965 Жыл бұрын
Wel done
@rakeshsharma-wo3jx5 ай бұрын
Sir meri different different hp ki motor h...15hp,10hp,5hp and three 2hp....to in sab m different mccb lagani padegi ya ek se kaam ho jayega..thank you
@shahbaazalam10033 жыл бұрын
Awesome work sir Ji
@electricalwithabhishekjoshi3 жыл бұрын
Thank you..
@Ayyubqureshi8772 Жыл бұрын
Sir Good Morning please ye batayen के बड़े banglow me जहाँ एक ही banglow ka load 50kw से ज्यादा हो तो कितने amp ki mccb lagayenge
@saifshaikh48113 жыл бұрын
How does the breaking capacity is decided?
@gautamKumar-ss3cy2 жыл бұрын
Sade 17 HP load mein 220 empier ka MCC bhi Laga sakte hain ya nahin
@nishikantasahu4273 Жыл бұрын
Sir mera full load current 15 kW hai. Mai 100 amps ki mccb lagane se koi problem nehi hai?
@navneetkumargupta81112 жыл бұрын
Sir mccb me short circuit 36 KA aur 25 KA me kya difference hai aur ye kitane ka lagana chahiye. Sir please batao.
@kanhucharangouda48332 жыл бұрын
Sir ek 160 amp mccb me one phase me 160 se zyada load aanese trip hoga ya 3 phase milake 160 se zyada ayega to trip hoga, Example, R-110amp ,Y- 78amp,B-88 kya me 160 amp mccb me use kar sakta hnu
@sudhansusamal88862 жыл бұрын
Sir In mcb case u said 25% of full load current and in mccb case 1.5 times of full load current . Which has used in mccb. Both r different or same
@jyotiprakashbehera58892 жыл бұрын
Sir gaao me jo 100kva transformer me kitni amps ki mccb use karege
@snehalshewale73408 ай бұрын
Hello Abhishek..I am continuously watching your videos and it is helpful can you make the video on Ics ICw and Icu and why it is same in ACB
@demothungdok72602 жыл бұрын
If RY=100 Amp,YB=100 Amps,BR= 80 Amps then what Amp MCCB should we use?
@mdnawab52653 жыл бұрын
How you put 1.5 please tell me Or how you calculate 60 amp.that wrong according to rule P=√3*v*I*cos(0.8)
@electricalwithabhishekjoshi3 жыл бұрын
Nawab it's a shortcut method. It is not to get accurate result but to take an idea about current rating.
@mdnawab52653 жыл бұрын
@@electricalwithabhishekjoshi brother please one video for cable size calculation with written details Please this is for me
@mdnawab52653 жыл бұрын
@@electricalwithabhishekjoshi can I get ur what's app no.
@brijeshkumar39084 жыл бұрын
Very good and thanks. Please also explain VCB selection video.....
@SandeepSharma-xy3oj4 жыл бұрын
T/F 11kv/440V Village Area If any fault occure in 440V side L-L , L-N L-E , then Is power trip yes/No..? Plz Explain sir. 440V side no any sefaty Breakers used.
@Rajagamingyt303 жыл бұрын
Thinks sir this video is very useful
@naushadmohammad2784 Жыл бұрын
Sir magar actual practical me 20A Ka breaker s/d chenge hone ke time pe trip ho jata hain
@surendrakumarpuniya4 жыл бұрын
Good explain sir ji
@electricalwithabhishekjoshi4 жыл бұрын
Thank you Surendra..
@surendrakverma555 Жыл бұрын
Very good 👍
@arunjoshi20894 жыл бұрын
Nicely explained.
@electricalwithabhishekjoshi4 жыл бұрын
Thank you...
@harpreetsingh26962 жыл бұрын
Sir agar starting ma motor FLC 5 time ja 6time Jada current late ha to Ham Mccb flc ka 1.5 kyu late ha FLC *6 ampere Kyu n late
@navdeepsingh9243 жыл бұрын
10kva copper stabilizer ka lyee ketna amp ka mccb ke jroorta ha
@parmpalsingh19352 жыл бұрын
Sir ka value of selected mccb 10/25/36/50???
@tarunkumarmondal4683 жыл бұрын
You explained very nice👌👌👌, but requesting you to explain star-delt circuit with drawings.
@utpalkumarchakraborty7262 жыл бұрын
Very good Explin
@mirirshad8101Ай бұрын
Sir i have a question may i ask...?
@sonumeena39573 жыл бұрын
Mccb pr phase 160 ampr hota h ya thito ph m 160 amp hota h
@VinayKumar-ew1qm3 жыл бұрын
Very nice video sir ji
@bibhubisoyi5252 жыл бұрын
If motor takes starting current 6-7 times of full load current during start up, then how we select mccb selection as 1.5 times of Flc...it must hv tripped.. Plz suggest
@zakirhussain81502 жыл бұрын
No it will not trip because motor draws high current in starting for very low period of mili sec and due to braking capacity of mccb it will sustain that current for that period of time and after that in normal running condition if motor draws 1.5 times of it flc then mccb wil trip hope u understand
@bibhubisoyi5252 жыл бұрын
@@zakirhussain8150 Thanks for giving me ur valuble knowledge
@Akhileshkgyan Жыл бұрын
Very nice lacture
@raghavkumar76094 жыл бұрын
Sir aap kh rhe ho ki mccb 1.5 time uper lgana hai but starting current kisi motor ki 6 time jyadad jati hai to kya wo trip nhi krega???
@electricalwithabhishekjoshi4 жыл бұрын
Nahi Raghav nahi karega. Starting current kuch millisecond ke liye hi high jata hai. Aur MCCB Mein aap Delay laga sakte ho
@raghavkumar76094 жыл бұрын
Thanku sir
@electricalwithabhishekjoshi4 жыл бұрын
Most welcome Raghav.
@vkdanewa1173 жыл бұрын
@@electricalwithabhishekjoshi u should clarify this point in ur video...don't upload confusing video
@kannasesham50293 жыл бұрын
Meaning of utilization category A or B , which Cat A ir B used for motor or feeder ...
@NitinSharma-xp8zc4 ай бұрын
Sir mccb ka short circuit rating bhi batao I requested u repeatedly
@aflatoon51096 ай бұрын
Mai always double lagata hu .. kal ko agr ek do mottor. Or addition krni ho to ho jati h as a dummy
@phoolsingh36582 жыл бұрын
Motivational.
@atulthanawala63974 жыл бұрын
Good present ation
@Gopalsinghkhola Жыл бұрын
Sir pls explain short circuit current ratings of MCCB and MCB
@Gopalsinghkhola Жыл бұрын
Pls sir
@shahzadakhan37863 жыл бұрын
Suppose we are connecting 6 Nos of MCBs rating 16 amp in each phase RYB respectively. What will be tha size of MCCB?
@volterkhristi33532 жыл бұрын
100A mccb
@sarveshshegade970 Жыл бұрын
How to choose KA rating for MCCB ?
@Rajagamingyt303 жыл бұрын
Sir Mere co ka lode 120a 1fes Hai to kitne a ka mccb lgaye
@uniquewords9874 жыл бұрын
🎋Nice thanks sir for the information .
@electricalwithabhishekjoshi4 жыл бұрын
Most welcome Akshay..
@tejshreekadam6204 жыл бұрын
00
@anupsingh58583 жыл бұрын
But During MCCB selection- we directly multiply 1.5 to FLC and we get desired MCCB. So How this time why we don't add the multiplication value to FLC at the Last like we do in the case of selection of MCB rating??
@kuldeepjangra18683 жыл бұрын
Very nice sir 👍 But resistive load pr mccb kaise calculate karenge
@rehanbabu14562 жыл бұрын
Total 4 Floor hai per floor me 6 unit hai usme kitne AMP Ka Msb Aur Mccb lagaye please help
@fahimasghar63754 жыл бұрын
Nice video Sir. Please tell us how to select MCCB in industry of any machine? Eeven that machine having different motors and other loads? Thanks
@dipankarmallick84453 жыл бұрын
u hv to consider total loads' summation as full load
@himanshupatel84344 жыл бұрын
very nice vdo..
@NARENDRAKUMAR-ub7nj Жыл бұрын
Aur uska overload protection kaise setting Kiya jata hai
@NP-up4dz4 жыл бұрын
How to calculate ka rating formula for mccb
@electricalwithabhishekjoshi4 жыл бұрын
Nayan, it is mentioned in video that how to select rating.
@dipanbarman87162 жыл бұрын
Valuable tha♥️
@rameshthakur7941 Жыл бұрын
all size mccb kitana amp se lekar kitana amp tak ata hai
@NARENDRAKUMAR-ub7nj Жыл бұрын
Hame mccb me I'm(a) ka matalab kiya huta hai sir use per video banakar bataiye
@RakeshPatel-jc8wv4 жыл бұрын
100 a ki mccb hai R 90 y90. b 90 total 270 a ka load hai to konsa mccb lgana chahiye batao
@shishirakathar2402 Жыл бұрын
Good
@TarsemSingh-zz2ot10 ай бұрын
industrial induction Road Ke Liye mccb ka selection kaise karen
@priyabrataswain3631 Жыл бұрын
Sir ABB MCCB CURRENT SETTING KESE KARENGE EK VIDEO POST KIJIYE
@vrushabhuniversalsolutions9462 жыл бұрын
But mccb trip rating kaise select karenge
@rchadha743 жыл бұрын
which mccb required for 7 no Ac of 1.5 ton.
@MagnificentVillain Жыл бұрын
200 A
@smartidea16364 жыл бұрын
Thanks sir for this video....
@electricalwithabhishekjoshi4 жыл бұрын
Most welcome Prashanta..
@smartidea16364 жыл бұрын
@@electricalwithabhishekjoshi hello sir ... Sir mai ek 12MW power plant me job karta hu... Odisha me Sir thoda bataye resume kese banayenge aur kese hau other Power plant keliye apply kare... Sorry sir thoda personal questions puchh liya Pls sir thoda help kariye
@electricalwithabhishekjoshi4 жыл бұрын
Prashanta, aap yaha mujhse personal and professional dono hi batein discuss and share kar sakte ho.. Prashanta, abhi switch k liye thoda ruk jao. Agar present job mein koi problem na ho to abhi hold karo. Resume mein aap apne key responsibility ko presentable way mein likho. Agar koi project mein involve rahe ho to use mention karo.
@dipankarmallick84453 жыл бұрын
KA also need to be mentioned
@devrana..4 жыл бұрын
Full load current Ka 6 to 7 time ya starting current Ka 6to 7 time
@devrana..4 жыл бұрын
Difference between star and delta connection
@electricalwithabhishekjoshi4 жыл бұрын
Starting current full load current ka 6-7 times hota hai.
@electricalwithabhishekjoshi4 жыл бұрын
Dev, ispe maine video banaya hai.. Aap wo video dekhiye..
@devrana..4 жыл бұрын
@@electricalwithabhishekjoshi Star me full load Ka 33 percent hota.hai To 33 percent multiple 6,7 time Ya full load current Ka 6 to 7 time
@electricalwithabhishekjoshi4 жыл бұрын
If you are taking about str Delta Starter then kindly watch my video on that. Because case is different for star Delta Starter.
@RakeshPatel-jc8wv4 жыл бұрын
R 70. Y 80 b80 current hai to kaise select kare mccb tino phase load
@prakashkumar87184 жыл бұрын
160 amp Mccb me 25 ya 36 ka selection kaise kere
@electricalwithabhishekjoshi4 жыл бұрын
Let me see which type of MCCB you are using.
@sumitkumar-xm8rh Жыл бұрын
Ho mai kyun conver kiya gaya direct kw ka FLC ka1.5 kyun nahi kiye
@sachinhowal88004 жыл бұрын
👍👍👍
@electricalwithabhishekjoshi4 жыл бұрын
Thank you Sachin..👍
@Parihar19863 жыл бұрын
Parnam sir
@nemchandsahu433 жыл бұрын
Sir 36kw Load ke liye MCCB ka calculation kaise karna hai
@mubasshiryunus22414 ай бұрын
❤❤
@abhishekyadav553523 жыл бұрын
Tq sir
@solarexpert7688 Жыл бұрын
Nice information
@naushadmohammad2784 Жыл бұрын
Mccb 1.5 times or mcb 25 % extra kyu
@muradbaloch3704 жыл бұрын
0.764 say q divided kary
@mubasshiryunus2241 Жыл бұрын
❤
@vignesha4507 Жыл бұрын
English subtitles needed
@gyanadas16262 жыл бұрын
You could have said the same thing in the MCB rating video only. No need to rack up more videos..