Nicely done. I’m an electrical contractor 35 yrs in the trade and I would have no problem showing this video to my new helpers. I only have a few of my own personal things I like to do but that’s just how I’ve always done my panels. I tape my bare ground green helps to keep it from damage and oxidation. I also prefer to dress my mains last. More sore for replacement panels than new construction just has always been easier and a faster install for me. Big fan of a nice neat dress of a panel. One of my specialities, seems to be a dying art but glad to see it’s not dead. Ty
@ryanthepianoman272 жыл бұрын
Can’t double tap neutral
@tonys8448 Жыл бұрын
American electricians are rough
@johnerway7255 Жыл бұрын
Very neat panel wiring job, thanks for sharing. Our home was wired in 1984 and it looks nothing like yours. Now to find a guy to come in and rerun the in panel wires to look clean and like a pro. Thanks for sharing.
@tazdevl20008 жыл бұрын
i have never seen an electrical panel so neatly laid out in the placement of the wiring. Awesome job
@warrenmichael9188 жыл бұрын
LOL I know it, really nice and neat.. I have watched this video 3 or 4 times just because it is done so neat !
@markmeybell23803 жыл бұрын
Our house is 102 years old. I just came here to see what a tidy panel looks like. Squeaky-clean work, my sir!
@jackriley59743 жыл бұрын
Your house wiring is probably safer than his!!
@SEaudiofan5 ай бұрын
Similar comment, 100+ yr old. Knob and tube with dangerous flying splices. Original branches ran everything, then sketchy upgrades over the years. Getting it neat is a relief
@arobertsworld209910 жыл бұрын
Project circumstances are going to be different everywhere. I used to work for SQD selling same panels and I think this is an Excellent video. Great electrician and communicator.
@rabagochingon5 жыл бұрын
Great video, one note to it, When landing your grounds and neutrals, you DO NOT double them up unless you run out of screws in the ground and neutral bar. and if you do run out, you can only double up with the same gauge wire. like it... nice and clean.
@BearStar12 жыл бұрын
Code only allows the equipment Ground Conductors to be double tapped , but NEVER a Neutral Conductor !!!!
@masterelectrician56122 жыл бұрын
Great video! Very clean & neat install!! Ontario, Canada installers take note! The ground wire goes to the Neutral bar to bond the Neutral to Ground. Then a green ground screw (factory installed) connects the grounded Neutral to the metal box. Electrical inspectors up here will reject the main grounding method shown in this video. Also branch circuit wiring (yellow & orange shown here) CANNOT be run through the main breaker compartment for safety reasons. There is an exception to this allowed if there is a main disconnect switch ahead of this box near the meter box.
@BearStar12 жыл бұрын
But YOU NEVER BOND the Neutral Conductor and the Equipment Ground Conductor in a SUB PANEL , ONLY at the Main Disconnect Panel of the System !!!!
@daninnj85804 жыл бұрын
Yes, everyone argues about who does it best, but this is an EXCELLENT plain and simple, "this is how it works" video. We can argue about how it's done, but this is the neatest cleanest video I've ever seen about what goes on and why.
@dichotomy159310 жыл бұрын
DAMN!...that is a very pretty install! I certainly respect the artistic positioning of an experienced electrician. From one to another.
@celsojoven35254 жыл бұрын
Batangas
@jmelectric82117 жыл бұрын
nice work. very informative. I'm an electrician apprentice I've felt with this type of work for the past 7yrs. working on getting my electrical license. I appreciate your video
@313-v9k4 жыл бұрын
I noticed my Siemens panel has one, it's the only panel and the screw is not turned in. Leave it out or turn it in? Looks to me like it goes through the neutral bar so won't it be connecting the grounds on the box to the neutrals?
@goodbrew18 жыл бұрын
Nice job, a clean panel presents well and gives the comfort of knowing that who ever did the install took good care, attention to detail. I take my wedding band off though....
@Reegareth4 жыл бұрын
Worth Mentioning NOALOX is indeed used for what you said but it's not intended to make a better connection it's designed to maintain a good connection. When aluminum oxidizes as it heats and cools and because of the atmosphere it develops a layer of oxide on it that is not very conducive and actually can increase the overall resistance of your electrical system causing the heating and cooling to become more and more extreme over time which will eventually lead to failure. Just a small note. Excellent installation on all accounts.
@akinsjp10 жыл бұрын
Thanks for the video. Very nice panel detail. I am impressed with the neatness of the wiring. I work at a school district and you would be surprised at what kind of mess I find in the panels when I open one up. Very well done sir.
@nml45464 жыл бұрын
I've watched several of these, yours is one of the better ones, not so much on the technicalities (not criticizing that BTW) but on the presentation.
@robertdalga1284 жыл бұрын
Thanks for the vid! A couple of comments for others watching and reading. It doesnt matter which hot wire goes to either of the two lugs on either side of the neutral lug for the two 120 volt 'hot' service entrance conductors. Also, grounding (bare copper) wires can be directly attached to the neutral bars (No need for separate ground bars) if the service goes directly back to the meter (grounds only need to be separated from the neutrals for auxiliary panels). Lastly, the 'goop' he put on is an anti-oxidant so the aluminium wires do not corrode.
@ozzypozo2 жыл бұрын
Exactly. I don't understand why he does not clarify that
@vipelectric10 Жыл бұрын
Wrong, grounds do need to be separated bc it's a sub-panel..
@TammieFulmer Жыл бұрын
I am pretty sure he said the main wires go back to the meter, so if that is true, the panel he is working on is the main, so that means his ground and neutral should be bonded together unless his meter can also has breakers. So after this main panel if he was to add another panel somewhere else in the home that would be a sub panel witch the ground and neutral should be separate. He should also have plastic covers over the two hot legs terminal and its a great idea to keep neutrals separate and you can double tap your grounds if the wire is the same size if your inspector agrees with that but absolutely a very neat panel and excellent keeping the wires labeled.
@midnightrider715910 ай бұрын
@@vipelectric10 When did he say its a subpanel? I heard the sec was straight from meter with no other service disconnect mentioned.
@AmericanOne96217 күн бұрын
@@TammieFulmer A little late for me to be responding but you are 100% correct and win the golden egg, if I could remember where I put it..... It's a old age thing I recon....
@8__mi7 жыл бұрын
Finished product smells of pride in workmanship... great video and great job.
@scarecrow27jf5 жыл бұрын
I've seen you put 2 neutrals under one set screw. I've always understood that to be a no no. You did clean panel work
@PedroGarcia-zf8zg3 жыл бұрын
He most likely will fail inspection my teacher gave us this video as a exam to see what he do wrong.
@insignia25433 жыл бұрын
I bet you he didn’t fail, as an electrician I have seen much worse pass and be overlooked
@MrJohnpro715 күн бұрын
I love your explanation and neat work! That said however, I would add two things: (1)The lugs on the main lug and main breaker load centers will use a 3/8" Allen (hex head) wrench and should be torqued to 250 lb-in using a torque wrench. (2)Never put two white neutral wires under one lug or you will fail inspection in our state.
@carylamari654610 жыл бұрын
Ryndon, First of all I want to say nice job, I am a Master Electrician and have been for 35 years. Overall I think you did a nice job clean, defined and secure. I just would like to clearify a couple things we do in Maryland and of course people should realize the National Electrical Code are minumum requirements. The Load Center you installed is what is termed a sub panel that is why you have Isolated the ground from the Neutral and you installed 4 conductor feeder cable. People should know in an installation such as yours the main service is located near the Electric meter and feeds this panel also if it were a Main Panel there would have to be a Identified Green Bond Connection either a green screw or a Green tie connecting the Ground Bar to the Neutral Bar. If it were the main panel you would have used a 3 conductor Service Entrance Cable and you would have to have the panel terminate immediatly upon entrance to the house in Montgomery County Md the accepted code is within 5 feet. Also We are not allowed to intall a Main Panel on a interior wall unless it is Isolated with fire rated drywall. As I said you did a fine job I just wanted to throw my two cents so people realize there are differences where in the Country you do the work and whether you are installing a main panel or a Sub Panel. Thank you for helping people understand what a Load Center Installation entails.
@allaboutworld76715 жыл бұрын
kzbin.info/www/bejne/amHIi36fo89-ptk
@headbanger45465 жыл бұрын
hi Cary, i have a question if i may, whats the longevity of the instalation? the cable last for 10 20? years? what happens if you have to rewire the house? thnx. best regards
@peterclewis49785 жыл бұрын
I agree with you; this video was very well made and thank you for your relevant and experienced commentary.
@shockingguy5 жыл бұрын
Head Banger The basic service life of your wiring is the life of the property. But in general 50 to 100 years
@Oaxmex3465 жыл бұрын
Cary Lamari i got a question, why some times I see ground wire with neutral wire together is that bad? Or is no big deal
@alltakennow6 жыл бұрын
Why do experts watch tutorials? Awesome job. Nice and neat. Thanks. It was a big help.
@vrea775 жыл бұрын
I agree, maybe there not certain themselves
@muncieZ3105 жыл бұрын
experts, critics...theyr usually the same ppl....*chukl*
@TunafishSmoothie5 жыл бұрын
I can always learn new things and techniques, and in return, I may be able to pass my knowledge and experience on to others. That is why.
@danieldoster89105 жыл бұрын
Really, complain that old pros like myself can't sit in a Waffle House and eat an omelette and watch a video? I had to look at the date it posted as things have changed in subsequent years. Not to bust him but to see if there was an idea or two he might have that I could use. Use your brain every day and it might not get too fuzzy in your later years.
@TheExcellentLaborer5 жыл бұрын
Square D makes a nice panel. I just installed the Homeline version with the plug on neutral. Talk about a time saver! Great video!
@ahsanawan45038 жыл бұрын
I passed the 3 year diploma in Electrical Technology and now I learning practical work. very nice
@Virgil2U9 жыл бұрын
Finally a good intelligent young good American man who knows exactly how to wire a breaker box and shows it in a very intelligent manner and explains everything without wasting a person's time talking about hearts and fingers and holes. If I had the money I would send this young man $100,000 for Christmas for helping so many people.
@researchcapt4 жыл бұрын
Very neat job. I wish I could have seen the entire installation. For the others commenting on it, aluminum does expand when it oxidizes.
@science-10149 жыл бұрын
Just a foot note, at 1:34 you talk about "noalox" for the aluminum wire to prevent expanding & contracting. It actually has nothing to do with that. it literally means, No Al Ox, which is No Aluminum Oxide will be formed, it prevents oxidation on the aluminum wire which will inhibit conductivity down the road. Great video though thank you!
@broken19659 жыл бұрын
yep
@HBSuccess8 жыл бұрын
+Science-101 Hey didn't I already say that ? :-)
@tommulvehill78348 жыл бұрын
hack and this video is pointless
@dougankrum33288 жыл бұрын
...You're right.....AND...out here in California....no aluminum in residential anyway.... Aluminum wire shouldn't expand/contract anyway unless it's overloaded...? I've worked as Commercial Elec/maint....seen a good deal of aluminum in newer buildings....seldom seen it get anywhere near warm.....as long as it's not overloaded
@fordman30748 жыл бұрын
how to rewire a house
@martincorona22795 жыл бұрын
I like this guy he's a real deal he goes straight to the business not like some other guys that mess around too much you know thanks man I really appreciate your work
@Lakota41210 жыл бұрын
Nice video, good job on that panel. Nice to work with quality panels like Sq D. Also nice to see someone who loves what he does so much he'll make a video of his work. This is when work becomes fun, and isn't work anymore. Electricians Rule!
@jsal9999998 жыл бұрын
This was not only interesting, but as a camera geek, I appreciate the good lighting, clear video with camera mounted on a solid tripod or platform. Let's dump hand-held phones in portrait mode, lit by a flash light, shot in 360. :-)
@nitramretep7 жыл бұрын
This is a good video for those trying to understand wiring a panel. Well presented and clearly explained!
@Reean084 жыл бұрын
Except he brought home runs through the service entrance
@mubarakkhan5375 жыл бұрын
I learn from watching videos and also take notes from the comments. For me this is a useful video. Thanks for sharing.
@dortot16 жыл бұрын
I think it is worth mentioning that the panel has separate grounding bars because it is treated as a sub panel due to it being an extended service. Don't forget kickplates when the homeruns come closer than 1 1/4" to the face of the stud they are passing through.
@mrnade3332 жыл бұрын
was wondering where the bonding screw was!
@ozzypozo2 жыл бұрын
Good observation. That is what I was wondering.
@33electric33 Жыл бұрын
Nice panel job! Aluminum is nice to use for service entrance to save a bit of cost on the job. Aluminum does expand and contract more because it is a lighter metal than copper. The reason to use noalox is because it's an anti oxidant. Aluminum exposed to air and environment will form a hard coating of oxidation over time which makes it non conductive. Basically it becomes corroded and can lose connection. So the noalox is like a barrier to that. I have seen many of aluminum neutral conductors become oxidized, (when its in damp location) lose connection at main lug and cause voltages to spike through the electrical branch circuits and burn up equipment in the house because the electrician failed to apply the noalox. So, the aluminum is still going to expand and contract even when you apply noalox, but it will protect the aluminum from forming the oxidation layer which will cause connection to be inhibited at terminal point. If you read the instructions on bottle of using noalox you will see it says to first use a wire brush on the conductor end before applying the noalox and landing it at connection which almost nobody does. You were basically right but wanted to share what I have learned over the years.
@robertmattison12829 жыл бұрын
WOW! 416 comments and mine makes 317. Thank you for making this video and posting on youtube. Please post more video's . Every one that see your video and then read all the posted comments below, will come away with something they didn't know. Great work done in making this video.
@randomstuff63413 жыл бұрын
wait what
@Katshands8 жыл бұрын
Idk anything about this stuff, but this was so satisfying to watch. I'll make sure I show my husband this when he does our home soon! Thank you..very informative
@stephenc54438 жыл бұрын
did a very nice job on installation. 1 screw one neutral is code.
@neonc2c28 жыл бұрын
That what I was going the ask. One wire pre lug. One hole and screw can't have two wires in it.
@allinbeam8177 жыл бұрын
Yeah thats what i was wondering what he was doing too. Can only do that with grounds.
@bennybonez9 жыл бұрын
He's just happy cause he's doing a new OPEN rough in! THATS A VACATION!
@jameshollen97233 жыл бұрын
open is always easier ! NOTHING HOT !
@black83shadow9 жыл бұрын
I did in fact learn more in my first day as a apprentice than what I just seen. If I inspected this you or someone would be doing that panel again the right way. I would list your mistakes but if you read the comments you will find most of them lol.
@DaniilStanisevschi4 жыл бұрын
Clean work, very nicely organized panel. One thing though: landing more than one neutral under a screw is a huge no-no. That should never be done.
@dneitzke5 жыл бұрын
Excellent vid., I have been a commercial HVAC tech for 30 years now, If you could have seen MOST of all the single and 3 phase panels that I have had to deal with you would scratch all of your hair off in just plain wonderment!. And many of these nightmare (Death waiting to happen) installs and sub additions are done by Lic. electricians. You wire very neatly and very correct, Come to Omaha,NE, and I will hire you before you get here.
@skymiller5307 жыл бұрын
This is the first of your videos I have seen (if you actually have more, haven't checked). Compared to others' videos on KZbin, this was the best so far. Looking forward to seeing more from you. One thing though, the Noalox is an anti-oxident that hinders corrosion on aluminum conductors.
@rickpearce4653 Жыл бұрын
It’s a pleasure to watch a Professional. Thank you for the video.
@sparkydave5 жыл бұрын
Nice job mate, looks a tad different from our wiring in New Zealand!
@nbultman_art8 жыл бұрын
7:00 Im curious as to why the ground wires are not insulated, while all the other wires are?
@acwrobel18 жыл бұрын
Well done, man. Good job. This isn't perfect, but it's far from disappointing. This is probably one of the best and most concise vids on YT about Main Panel installation. Not sure whether you WARNED people that your service wires were not connected yet. Those hot wires can and will kill you.
@doomaster48 жыл бұрын
He did say lines were not connected in the beginning.
@wyliesdiesels41698 жыл бұрын
This is a subpanel as evidenced by the 4 wire SER...
@rayford218 жыл бұрын
If you have to do anything else in the main panel besides installing new or replacing circuit breakers (NOT the main c.b.) make sure the meter is disconnected, even if there's a disconnect before the panel...don't trust your life to a switch that might have a blade still connected when you think the switch is off.
@rayford218 жыл бұрын
Diesel Boy, Which means he's violating code with more than one neutral wire connected to a neutral bus block terminal connection..
@jianfeilu76278 жыл бұрын
rayford21 hi
@victorteran48794 жыл бұрын
Is very interesting how in USA make the electrical wire panel is so different here in Latin America I'm electrician with more than 30 years of experience But never seem before how work the electrician there in USA Thank you for your videos I hope so that you can to still sending videos because they are very interesting
@rrfields659 жыл бұрын
The one thing that you should also do is "Load Calculation Landing" of the HOT conductors{ 240vac/220vac DPST breakers @ the very bottom - so that you will have alot of bar as HeatSink for A 120vac [ Blk.] & B 120vac [ Red ] phases. Also separate the Constant duty from Intermediate duty SPST breakers & divide as much of the LOAD between A & B{ I"ve seen older home Mains burn up one or the other phase contacts -because of none Balance}.
@bigchrisable1 Жыл бұрын
Excellent 👍
@antoniopierce32596 жыл бұрын
Wow that brought back memories. He did a great job. Very good presentation. Thank you, for showing me a different way of setting ground. Keeping them separate! Great idea
@piqua7938 жыл бұрын
Nice looking install. Two questions though, what are those connectors you're using to run the Romex through the panel and why did you double tap your ground and neutrals when you had the space to single tap them?
@Esspppiia2 жыл бұрын
Double tap: He doesn't know any better.
@BearStar12 жыл бұрын
Code only allows the equipment Ground Conductors to be double tapped , but NEVER a Neutral Conductor !!!!
@decaalv7 жыл бұрын
hi greetings from Costa Rica. I just realized that the yellow wire in itself is the conduit. interesting. beautiful work.
@kirklandelectricicnc10 жыл бұрын
I like you video Ryndon, you seem very enthusiastic and energetic, the kind of guy I would hire. If I may say, most electricians will pick apart a video of other electrician because they may think they know a lot. If you don't want to be one of those guys that gets knocked around by those know it all's, take a little time to learn a bit about wiring a panel board, or any thing for that matter. Understand what a service grounding conductor is used for and why the neutral and grounds are separated in a sub panel. Use the right terminology when referring to the ground terminals verses ground rods. Grounding conductors are not typically used for current caring conductors. There is some truth in most of the comments below, but don't take it too hard, there just trying to help. I noticed your panel was flush with the wall stud, I would set it out to the thickness of the wallboard you plan on installing, this will save you looking for longer screws to mount the cover panel. One last thing, double wiring grounds and neutrals is fronded upon, specially with the neutrals my friend. Stay Safe!!
@gregl224910 жыл бұрын
Why don't u make a video to explain how to do everything correctly----or is there a diff videio u can recommend? im going to wire my own garage thx
@kirklandelectricicnc10 жыл бұрын
Greg, as much as I would like too, the logistics alone would be more than I could handle, like video taping. Not to take away from Ryndon video, he actually did a pretty good job, it's to bad his video didn't show other aspects, like roping and make-up. If I may suggest-getting a self help book and study it. You may be able to find them on-line. If your able to video your project, by all means post them and I would be glad to help you in any way. Best to you.
@mrrickray7 жыл бұрын
look closely, his panel looks proud of the studs by a 1/2". great video. where I live you can only use EMT.
@nooneanybodyknows13216 жыл бұрын
You're one of the nicest professional comments; offering honest well thought out reasoning to assist not tear down. I admire this about you sir; sign of a true journeyman.
@KitchenerLeslie26 жыл бұрын
Richard Thoma Illinois?
@jimj69169 жыл бұрын
Great video.....learned a lot but I rather hire a master electrician to redo my box than try doing it myself. Great job on the box, wish you were close so I could hire you to do my box in my condo. I have witness some bad wiring jobs in a couple of states, I am so glad there is professional people like you who know how to do a great job ! Tks again....
@ednorton57399 жыл бұрын
You must the brother in law.
@slpss20027 жыл бұрын
Nice job. Who doesn't have a few flaws? I'm not perfect. Your video shows people curious about electrical panels a good overview. I've seen some electrical veterans who wire up rats nest in their panels. I like people who take pride in their work.
@fnhwk6 жыл бұрын
Thank you for finally putting that out there. Everyone in the comments acts like a master electrician who has never made a mistake.
@pxndxlunx58216 жыл бұрын
@@fnhwk lol everyone does that from time to time especially on the internet. I know, Im a Cardiothoracic and Neurosurgeon 😁
@erictold8 жыл бұрын
99% Perfect video. 1% is double neural wires in a hole, which becomes a safety hazard when testing or repairing the circuit in future. NO multiple neural(white) wires in a hole(X). YES multiple ground(bare copper) wires in a hole(O).
@k.m.parekh46978 жыл бұрын
Thank you so much for the video really informative. So essentially the two single phase hot wires need to be secured along with your neutral and ground. Are the neutral and ground connected?
@Goni9833 жыл бұрын
The only clear and concise video Ive seen on this, thank you!
@jimharrydariusjr.whitesell40268 жыл бұрын
check the video 7min 38 sec. The national Electrical states only one conductor is permitted for each lug or termination point. You can't double up landing your wires. Other than that its a text book installation. Good job
@maynardr68 жыл бұрын
NEC 408.21 "Exception: Grounded conductors of circuits with parallel conductors shall be permitted to terminate in a single terminal if the terminal is identified for connection of more than one conductor."
@augustgunderson80858 жыл бұрын
NEC 408.41 is an exception for "parallel conductors" as when you pull feeders in parallel to ease cost and difficulty pulling due to wire size (imagine pulling two 3/0 as the neutral (or "grounded") conductor for a 500 amp feeder). Needless to say, that implies the same circuit which means you placing neutrals from separate circuits under the same terminal is a plain violation of 408.41. Grounding electrodes (grounds) can be terminated under the same lug if rated. Guess you got some lax inspectors out there.
@jimharrydariusjr.whitesell40268 жыл бұрын
I have seen double lug terminal blocks. That may be what NEC 408 is referring to allowing multiple conductor termination.
@SHAKA-NEU-LU7 жыл бұрын
Jim , Harry Darius Jr. Whitesell double lug is different from terminating to conductors under the same lug
@joshuadevall41827 жыл бұрын
Also missing bushing on his 2" Romex connector holding his SEC
@bcn19708 жыл бұрын
Felicidades es grato ver a otro profesional trabajar tan bien, vuestras instalaciones son diferentes a las nuestra en España, te mandaré fotos para que las veas. Un saludo y de nuevo felicidades.
@donaldhester99529 жыл бұрын
You cannot land two neutrals (grounded conductors) under one lug, this violates the manufacturers spec and now is in violation the 2014 NEC.
@BigBear217409 жыл бұрын
Thank you. Thought I was going crazy.
@donaldhester99529 жыл бұрын
***** I goofed a bit even though what I said is correct. Since 2002 the NEC (Section 408.21) has not allowed 2 under a lug, it still was a violation of the panel specs prior to that and in violation of 110.3(B).
@REMY45HST9 жыл бұрын
***** Me too
@smallieback41939 жыл бұрын
Donald Hester didn't know the 2014 code was in use already
@9FingerMonkey9 жыл бұрын
+Donald Hester I thought it was weird. I think he was being lazy. Since he got enough lugs for all ground wires.
@sacramentoelectricians64359 жыл бұрын
This is a great video concerning how to wire an electrical panel. Its so interesting also how we all have different codes and enforcements from different counties but are also supposedly 'governed' by the NEC. Great video ryndon! Thank you brother
@TimEllenburgPhoto10 жыл бұрын
Damn fine job sir. Don't let all these naysayers who probably own a 10-in-1, strippers, and a couple pairs of channel locks get you down. It's easy to do precision wire bends and make it "pretty" when you get paid by the hour. I've been doing this 25 years and I'd hire you in a minute!!! The only thing I see wrong is the double-lugging on the neutrals, ain't nuthing wrong with the rest!
@awickedtribe10 жыл бұрын
*****... while I agree with you that this is totally inadequate... and he doesn't seem sure of what he is doing, making statements as questions... I will add, as I stated before, what the manufacturer allows isn't acceptable in Commercial or Industrial applications by any Inspector... Residential Codes must be different... I don't remember as I only did Resi work in my first year as an apprentice...
@jamesmartin695810 жыл бұрын
***** Wrong jurisdiction, but most of our code is identical to the US, or behind. Canadian Code says neutrals must be terminated in such a manner that they can be disconnected without interfering with other neutrals [4-028(d)]. Therefore, double landing is prohibited. It's dangerous because while I'm removing one circuit's neutral, and incidentally break contact on the other neutral, and that other neutral is shared between 2 phases, then I have made a floating neutral situation, putting the loads in series across 240V. That can be colossal failure if those 2 circuits were imbalanced and supplied expensive equipment. Law trumps manufacturer. Law may sometimes state "as per manufacturer", but manufacturers always state "install in accordance with local laws".
@howardblasingame79616 жыл бұрын
@@briankwahl Agreed. Double lugging is acceptable if the wires are the same size & style.
@lazaryanya94076 жыл бұрын
You are not allowed to work on a live panel. So how will removing one neutral affect a dead circuit? @@jamesmartin6958
@jamesmartin69586 жыл бұрын
@@lazaryanya9407 We don't wire things to what people are 'supposed' to do.
@TSNEC4 жыл бұрын
There needs to be more craftsmen in the trades and not just people who claim they are. My panel looks like crap compared to this. Good job man keep up the good work.
@mharmon9669 жыл бұрын
I don't think that you're supposed to double tap neutrals..
@ShortArmStrongArm3 жыл бұрын
🧐
@ShortArmStrongArm3 жыл бұрын
🤔
@PedroGarcia-zf8zg3 жыл бұрын
@@ShortArmStrongArm yea you will fail inspection my teacher gave us this video for a exam and we had to find out what he did wrong and he double the neutrals. He had enough space but still double them.
@mattsabeast52 жыл бұрын
Okay princess can you tell me why it is an issue? In principle of building code and application of installation, or theoretical in load calculations? They land in the same bar over the same conductors, and many times you will be landing a 15 amp circuits neutral in a location that could accommodate a 100 amp sub panels neutral conductor...why not double up? I'm guessing your gonna have to email the guy that couldn't get a profitable job working in the trade (aka he's teaching you) for an answer 😉
@mattsabeast52 жыл бұрын
@@PedroGarcia-zf8zg talking to you bud
@diverpoa3 жыл бұрын
Nice work,clean and labeled panel,professional finish,👍🏻
@richardkaufman16438 жыл бұрын
I believe each neutral must be connected under its own terminal
@jsparlin15 жыл бұрын
it is code. and grounds also.
@PixelPlayground4735 жыл бұрын
I also believe this guy is professionaly trained
@1450JackCade5 жыл бұрын
@@jsparlin1grounds do not, actually.
@watherby295 жыл бұрын
What logical sense does this make?
@thomasmarable68184 жыл бұрын
@@fedfreds832 look at 110 3b then make your remark, because you don't know code
@twotfreigh49462 жыл бұрын
Best explanation on how to do this yet!
@MsamerieJohnson8 жыл бұрын
I love this video because he explains how to set up the electrical panel and wiring from scratch.
@ahsanawan45038 жыл бұрын
Amerie Johnson nice me also
@sohannetm8 жыл бұрын
The only time you can put neutral and ground wires in same bus bar is when panel is bonded. Normally in first means of disconnect. In older homes you will see tht a lot because you only have a 3 wire system . 2 hots and neutral. New homes now have 4 wire system. 2 hots neutral and ground. Or if you do an upgrade (4 wire system) inspector will look for neutral wires to be separate from ground wires. Which means you have to separate neutral wires and ground wires. hope this info helped.
@josephnorcalusa17105 жыл бұрын
Helpful information thank you for sharing !
@jonathanbodge21138 жыл бұрын
In CT on a main panel the neutral is connected to ground via the green screw through the neutral bus bar. Sub panel they are separated.
@jonathanbodge21138 жыл бұрын
As an unlicensed electric guy, I was asked to disconnect a hot tub for a billionaire (actually come to think of it I disconnected a sauna for Danny Devito in my youth) anyway, this billionaire had a 250 amp sub panel and I had to remove the wires from the breaker. Nice neat wiring.(Company proudly named on box) But as I inspected I noticed the neutral was never tightened at all. (Same house that had an electrical fire because the garage heater hooked up wrong). This is actually the second time I discovered this in a panel. A relative called me once and said his stereo blew up and other odd things in his brand new house. Again, an un-touched neutral lug.
@RudyNortz6 жыл бұрын
Someone could do a video of how to boil water and there would be 500 arguments on how it SHOULD be done. LOL
@xeanheart26145 жыл бұрын
Person 1: Ok first you turn on the burner and start warming the pot. Then put warm water in the pot only when the part is warm but not hot, don't want to wrap the pan. Then put the heat on high Person 2: No you fill the container with water first, then just put it straight on high heat. Person 3: instructions not clear, burnt my water and warped my pan
@whitechocolate31355 жыл бұрын
@@xeanheart2614 lmfaooo so true
@skyisthelimit32555 жыл бұрын
Step 2 doesn't seem right
@TheJourneyofAll5 жыл бұрын
That's electricians for you. Never met one who didn't think he knew everything
@varietyyachtsvessels67695 жыл бұрын
I totally disagree with you.
@MrElectricianTV9 жыл бұрын
Very neat job inside of the Square D load center.
@Okicombo11 жыл бұрын
12/3 on smoke alarms?
@Order-in-Chaos11 жыл бұрын
He said "3 wires" when talking about the smoke alarms' wire. He was simply explaining how to strip them. If you look carefully this is a 12/2 wire. Most municipalities require a 12gauge wire for smoke detectors. 12/2 to the first smoke detectors and 12/3 to the rest.
@6565Jimbo10 жыл бұрын
I know strange, but maybe the smokes are going far. next size wire. I believe they are thinking about the wire in the basement, crawl space & 1st floor when in a flood zone may have to be UF! Up goes the price. Dam Hurricanes.
@patrioticgunner80343 жыл бұрын
Ur work is neat but u missed 2 things: The neutral and earth should be bonded( meaning both the Neurals & earth wires should be on the same bars) cuz the panel has the first disconnect after the meter . There should only be one neutral wire per hole on the neutral bar,not 2 but u did a neat job. Square D makes great panels so good choice 👌
@mrromantimothy6 жыл бұрын
You have all the room on those neutral bars why are you doubling up your neutrals?
@timbucktoo66335 жыл бұрын
Yeah. Same with the ground wires. It's a new installation. No need to do that as there's plenty of termination screws. Having individual wires would make it safer to work on later.
@fedfreds8324 жыл бұрын
mrromantimothy why wouldn’t you?? Save room in the panel
@timbucktoo66334 жыл бұрын
@@fedfreds832 For safety reasons it's best to keep ALL terminations separate for future system maintenance. How's that for a reason? Need more room, get a bigger panel!
@fedfreds8324 жыл бұрын
Timbuck Too lmao for future doubling up neutrals will cause problems?? Sounds like something an apprentice would say😂😂if your gonna work on a lug with two different nuets then TURN BOTH BREAKERS OFF. It’s not fucking rocket science. Do you need help untwisting existing wires that were nutted together to Tim buck??
@fedfreds8324 жыл бұрын
Timbuck Too also if it’s the main then doubling whites and greens is perfectly legal considering a regular 200 amp Siemens panel
@adamwise17907 жыл бұрын
The panel looks good I like how you leave extra on the mains
@caseystetson92276 жыл бұрын
Nalox is an antioxidant to keep your aluminum from oxidizing
@landim86558 жыл бұрын
Nice job guy. It is a pleasure to see that. Very clean the way to connect the cables like this. From Brazil.
@johnalexanderchaneljoseph89475 жыл бұрын
You did a nice clean job but you should not double tap any conductors. One wire per lug or screw.
@KOSIARA6665 жыл бұрын
GREAT video and You explained everything PERFECTLY WELL !!! THANK YOU!
@alwayslearning36718 жыл бұрын
I like your wire labeling method, I'll use that on my next house.
@delmerb45106 жыл бұрын
When is it allowed to run load branch ccts thru the main line side and no barrier between line and load side? Commercial yes but then it’s usually a load centre not a panel with a main breaker. I follow CEC of course is that a NEC thing?
@badimp310 жыл бұрын
One other thought here is that you Might state what State you are working in ...and maybe even the city, these methods might change from State to State and city to city.
@nkel61114 жыл бұрын
Cleveland ohio had a rehab code...not as stringent as the current NEC manual. worked for me
@robertallon93875 жыл бұрын
do you have a follow up video showing how to put in those black turny offy things?
@JustAnOldMan7 жыл бұрын
OK everyone 1. he is a licenced electrician 2. his work has been, and in this case will BE INSPECTED 3. do you really think he would do something he is not permetted to do when he knows he WILL be inspected ?? 4. perhaps everything does not match your area's code, but once again he is an licenced electrician who's work has been, and will be inspected each time, so what ever he is doing IS up to code in his area. 5. Final note Norway STFU running all 240v curcuits is a whole diff. program 6. OH, who ever got paid off to requir Aluminum wire should be jailed, inferior metal! 7. OH Ya, nice video !!
@zerocool58787 жыл бұрын
Tom Chrissy if that isn't a subpanel he needs to bond the neutral to the box.
@cesarin159x6 жыл бұрын
I think the city electricity supplier provided the aluminum service cable, some counties and cities do this alot
@brianleeper57376 жыл бұрын
There is nothing wrong with aluminum wire. Majority of houses have aluminum between the transformer and the meter, and between the meter and the panelboard. Many have aluminum wire between the stove and the panelboard as well.
@robprocctvcameras87336 жыл бұрын
There arent many inspectors out there that actually know what there doing.
@adamelliott61126 жыл бұрын
zerocool5878 I it wasn't a sub-panel it wouldn't be fed with a 4-wire, and you can clearly see it's in an interior wall so it has to have a disconnect ahead of it somewhere-
@toyotalover16 жыл бұрын
Looks nice and clean , here in California we can not have 2 neutrals together, also all of our outlets and smoke/carbon now have to be ARC fault protected, also your main panel needs to be bonded which I believe you are unless you remove the flat head screw next to your neutral , only on this type of panel.
@Scott0272111 жыл бұрын
Missing a bushing on that 2" SE fitting?
@strayspark196711 жыл бұрын
yep, true
@josephcerello63136 жыл бұрын
Good job, not sure if your allowed to double up the neutrals in your area but I have never done that..also that is your main panel,I know your service entrance comes from street then down to your meter then you jumped over to your main panel,You need to bond the grounds and neutrals on your main panels..only on sub-panels you have to isolate the grounds and neutrals..but besides that good work..
@gregl224910 жыл бұрын
Thank you so much for this video----it seems to be the only one on u tube that takes on this task that seems so difficult for the do it yur selfer-----I don't understand why someone hasn't posted a similar video much sooner---I just assumed electricians didn't want others to learn for job security ---which is why I think u r getting negative comments Thanks again and pls make more of these ---u have my subscription
@FrannyWard10 жыл бұрын
Home Depot used to have a display of how to install a service.. Until non electricians began getting killed and the lawsuits started coming.
@telosfd10 жыл бұрын
***** 6.000$ to replace a main electric board!!!!!!!!!!!
@DefinitelyNotHaraku10 жыл бұрын
***** When I lived in cali(5-10 years ago) a 100 to 200 amp service upgrade was 4000-5000, now in arkansas area the same thing is 1000-1500(which will be going up starting next year when AR adopts 2014 code)
@dallas53747 жыл бұрын
Because people burn houses down when they try to do something over their head like this. Leave it to the professionals.
@atkgrl7 жыл бұрын
I bought a square D main panel 200 amp 30 slot box and have it installed, now running my wires. I am upgrading some of the lines since and breakers since there are no gfci or arc faults. I also upgraded the stove to a 50 amp and am installing the Home Depot 100 amp RV panel. I did not get a separate ground bar with my box and see you have installed 2 on opposite sides of the box with only one attached to the grounding wire now I'm questioning. On my old box the ground wire was attached to the neutral bar as was the neutral main line. I only have the green screw. So this is a main panel installation which I have always understood that white neutral lines and bare ground lines be on the neutral bar. Now also wondering how my new 50 amp stranded wire should go which definitely will not fit in the small neutral bar hole and I would normally use a large hole attachment to the neutral bar. Just trying to make sure it's correct before it's inspected.
@NemudusM10 жыл бұрын
Drill is the way to go save time and for ended money, and that drill he was using have a clutch, so how many of you are drilling holes on 2x4 with a manual drill ? Let the man use his drill to tie the screws who cares they got tie and he didn't strip any, video was great and high quality picture, you ain't a teacher why all you heaters want him to use terminology the only you guys can understand? Plain and simple is ok. I'm sure all the lights and outlets are going to work when you get done.
@johnsmith-sw7ii6 жыл бұрын
I see you live where 4 wire entrance is required. In my area there is 3 wire entrance and neutrals and grounds go to the same place and there is a bonding screw that grounds out the panel itself.
@linehandibew62055 жыл бұрын
john smith it’s a sub panel because it’s more than 5 feet from the meter base. Where I’m from 4 wire with bond is required over five ft from meter and the meter base to be installed should have a main breaker on it
@tikonovgrenadiers312210 жыл бұрын
I'm a licensed electrician you did a good job but the main reason you hire a electrician is for insurance if you have an electrical fire when the insurance company investigates the will want to know what electrical contractor you used. No electrical contractor no money. Now if the load calls are right he is all good. But I would never recommend using aluminum wire. But as far as the application good job.
@jimdandy86489 жыл бұрын
Tikonov Grenadiers Aluminum wire is used coming from the mast head.
@MrShockman109 жыл бұрын
Jim Dandy Thats because of cost plus your utility company knows how to work with it plus weight. Aluminum wire can cause fires if not properly installed.
@dave48549 жыл бұрын
Tikonov Grenadiers they can cancel; the ins., but they have to pay the owner,
@gravelydon70726 жыл бұрын
The Awgster, Please tell that to the local power company that AL wire isn't worth anything. It gets stolen all the time such that they now have their name impressed on the wire so that only the company can recycle it.
@johnbecich95407 жыл бұрын
My compliments to the well-spoken moderator and producers of this nice video on basics of modern service panel installation. Thanks for saving us from ponderous tutorial points by speeding up and editing appropriately. I would have appreciated some elaboration on the requirements of wiring for AFCI (arc fault circuit interruption) breakers; I'll have to dig elsewhere to answer questions in my mind, raised (at about 9:00) by the moderator.
@TheAmtrack695 жыл бұрын
Well done. Seen a lot of wired breaker panels, and most of them not nearly as neat as your, good job!
@clintonjeffs17 жыл бұрын
PS I have never seen a cutter for Romex like that and I love the labelling idea it allows you to do, I'll have to look for one of those.
@Design4Building8 жыл бұрын
As a habit, you should NEVER touch the bus bars or lugs. Even if you know its not hot. Its the same law as working with a gun. always consider the gun loaded. Practice the bus is always hot. Even when showing a video. This Practice Saves Lives
@markwillride8 жыл бұрын
Design4Building as a shooter, that sounds like a good idea to me. Habits can take you where you don't want to be.
@allinbeam8177 жыл бұрын
Well said sir i totally agree.
@Krishnakumar4372-g7l7 жыл бұрын
Design4Building
@666antichrist7 жыл бұрын
Always use your fluke as well.
@RFCarpenter7 жыл бұрын
Yes... Treat a panel like a gun...It's always HOT.... Like the shank of your screwdriver when doing electrical work... Don't touch It...
@danielponton35396 жыл бұрын
Wow! So many haters. What is so wrong with a guy making an informative video? The guy just showed a perfectly legal way of stripping in a panel in a house. Good job man! Also, I saw some people commenting on using the Aluminum. There's nothing wrong with using aluminum subfeeds. It's an excellent way to keep the cost affordable for the homeowner. What do you think all these powerlines are using? Same goes for hating on Homeline. Do you really think you are getting so much more value using QO?
@lonny33445 жыл бұрын
Maybe over kill but I would have put a plastic bushing on that service entrance cable. Good job M8.
@shamod07utube Жыл бұрын
Beautiful panel! I was looking at mine the other day thinking about adding a few circuits for the basement and nothing as nice as what you have there! For some reason I have neutrals and grounds on the same bar … hmmmm
@PaulphotoeyeVideo8 жыл бұрын
I am glad I am an electrician in the UK!
@villabellini298 жыл бұрын
Paulphotoeye Video . I'm glad I'm an electrician in South Africa. That horrible installation will never pass an inspection.
@PaulphotoeyeVideo8 жыл бұрын
Some of this makes me go cold. They seem to worry about all the wrong things!