Very helpful! Thanks for including the specific number ranges for good/bad solenoids and transmitters, etc!
@Hunter_Landscape_Irrigation8 ай бұрын
Glad it was helpful!
@desert_chronicles_EUC2 ай бұрын
Very helpful! My sprinkler heads are all popping up and down with the continuous clicking of the solenoids. I'm going to have to do some troubleshooting using your information! Thank you.
@brianridesbikes41172 ай бұрын
Same problem, please let me know if you already figured it out :)
@Hunter_Landscape_Irrigation2 ай бұрын
This 100% sounds like a good reason to contact our customer support department: www.hunterindustries.com/hunter-technical-support-email-request
@Hunter_Landscape_Irrigation2 ай бұрын
Please contact our customer support department here: www.hunterindustries.com/hunter-technical-support-email-request
@dmetal12215 ай бұрын
Priceless info
@sebaxh2210 ай бұрын
Great video!!! Thank you for posting!!
@Hunter_Landscape_Irrigation8 ай бұрын
Glad you enjoyed it!
@V3VoVo3 ай бұрын
Great and very useful
@farzingharahgozloo7 ай бұрын
Helps a lot 🙏🌹
@Hunter_Landscape_Irrigation7 ай бұрын
Glad to hear that
@wstt411 ай бұрын
If I want to test two extra loose irrigation wires for continuity so I can add new zones on them, and I connect these loose wires at a solenoid, and then with my multimeter I touch both same colored ends at the base control box, and I get a reading of 1.0 Ω, is that a good enough result?
@AlejandroAste-Nieto9 ай бұрын
So you created a loop with those wires? You tied them together at one end and tested resistance at the other? Then 1 ohm is a good thing. Your wires have good continuity. Smaller wire gauges will have more resistance the further you go. 18 AWG: 6.5 Ohm / 1,000 ft (multiplied by 2 for the wire to and from the end). So if you have 1 ohm on 18 AWG, that suggests you were 35-40 feet from one end to the other (70-80 feet of wire in a loop).
@truongvo19784 ай бұрын
I have a Hunter 8 zone. I have a P ERR error. Error comes on every station. Doesn’t mattter what station I turn on manually. The error comes up right away. I tested all 8 station for continuity. Station 1, reads 50 ohms and stations 2-8 reads about 26.5 ohms. Is station 1 solenoid bad?
@Hunter_Landscape_Irrigation4 ай бұрын
Please contact our customer support department here: www.hunterindustries.com/hunter-technical-support-email-request
@Son_of_Aragorn8 ай бұрын
Is 16 AWG "marine wire" good for sprinklers? Wasn't sure if all 16 AWG wire are created equal. Thank you!
@Hunter_Landscape_Irrigation7 ай бұрын
Wire can vary with region and wire length. A local contractor or irrigation distributor can clarify.
@shoyrushoyru6 ай бұрын
I have a zone that has recently been causing awful water hammer noises when the sprinkler runs. I tested the AC voltage on the zone while running and it starts 26.2V but then immediately drops to 0V and quickly goes back to 26.2V every couple seconds. Does that sound like a station module issue? The transformer is giving a solid 27 volts. Edit: I replaced the station module and I believe the problem is solved.
@Hunter_Landscape_Irrigation5 ай бұрын
Water hammer is a hydraulic or water issue and is independent of electrical issues. It may be time to contact a local irrigation professional for help with your problem.