Awesome had to have a quick refresher just to make sure my diagnostic was correct. Thanks for the video!
@johnjennings-JJ2 жыл бұрын
Not much too it but to do it! Thanks to you sir. Been a minute since I have seen an 0311.
@Woozy-pt9js2 жыл бұрын
@@johnjennings-JJ I know a few 0311s working the hvac trade. Not sure why this job field attracts us. Maybe it's the long work days with little sleep mixed in with low crawling and uncomfortable spaces 🤣.
@simmonsjr253 жыл бұрын
Another awesome video. Keep them coming.
@johnjennings-JJ3 жыл бұрын
I hope you remember how to do this!
@simmonsjr253 жыл бұрын
@@johnjennings-JJ yes indeed I remember.
@johnjennings-JJ3 жыл бұрын
Too easy.
@Pubstomper2310 ай бұрын
I needed that . To understand how to ohm out a comprossor
@soloch692 жыл бұрын
Great video like always my friend keep them coming 🙌🏻🙌🏻🙌🏻🙌🏻
@johnjennings-JJ2 жыл бұрын
Thanks SOLO TECH.
@Rhenexful2 жыл бұрын
Very detail... thank you for sharing
@johnjennings-JJ2 жыл бұрын
Thanks.
@josephspitzley90095 ай бұрын
I had one the other day that was shorted to ground on me. And another tech came out and swapped the capacitor and it worked fine.
@johnjennings-JJ5 ай бұрын
And you checked it at the actual terminals on the compressor? Or from the contactor?
@josephspitzley90095 ай бұрын
@@johnjennings-JJ I did all three terminals and all three wires. Got a reading on all 6 never a OL.
@johnnygallardo769 ай бұрын
You didn't specify if it was bad or good when checking it for resistance what number should it display if it's good or bad and in what way?
3 жыл бұрын
Scroll compressors will have 20 olms to ground but the motor is fine. The windings actually sit in the refrigerant to be cooled.
@johnjennings-JJ3 жыл бұрын
Thanks for leaving a comment. There is a lot of info out there such as that. I hope that techs would search out the specs on all the motors they come across in the field before assuming it is bad.
@joehead12943 жыл бұрын
@@johnjennings-JJ AE4-1294 Emerson/Copeland bulletin says not to meg a scroll but if you do the min is 500,000 ohm winding to ground. 😵💫
@johnjennings-JJ3 жыл бұрын
I hadn't seen that bulletin. I will check it out. Thanks for sharing.
@JuanSanchez-nn1db2 жыл бұрын
Adding the Run and Start should equal the C reading right?
@johnjennings-JJ2 жыл бұрын
The common is just the terminal labeled on a PSC compressor motor. The testing of run to start gives you the added resistance of both windings. Run winding is from R to C, start winding is from S to C. There is no common winding. It is "Common" because that is where the run and start winding both meet "the other side of power".
@Rod2646 ай бұрын
I have ohm out my compressor and my number where high will that indicate I have a bad compressor?my number don't match from R to S.
@johnjennings-JJ6 ай бұрын
The numbers might not match exactly but should be fairly close but higher resistance values could be indicating a problem with the compressor motor. But I honestly don't get wrapped up too much because I don't know what the values should be exactly until I look the up from the manufacturer. Then you can see exactly what they have designed and if your numbers are truly higher.
@kastenusa2 жыл бұрын
My compressor pulls 110 amp at the start, LRA states 118amps. 5 ton unit. How much life left on my compressor? Thank you!
@johnjennings-JJ2 жыл бұрын
Tough one. Sounds like it is within specs! But I have had them go bad while I was at the unit too. Let it run until it doesn't is what I would say. If you want a good read, google this - Trane Snowball or Snowball 2. compressor.
@kastenusa2 жыл бұрын
@@johnjennings-JJ I will. Thank you!
@simmonsjr253 жыл бұрын
Thank you. You have let the secret out of the bag. Thanks for sharing 👍
@johnjennings-JJ3 жыл бұрын
You bet! We got a lot more stuff to cover though.
@rickdeckard1075 Жыл бұрын
shorts can be intermittent though, depending on applied current/voltage or vibration...
@johnjennings-JJ Жыл бұрын
You are right sir, and I especially hate intermittent low voltage shorts.
@jollyscaria1922 Жыл бұрын
Vrey vrey good shering gues welcom my best gues all thankes for me all shering gues
@rafaelandreano2 жыл бұрын
What happens if the resistance values are extremely high, I’m assuming is a bad compressor but what could cause to have such a high resistance ?
@johnjennings-JJ2 жыл бұрын
Well...too much resistance for "X" amount of voltage in general will not allow the thing to run. But I (personally) have never had a compressor with an extremely high winding resistance. Not saying it can't happen but I just haven't seen it. Best practice is to get the manufacturers specs I guess and compare it to the actual readings. Example I have seen is a tech put a 480v rated relay coil in a 24v system...just didn't pay attention to the relay they grabbed...and nothing worked. They check voltage to the coil and it is there, just the relay isn't working. They had a relay with more resistance than the voltage could overcome and energize the coil.
@mdtabul40433 жыл бұрын
Nice
@johnjennings-JJ3 жыл бұрын
Thanks
@lynnprince66357 ай бұрын
Wow, really you left out the reson for the video. 1.7 and 1.4 should equal close to the 2.9.😮
@johnjennings-JJ7 ай бұрын
That it should... but I have really never seen them add up perfectly. The whole resistance checks and ohms law works good with DC circuits and purely resistive circuits though.