HVAC: LG MULTI V Refrigerant & Oil Acid Testing (Nu-Calgon Oil Test Kit/Qwik Check 2-Second QT2000)

  Рет қаралды 6,014

Jumper man Tech

Jumper man Tech

Жыл бұрын

HVAC: LG MULTI V Refrigerant & Oil Acid Testing (Nu-Calgon Oil Test Kit/Qwik Check 2-Second QT2000) #jumpermantech #hvac
QwikCheck Acid Test Kit (2 Second Acid Test):
Detects inorganic acid in 2-seconds down to 1 part per million in HVAC/R systems. Fast, accurate, and easy to use, QwikCheck provides an early warning of acid problems. The Yellow to Red color change allows you to easily and clearly communicate the need for action to the equipment owner. Works with all refrigerants and oils. Meets EPA venting regulations. For use, simply insert the valve core depressor into the center of the suction-side, vapor-service/Schrader valve while system is operating.
The concentrate of acid in refrigeration oil is expressed as an acid number in mg of KOH per gram of oil (milligrams of potassium hydroxide per gram of oil). The acid number is a measure of the amount of hydroxide solution needed to neutralize the acid in the oil. The more acid there is in the oil, the more potassium hydroxide is needed to neutralize it and, so, the higher the acid number.
Nu-Calgon Phase III Acid Test Kit:
In the Phase III test, an acid number of 0.05 mg KOH per gram of oil has been set as the maximum acceptable acid concentration in mineral oil and alkylbenzene oil. In polyol esters, the number is generally accepted as 0.16 mg. Mineral and alkylbenzene oils with an acid number less than 0.05 mg or POE’s with an acid number less than 0.16 mg are acceptable and will cause no change in the color of the test kit’s acid indicator. However, if the respective oils have an acid number greater than these limits, it will cause the acid indicator to change from purple to pink or clear indicating that the oil is contaminated.
GoPro HERO8 Black (Camera Used In This Video)
amzn.to/3q4FmEz
Veto Pro Pac TECH MC
amzn.to/3gURJyZ
Fluke 902 FC HVAC True-RMS Clamp Meter
amzn.to/39wvwiK​​
Fieldpiece ADK7 Deluxe Silicone Test Lead Kit
amzn.to/3VNYXDv
Klein Tools ET600 Megohmmeter Insulation Tester
amzn.to/409iNvu
Supco M500 Insulation Tester/Electronic Megohmmeter
amzn.to/42oy0ua
Fluke 1AC-A1-II VoltAlert Non-Contact Voltage Tester
amzn.to/3FcWElQ
Fieldpiece JL3KR4 HVACR Charge Kit (Digital Gauges/Probes)
amzn.to/3E4W0Fr
Fieldpiece SPK2 Folding Pocket In-Duct Thermometer
amzn.to/3mi8Fih
Fieldpiece SPK3 Folding ROD Dual Temperature Thermometer
amzn.to/3FbDufQ
Milwaukee M12 2-Tool Combo Kit 2598-22
amzn.to/3CtCRNC
Milwaukee Cut 1 Dipped GLOVES L
amzn.to/3s8H18O​
Milwaukee 2351-20 M12 LED Stick Light
amzn.to/3rVJKEK
Milwaukee 48-22-1985 Fastback Hawk Bill Folding Knife
amzn.to/3e53ygW
Milwaukee 48-22-1500 Fastback Compact Folding Utility Knife
amzn.to/3qazJkC
Milwaukee 48-22-4041 Iron Carbide Core Large-Looped Jobsite Scissors
amzn.to/32fxC6I
Milwaukee 4932459097 Billet Torpedo Level
amzn.to/30Dh6Nw
Milwaukee Wide Blade Magnetic Tape Measure 16 FT
amzn.to/3yEN7kL
Milwaukee Fine Pt. Markers Black
amzn.to/3e4fH5W
Streamlight 66604 MicroStream USB 250-Lumen Rechargable Pocket Flashlight
amzn.to/320XiEF
Klein Tools 11-in-1 Screwdriver / Nut Driver
amzn.to/3s3o8ql
Klein Tools 32561 Multi-Bit Screwdriver / Nut Driver 6-in-1
amzn.to/3e4ur4x
Klein Tools 32807MAG 7-in-1 Nut Driver, Magnetic Driver
amzn.to/321n4bW
Klein Tools 600-4 1/4-Inch Keystone Cushion-Grip Screwdriver
amzn.to/3J11hS1
Klein Tools 32581 4-in-1 Electronics Screwdriver Set
amzn.to/3yEj3WC
Klein Tools LLK12 L-Style Hex Key Caddy Set 12-Piece (Metric/Sae)
amzn.to/3yRUiGJ
Yellow Jacket 18975 Charge Tool
amzn.to/3J4pfvJ
Yellow Jacket 60613 Service ratchet Wrench
amzn.to/3E8iYeZ
Yellow Jacket 19173 5/16" Female Quick Couplers x 1/4" Male Flare
amzn.to/3q0TQ4M
Cooper Bussmann BP-FP-2 Cartridge Carded Fuse Puller
amzn.to/3e0USrY
Crescent 2 Pc. X6 4-in-1 Black Oxide Spline Ratcheting SAE Wrench Set
amzn.to/3qqKlw7
Crescent 4" Adjustable Cushion Grip Wrench
amzn.to/3J4qsmL
Knipex 09 08 240 SBA 9.5-Inch Insulated Ultra-High Leverage Lineman's Pliers (1000v)
amzn.to/30EQmw5
Knipex 09 11 240 9.5-Inch Ultra-High Leverage Lineman's Pliers with Fish Tape Puller and Crimper
amzn.to/3H9iYAu
KNIPEX Tools - Long Nose Pliers With Cutter, 1000V Insulated
amzn.to/3e3IEi7
KNIPEX Tools - Long Nose Pliers With Cutter
amzn.to/3gUSE2i
KNIPEX Tools 98 62 02, Flat Nose Plastic Pliers 1000V Insulated
amzn.to/3p6lFsZ
KNIPEX - 74 08 200 - High Leverage Diagonal Cutters, 1000V Insulated
amzn.to/3mh8K5U
KNIPEX - 74 01 200 Tools - High Leverage Diagonal Cutters
amzn.to/3F1VScb
KNIPEX Tools - Cobra QuickSet Pump Pliers, 1000V Insulated
amzn.to/3sftr5Q
KNIPEX Tools 3 Piece Cobra Pliers Set
amzn.to/3FbRwy7
KNIPEX Tools Pliers Wrench 3-Piece Set
amzn.to/3nnRLfW

Пікірлер: 60
@user-io5zo3to7r
@user-io5zo3to7r 5 ай бұрын
Hey Jumper man, I love watching your videos. I'm an LG startup tech and would like to share some info with you. Just so you know LG VRF systems can operate, on the low side, down to a low pressure of 43psi if outdoor temps are close to 5° F. Those low pressures can be normal IF other parameters are met. Like; High pressure trace in line with its high pressure target ,inverter discharge temperature in range, EEV's indoor and outdoor are in normal range (with good airflow across coils), compressors and fans operating in their range. I would advise getting an LGMV wifi module and download the free software from LG onto your laptop, that way you could see other things like oil sensors and thermistor info. Also, you can directly control ALL the IDU's, from your laptop, connected to the ODU on the roof. Let me know if you would like more info. I could send you a parameters chart. Thanks
@HVAC544
@HVAC544 Жыл бұрын
Looks like you finally found out why they are failing. VRF can be rather hard to determine issues as they can be multi layered. Going back and trying to figure out if they were installed and commissioned right is very time consuming. I have experience with the Gen 5 LG VRF's we have a few problem sites my company installed. We kept losing compressors and no one could figure it out. Turns out airflow was never set on the ducted airhandlers and they specced high static units with large spiral duct. The additional charge for lineset lengths may not also be correct too. Our compressors were being nuked in heating these things really run hard and hot in heating mode. Those indoor units look terrible and no doubt causing issues with the compressors. I wish people would install the outdoor up on a platform like that around here and do all the piping out the bottom. They always pipe out the front and it makes it annoying to get the compressors out.
@thesilentonevictor
@thesilentonevictor Жыл бұрын
This building keeps on giving 😂jmt professional work
@JumpermanTech
@JumpermanTech Жыл бұрын
The gift that keeps on giving 😂 Thank you!!
@thesilentonevictor
@thesilentonevictor Жыл бұрын
@@JumpermanTech do you work on co2 systems and ammonia as well
@aungthiha5050
@aungthiha5050 Жыл бұрын
Thank you so much bro. Worth following the channel. Keep it up
@JumpermanTech
@JumpermanTech Жыл бұрын
You're very welcome & thank you for watching/supporting 🙏🔧⚡️
@scottmaz4063
@scottmaz4063 Жыл бұрын
You gotta get the owner to give you the ok to clean all those units. Wow those units are dirty.
@JumpermanTech
@JumpermanTech Жыл бұрын
Facts. They definitely need the cleaning a preventive maintenance program afterwards. Units are all in that condition. They have around 135 air handlers inside. No wonder there are complaints and many failures 🔧⚡️ Thanks for watching & commenting!
@scottmaz4063
@scottmaz4063 Жыл бұрын
Get him to sign up for annual tune ups. Preventive maintenance. Great job
@briancarlisi2224
@briancarlisi2224 Жыл бұрын
Despite this being SSDD, I’m finding something new to learn. Thanks for taking the time to video. I certainly appreciate these!
@JumpermanTech
@JumpermanTech Жыл бұрын
@briancarlisi2224 What is SSDD? Glad you're learning. You're very welcome & I appreciate you & your time🙏🔧⚡️
@briancarlisi2224
@briancarlisi2224 Жыл бұрын
@@JumpermanTech SSDD… same sh*t, different day, lol
@samuelsteffan6987
@samuelsteffan6987 Жыл бұрын
What i have seen when working on VRV. Is when you have flood back to the compressor, that liquid pushes your oil from the compressor. Meaning, with no oil you get extremely high discharge temps. Almost in all cases, we change the discharge thermister with every compressor changout along with the inverter board. If acidity is present, we always install a liquid line drier.
@Laker4life760
@Laker4life760 Жыл бұрын
I just changed a compressor on one of these. 24hr vac 👍👍👍
@JumpermanTech
@JumpermanTech Жыл бұрын
Thats awesome. Hard work right there. Definitely need a long deep vacuum for a system like this. Thanks for watching & commenting🔧⚡️
@ILoveKittys78
@ILoveKittys78 Жыл бұрын
you truly are phenomenal 💚😻
@JumpermanTech
@JumpermanTech Жыл бұрын
Thank you!💜⚡️
@hamitavcoglu9813
@hamitavcoglu9813 12 күн бұрын
Nice to watch you bro
@Carloshernandez-kk7dp
@Carloshernandez-kk7dp 5 ай бұрын
Great video thanks!
@oldmetalguy4577
@oldmetalguy4577 Жыл бұрын
Scenario: You tell them how to fix the issue, they don't fix the issue, you keep coming out to replace compressors and boards...it would be gravy if it were only at ground level LOL!
@JumpermanTech
@JumpermanTech Жыл бұрын
Haha facts! Ground level would be amazing. Entering the building we must go down a flight of stairs so just entering the building is a nightmare with all the equipment. Gotta do what you gotta do though. New York City problems. Thanks for watching & commenting 🙏⚡️🔧 Much appreciated metal guy🤙
@oldmetalguy4577
@oldmetalguy4577 Жыл бұрын
@@JumpermanTech Man, I am such a primadonna. All these years of ground level or one level up, I watch this east coast stuff and realize pretty quick just how spoiled I've been in TX. Great channel and great work.
@NewDestinationEng
@NewDestinationEng Жыл бұрын
Nice work JMT! Have you checked the system alarms? It might help to diagnose the main issue there
@JumpermanTech
@JumpermanTech Жыл бұрын
Thank you!! Haven't checked any alarms. Do you mean like a history of error codes? Not sure how that's done. Maybe with the LGMV tool? Appreciate the feedback 🙏
@zekenzy6486
@zekenzy6486 Жыл бұрын
Great Video. Nice Work. Good job. Thank you for sharing
@JumpermanTech
@JumpermanTech Жыл бұрын
Thank you very much! You're very welcome & thank you for watching/commenting. Appreciate all your support 🔧⚡️
@jrh86
@jrh86 Жыл бұрын
Yep JM airflow restriction as you say, lovely jubbly 😆
@JumpermanTech
@JumpermanTech Жыл бұрын
Definitely air flow issues and liquid migration considering the entire building is in this shape. Thank you for watching & commenting!
@christopherleubner6633
@christopherleubner6633 4 ай бұрын
The pink chemical is phenothaline, it is pink in base, yellow in acid A stupidly cheap source of it is mylanta gas relif tablets ❤️
@shine-cg9uf
@shine-cg9uf Жыл бұрын
🇺🇸👍❄️💪 nice work. Solve the problem not the symptom
@JumpermanTech
@JumpermanTech Жыл бұрын
Thank you!! Facts🇺🇲🔧⚡️🤙
@johnwalker890
@johnwalker890 Жыл бұрын
Good job Jumper, I think the system is running high pressure, because the condenser coil and evaporator coil being dirty, I could be wrong, not sure.
@stevencossaboon3237
@stevencossaboon3237 Жыл бұрын
Nice work Jumper man.
@JumpermanTech
@JumpermanTech Жыл бұрын
Thank you very much!!
@kheansovannrith6907
@kheansovannrith6907 4 ай бұрын
Great work Sir, May you recommend me the type of oil compressor for LG multi-v?
@jrh86
@jrh86 Жыл бұрын
From my time in the industry its Installation and no or poor PPM maintenance that most problematic issues develop from.
@JumpermanTech
@JumpermanTech Жыл бұрын
This is definitely a mix of poor installation, poor service practices & no maintence for 12 years!! Everytime I cleaned a unit, they had to cut down the ceiling just to get access. It's been a ticking time bomb since day 1. Thanks for watching & commenting 🔧⚡️
@jrh86
@jrh86 Жыл бұрын
Thank you for your time and chanell it's great 😃👍👍👍💯
@JumpermanTech
@JumpermanTech Жыл бұрын
@@jrh86 You're welcome🙏 Thank for you the kind word and time as well. Stay tuned for new videos every week⚡️
@thomasvlaskampiii6850
@thomasvlaskampiii6850 Жыл бұрын
After watching another HVAC tech that lives out in California work, this whole situation makes me feel claustrophobic lol
@DxTalmus
@DxTalmus Жыл бұрын
Are there no elevator you can use on that building?
@JumpermanTech
@JumpermanTech Жыл бұрын
There's an elevator but you need to walk up 2 stories to reach these units on that fire escape/staircase. Thanks for watching & commenting 🔧⚡️
@jaimegutierrez9930
@jaimegutierrez9930 Жыл бұрын
Hey awsome videos bro i live here in nyc. I have a question did you went to a HVAC school ? im looking to get any training hvac related any recommendations? Any good training courses that you know of ? Would help alot. Also is there anyway to contact you through email ? I would like to buy you a nice peter luger steak lol so i could pick your brain? Also have you hear of “Boland” training on VRF ?
@jrh86
@jrh86 Жыл бұрын
WOW again !
@JumpermanTech
@JumpermanTech Жыл бұрын
Another one! Yes🔧⚡️
@sontungle2641
@sontungle2641 4 ай бұрын
Tell the building manager to install Daikin VRV IV H :))).
@arielhernandez2911
@arielhernandez2911 Жыл бұрын
Are you the owner of the hvac company ? If you are that’s dope and the customer never listen especially when system go off on high head pressure cuz they don’t want to pay to get pm done amh
@DxTalmus
@DxTalmus Жыл бұрын
Can you do a video of the car right now?😃
@JumpermanTech
@JumpermanTech Жыл бұрын
Ill make a video on that! Thanks for the idea 💡
@jonnyrottenshvacrchannel5884
@jonnyrottenshvacrchannel5884 4 ай бұрын
I'd always tell them pay it now or definitely pay more later
@user-mk3np8wi8z
@user-mk3np8wi8z 7 ай бұрын
That piping looks very crappy. If they don't clean the indoor units, the compressor is going to be killed again.
@christopherleubner6633
@christopherleubner6633 4 ай бұрын
Have a come to Jesus meeting with the property manager or owner regarding the unit air handlers being in desperate need of cleaning. They were terrible 😮
@aquaticspecialities5382
@aquaticspecialities5382 Жыл бұрын
Man those units are filthy.
@JumpermanTech
@JumpermanTech Жыл бұрын
Facts. The entire building is in this shape. We are talking about 135 air handlers 🤯
@aquaticspecialities5382
@aquaticspecialities5382 Жыл бұрын
@@JumpermanTech that’s insane hopefully they approve you for the bid 💪🏻 😂
@Cisco132
@Cisco132 Жыл бұрын
LG is the worst VRF ever made, and since they are cheaper than Daikin and Mitsubishi so they get installed by non-professional mom-and-pop shops that don’t send techs to classes to learn how to run nitrogen and install them properly.
@sontungle2641
@sontungle2641 4 ай бұрын
In Vietnam we usually install Daikin VRV IV & Panasonic FSV VRF 😎😎😎.
@AutoDudes
@AutoDudes Жыл бұрын
LG should be banned from making units.
@JumpermanTech
@JumpermanTech Жыл бұрын
Haha seriously!
Checkmate HVAC Test Kit
5:59
Refrigeration Technologies
Рет қаралды 8 М.
ISSEI & yellow girl 💛
00:33
ISSEI / いっせい
Рет қаралды 18 МЛН
CHOCKY MILK.. 🤣 #shorts
00:20
Savage Vlogs
Рет қаралды 28 МЛН
OMG what happened??😳 filaretiki family✨ #social
01:00
Filaretiki
Рет қаралды 11 МЛН
WHO CAN RUN FASTER?
00:23
Zhong
Рет қаралды 40 МЛН
Compressor Burnout and Acid Management: HVAC 101 @MechanicalPros
14:26
Refrigerant Oil, Volume Temperature and Weight
7:28
Love2HVAC with Ty Branaman
Рет қаралды 3,1 М.
WHAT WERE THE ICE MACHINE CLEANERS THINKING?
21:49
HVACR VIDEOS
Рет қаралды 31 М.
ISSEI & yellow girl 💛
00:33
ISSEI / いっせい
Рет қаралды 18 МЛН