Hydrolevel VXT-24 Wired Backwards - Lights Up, But Does Not Auto Feed

  Рет қаралды 10,246

Silent Steam Team

Silent Steam Team

Күн бұрын

Пікірлер
@rickstevens6787
@rickstevens6787 3 жыл бұрын
It's easy to get the hot and common mixed up at the LWCO. I drain down the boiler , put the delay on the feeder to 30 seconds and see if it feeds when it goes into low water condition. If it doesn't, switch the R and C at the feeder. Then set the delay usually for 8 to 10 min to give time for the water to come back to the boiler.
@gordonschweizer5154
@gordonschweizer5154 3 жыл бұрын
Good proceedure. I usually look for the "period" after the zero to see if the VXT is getting the signal to start the countdown. On this unit, I didn't see that dot when the LWCO was triggered. I first thought either the LWCO was not sending the signal or the VXT was defective.
@matthewbecker3674
@matthewbecker3674 3 жыл бұрын
Thank you for the tip. As always, looking forward to the next.
@gordonschweizer5154
@gordonschweizer5154 3 жыл бұрын
Thanks for watching!
@bauhnguefyische667
@bauhnguefyische667 3 жыл бұрын
Interesting find. Reading those wiring diagrams, that get ignored with ‘experience’.
@gordonschweizer5154
@gordonschweizer5154 3 жыл бұрын
Great point!
@scottk0623
@scottk0623 3 жыл бұрын
Nice tech tip. Thanks Gordon👍
@gordonschweizer5154
@gordonschweizer5154 3 жыл бұрын
This one was wired by "others" in 2019 The VXT counter showed 042, so it must have fed, right? It must work, right? Close, but not quite. Turns out, the previous owner was using the push to feed button- which does work as shown in the video- and that's what showed up on the counter. This is the first one I've seen like this. The current owner graciously let me video this.
@scottk0623
@scottk0623 3 жыл бұрын
@@gordonschweizer5154 I’ed of thought he would of thought something was a miss when he had to add water after paying for an auto feed? Can’t figure people out sometimes. Stay well
@gordonschweizer5154
@gordonschweizer5154 3 жыл бұрын
Well, I'd didn't realize something was amiss at first, and I'm the so-called "expert", so I'm going to cut the fellow some slack. I'm not sure when this error crept in. Other people may have altered this system since the install before I got to it, and I was mostly called to get a convector heating again (bad trap).
@ed6837
@ed6837 3 жыл бұрын
Good to know. In the old days 24 volts was ..............whatever. Now it "should" come off the secondary of a transformer with 1 side of the secondary the "neutral" grounded
@gordonschweizer5154
@gordonschweizer5154 3 жыл бұрын
Amen. I've been caught out more than a few times by not paying attention to 24 volt polarity. Like you said, the old stuff didn't care. The new stuff of a certain does!
@bauhnguefyische667
@bauhnguefyische667 2 жыл бұрын
Welp, Gordon I’m on a job playing coroner for everything you shouldn’t do with steam. Dry Fire, all safeties failed on a two year old steamer, except the smoke alarm. Gracious my new client is alive. Fire department estimated riser pipes hit 600-700 degrees, Burt pipe dope and section seals. Whoa!
@gordonschweizer5154
@gordonschweizer5154 2 жыл бұрын
Whoa Indeed!
@gordonschweizer5154
@gordonschweizer5154 2 жыл бұрын
Any idea why the LWCO failed?
@bauhnguefyische667
@bauhnguefyische667 2 жыл бұрын
@@gordonschweizer5154 Miud, Locked burner LWCO in up position. Lower LWVO, probe type was dirty and failed to send signal to condensate receiver pump. Didn’t mater fill water was off and no Hartford loop. Flow checks on receiver were mudded and open. Boiler drained itself, stand pipe on receiver dumped at tap level to pit. That’s some great craftsmanship 😡
@gordonschweizer5154
@gordonschweizer5154 2 жыл бұрын
@@bauhnguefyische667 A true cluster foxtrot!
@gordonschweizer5154
@gordonschweizer5154 2 жыл бұрын
It seems that even if there was a Hartford Loop, it would not have been enough
@realmadrid091884
@realmadrid091884 3 жыл бұрын
This automatic water feeder now they come with electrical tape on the solenoid probe and the screw to attach the valve to the box don't line up i have to use zip ties to hold it I had 2 similar problems .
@gordonschweizer5154
@gordonschweizer5154 3 жыл бұрын
I'm sorry to hear you got a bunch of the "taped" series of the new VXT. They are troublesome. Did you happen to see a video on how to fix it in the field? I hope it was helpful. If not, please let the folks at Hydrolevel know you are having an issue. Their latest fix appears to have nailed that problem for good.
@ramatraghubir1295
@ramatraghubir1295 3 жыл бұрын
How do u hook up 2 lwco on a steam boiler ny
@gordonschweizer5154
@gordonschweizer5154 3 жыл бұрын
Hook them up in series. If one is manual reset, hook that one up to power first in line.
Hydrolevel VXT Steam Boiler Water Feeder
19:59
Silent Steam Team
Рет қаралды 38 М.
Low Water Cut Offs & Water Feeders (Steam Boilers)
10:46
Jersey Mike HVAC
Рет қаралды 22 М.
-5+3은 뭔가요? 📚 #shorts
0:19
5 분 Tricks
Рет қаралды 13 МЛН
I Sent a Subscriber to Disneyland
0:27
MrBeast
Рет қаралды 104 МЛН
I'VE MADE A CUTE FLYING LOLLIPOP FOR MY KID #SHORTS
0:48
A Plus School
Рет қаралды 20 МЛН
Checking Out A Used VXT-24 Steam Boiler Water Feeder
9:38
Silent Steam Team
Рет қаралды 1,3 М.
Polarity Matters, Even with 24 Volts! How to Install Automatic Water Feeder on Steam Boiler
17:03
Mikey Pipes - Pipe Doctor Plumbing & Heating & Air
Рет қаралды 16 М.
old steam boiler automatic feeder will not feed
16:09
steven lavimoniere
Рет қаралды 85 М.
Low Water Cut-Off Replacement On Weil-Mclane Boiler.  But Why Two?
6:05
Jeff’s HVAC Adventures
Рет қаралды 2,9 М.
Hydrolevel VXT-24 Automatic Feeder Failed to Close & Flooded Steam Boiler
24:58
Mikey Pipes - Pipe Doctor Plumbing & Heating & Air
Рет қаралды 15 М.
This Could Keep Your Family Warm During An Emergency Power Outage.
16:38
The DIY HVAC Guy
Рет қаралды 2,6 МЛН
Weil McLain Steam Vid 2
23:01
grothcc
Рет қаралды 111 М.
-5+3은 뭔가요? 📚 #shorts
0:19
5 분 Tricks
Рет қаралды 13 МЛН