It's easy to get the hot and common mixed up at the LWCO. I drain down the boiler , put the delay on the feeder to 30 seconds and see if it feeds when it goes into low water condition. If it doesn't, switch the R and C at the feeder. Then set the delay usually for 8 to 10 min to give time for the water to come back to the boiler.
@gordonschweizer51543 жыл бұрын
Good proceedure. I usually look for the "period" after the zero to see if the VXT is getting the signal to start the countdown. On this unit, I didn't see that dot when the LWCO was triggered. I first thought either the LWCO was not sending the signal or the VXT was defective.
@matthewbecker36743 жыл бұрын
Thank you for the tip. As always, looking forward to the next.
@gordonschweizer51543 жыл бұрын
Thanks for watching!
@bauhnguefyische6673 жыл бұрын
Interesting find. Reading those wiring diagrams, that get ignored with ‘experience’.
@gordonschweizer51543 жыл бұрын
Great point!
@scottk06233 жыл бұрын
Nice tech tip. Thanks Gordon👍
@gordonschweizer51543 жыл бұрын
This one was wired by "others" in 2019 The VXT counter showed 042, so it must have fed, right? It must work, right? Close, but not quite. Turns out, the previous owner was using the push to feed button- which does work as shown in the video- and that's what showed up on the counter. This is the first one I've seen like this. The current owner graciously let me video this.
@scottk06233 жыл бұрын
@@gordonschweizer5154 I’ed of thought he would of thought something was a miss when he had to add water after paying for an auto feed? Can’t figure people out sometimes. Stay well
@gordonschweizer51543 жыл бұрын
Well, I'd didn't realize something was amiss at first, and I'm the so-called "expert", so I'm going to cut the fellow some slack. I'm not sure when this error crept in. Other people may have altered this system since the install before I got to it, and I was mostly called to get a convector heating again (bad trap).
@ed68373 жыл бұрын
Good to know. In the old days 24 volts was ..............whatever. Now it "should" come off the secondary of a transformer with 1 side of the secondary the "neutral" grounded
@gordonschweizer51543 жыл бұрын
Amen. I've been caught out more than a few times by not paying attention to 24 volt polarity. Like you said, the old stuff didn't care. The new stuff of a certain does!
@bauhnguefyische6672 жыл бұрын
Welp, Gordon I’m on a job playing coroner for everything you shouldn’t do with steam. Dry Fire, all safeties failed on a two year old steamer, except the smoke alarm. Gracious my new client is alive. Fire department estimated riser pipes hit 600-700 degrees, Burt pipe dope and section seals. Whoa!
@gordonschweizer51542 жыл бұрын
Whoa Indeed!
@gordonschweizer51542 жыл бұрын
Any idea why the LWCO failed?
@bauhnguefyische6672 жыл бұрын
@@gordonschweizer5154 Miud, Locked burner LWCO in up position. Lower LWVO, probe type was dirty and failed to send signal to condensate receiver pump. Didn’t mater fill water was off and no Hartford loop. Flow checks on receiver were mudded and open. Boiler drained itself, stand pipe on receiver dumped at tap level to pit. That’s some great craftsmanship 😡
@gordonschweizer51542 жыл бұрын
@@bauhnguefyische667 A true cluster foxtrot!
@gordonschweizer51542 жыл бұрын
It seems that even if there was a Hartford Loop, it would not have been enough
@realmadrid0918843 жыл бұрын
This automatic water feeder now they come with electrical tape on the solenoid probe and the screw to attach the valve to the box don't line up i have to use zip ties to hold it I had 2 similar problems .
@gordonschweizer51543 жыл бұрын
I'm sorry to hear you got a bunch of the "taped" series of the new VXT. They are troublesome. Did you happen to see a video on how to fix it in the field? I hope it was helpful. If not, please let the folks at Hydrolevel know you are having an issue. Their latest fix appears to have nailed that problem for good.
@ramatraghubir12953 жыл бұрын
How do u hook up 2 lwco on a steam boiler ny
@gordonschweizer51543 жыл бұрын
Hook them up in series. If one is manual reset, hook that one up to power first in line.