I think code requires a 2nd cutoff in certain states for boilers above a certain btu rating. That's a big boiler. I had 550,000 WM EG-11 in my house. Was able to replace it with an 8 section Burnham Independence.
@JeffsHVACAdventures Жыл бұрын
Didn’t think about that. Good point
@georgebrabec1749 Жыл бұрын
@JeffsHVACAdventures Somebody might have been thinking about redundant protection. Better to have 2 than none !
@georgebrabec1749 Жыл бұрын
Sometimes you could have 2 LECO's , one being used as the actual burner shutdown and the second one controls the make-up wster valve.
@JeffsHVACAdventures Жыл бұрын
Very true. These two basically shut down the same thing tho. The one I replaced cut main power to the boiler, the other cut power to the ignition control board.
@jeffreyhalet9632 Жыл бұрын
In case someone says Double hog dare ya… Better have 2 guard dogs 😂😂😂
@databasespace Жыл бұрын
maybe a odd safety feature, one for each burner but wired diffrently
@JeffsHVACAdventures Жыл бұрын
Could be..
@desieranks23 күн бұрын
They always put 2 of the same safety on Comercial boilers
@zlo92x21 Жыл бұрын
The size of the boiler is why I believe
@mikewhittaker5984 Жыл бұрын
Same reason it has 2 valves pads the bill
@nayemhossain4283Ай бұрын
Code over 300000 btu requar two low water cuts of one manually push to one ,if cut off