TROUBLE WITH DAIKIN REEFER CONTAINER ( System gets vacuum) | ETO TROUBLESHOOTING

  Рет қаралды 37,539

leckyjake

leckyjake

Күн бұрын

Пікірлер: 119
@ChoroTesla
@ChoroTesla 13 күн бұрын
May your soul rest in peace.... Best ETO of all times
@LarrydWoodruff
@LarrydWoodruff 4 жыл бұрын
This video is a good reminder on how to handle E109. Very nice!
@leckyjake
@leckyjake 4 жыл бұрын
Thank you.
@jeanermac1507
@jeanermac1507 3 жыл бұрын
Thank you for blog sir jake. Marami akong natutunan sayong vedio. Elect then ako sa passenger ship.
@kpreroualbertkezo2623
@kpreroualbertkezo2623 3 жыл бұрын
Good morning sir thank so much for this video . So we need more video concerning daikin containers .
@senthilanbalagan8532
@senthilanbalagan8532 4 жыл бұрын
Good job bro mostly I done blowing hot air on that eev part till now for clearing and tap sometimes but this helps a lot that I can clean the valve part hereafter thanks a lot bro
@janettelanuiki
@janettelanuiki 2 жыл бұрын
Thank you for rectifying that -10.1 temp (It was killing me) Nicely done
@stephenwoolway7495
@stephenwoolway7495 3 жыл бұрын
Jake - outstanding work. I’m a docking superintendent for Svitzer Australia 😉
@leckyjake
@leckyjake 3 жыл бұрын
Thank you. Been wanting to work in Australia as Reefer Tech ever since
@domalexus1991
@domalexus1991 2 жыл бұрын
Thank you very much sir! I just now encountered this alarm, good thing i saw your video just before i was about to replace the filter drier. Thank you very much! :)
@pradeepprakasan
@pradeepprakasan 4 жыл бұрын
thank you sir.as a trainee ee it really helped me ❤️
@leckyjake
@leckyjake 4 жыл бұрын
Just keep on sharing the channel so that we can help more aspiring ETOs
@pradeepprakasan
@pradeepprakasan 4 жыл бұрын
sure sir.i will share with my friends
@brahim21261
@brahim21261 2 жыл бұрын
Hello jack thank you for al the video's. I have a j081 alarm on my daikin. Pumpdown alarm. Where i have to look first? Thank you 🙏
@gautham2418
@gautham2418 4 жыл бұрын
Thank you so much lecky. Wish to sail with you someday.
@leckyjake
@leckyjake 4 жыл бұрын
Thank you for the support
@salemhunid9482
@salemhunid9482 4 жыл бұрын
thank you very much sir. keep doing videos about troubleshooting of reefer container
@leckyjake
@leckyjake 4 жыл бұрын
I will and expect more. Videos will be uploaded every weekends
@salemhunid9482
@salemhunid9482 4 жыл бұрын
@@leckyjake Thats will be great bro. good luck
@antoniolim2442
@antoniolim2442 2 жыл бұрын
good job sir and thanks for sharing on your experience so we can spread out and more knowledge to be apply .
@yevhenstelmakh4596
@yevhenstelmakh4596 4 жыл бұрын
we had same problem with daikin unit, but cleaning of eev dont help, we use manual eev from reefer kit. thank you for videos!!!
@leckyjake
@leckyjake 4 жыл бұрын
The EEV body is the problem then
@laljayasundara7371
@laljayasundara7371 2 жыл бұрын
thank you and God Bless.
@khaledmaher6981
@khaledmaher6981 Жыл бұрын
Thanks for the great video, What type of Loctite you do use ??
@ethanlove5513
@ethanlove5513 3 жыл бұрын
Excellent video very helpful and informative
@fatihdanfatimah1838
@fatihdanfatimah1838 3 жыл бұрын
You are the best, Sir. Thank you
@krishnakumarvv254
@krishnakumarvv254 2 жыл бұрын
Very good 👍
@aungkowinkyi8549
@aungkowinkyi8549 2 жыл бұрын
Tks you very much indeed.
@ferdirahim6794
@ferdirahim6794 3 күн бұрын
Full skill
@muhammadrasheed3848
@muhammadrasheed3848 3 жыл бұрын
good video my friend
@TuanMinh-zd4tr
@TuanMinh-zd4tr Ай бұрын
hope you still read this comment. looking forward to your help. my device is having error F803 and E107.
@reohsamjale6116
@reohsamjale6116 4 жыл бұрын
Swerte nman ng maging cadete mo sir,thank you for sharing leckyjake
@mehendranathramdath7174
@mehendranathramdath7174 3 ай бұрын
Very good
@robertemanuel2590
@robertemanuel2590 3 жыл бұрын
If the problem had been a blocked filter drier instead of the EEV could you have replaced the filter drier on board ship ? Thank you Lecky I really enjoyed your videos.
@leckyjake
@leckyjake 3 жыл бұрын
Yes it is the main goal onboard, to save the cargo. Filter drier is fixable onboard
@robertemanuel2590
@robertemanuel2590 3 жыл бұрын
@@leckyjake thank you. It is funny how a P&I Club correspondent is arguing with me that you can not do it !
@madushanashira9954
@madushanashira9954 3 жыл бұрын
thanks legi
@DiegoPerez-ms3yu
@DiegoPerez-ms3yu 2 жыл бұрын
VERY GOOD VIDEO, DO YOU HAVE OTHERS BRANDS TROUBLESHOOTING CASES?
@cyrildelacruzjr4365
@cyrildelacruzjr4365 3 жыл бұрын
Happy morning sir keep safe 🙏 god BLESs 🙏
@arulgnanaesther3942
@arulgnanaesther3942 8 ай бұрын
great job bro
@Yourservice
@Yourservice 9 ай бұрын
Mr.Leckyjake is there other cause of alarm E109? other than the EEV COIL?
@MrShanu621
@MrShanu621 4 жыл бұрын
Really helpful sir 🙏🏻
@leckyjake
@leckyjake 4 жыл бұрын
Thank you for the support
@Gokolito84
@Gokolito84 6 ай бұрын
Hello there, do you have any idea is zestia and regular daikin reefer have same condenser coil? I need to replace a condenser coil on zestia reefer but i have 2046165, not zestia's 2233495. Thanks.
@nizwarnd1636
@nizwarnd1636 3 жыл бұрын
Good.
@leckyjake
@leckyjake 3 жыл бұрын
Thanks
@Irvindzimlaz
@Irvindzimlaz Жыл бұрын
@leckyjake do you think its possible to run these containers all day on Solar. Say a 20ft size?
@acesuminguit4911
@acesuminguit4911 3 жыл бұрын
salamat po sir GOD bless po...
@brahim21261
@brahim21261 2 жыл бұрын
Verry useful thnx alot
@nunzio99lombardo56
@nunzio99lombardo56 Жыл бұрын
Hi Leckyjake, in my case I have an opposite situation, LPT does not move in any case, it always stays at 300 I also tried to close the EEV with the emergency cap but nothing to do. Any idea how I can fix it
@senly4147
@senly4147 3 жыл бұрын
sir you know everyday ii try to fine your new video for cantainer freezer because you have experience for that
@leckyjake
@leckyjake 3 жыл бұрын
How is your unit? I hope you already fix it
@cesdawa7938
@cesdawa7938 3 жыл бұрын
Hey we have an issue with our container.After a massive thunder storm,the fan inside is running but it seems the compressor and fan is not coming on?What do you think the problem is?Do you think a power surge may have caused a particular part to blow up such as a capacitor?Need your advise for our technicians to engage a reefer mechanic to have a look and fix
@senly4147
@senly4147 3 жыл бұрын
i.am very thank you somuch for helping me sir
@chathutangakumara3615
@chathutangakumara3615 3 жыл бұрын
thank you sir these videos very helpfull
@lusaneswisse9810
@lusaneswisse9810 2 жыл бұрын
Hello sir i will thank uu so much for sharing ur videos ..and ur experience its helping us so much ...just i want some help i hade probleme whith same reffer is giving alarm p0000 after some.time i check that is giving changing up to p0006 but still alarm is here and reffer not started any help plzz
@janettelanuiki
@janettelanuiki 2 жыл бұрын
Nice! My husband used to work for Seattle CEM shop(I saw the sticker on the condenser cover) well explained. Are you Pinay?
@marvindiazdeleon1993
@marvindiazdeleon1993 2 жыл бұрын
They used silicone as the service bulletin of daikin wants to seal the eev body and keep from moisture entering, but its look like it can't help as it is still clogged by the dirt and falls to E109.
@mithileshramteke3882
@mithileshramteke3882 3 жыл бұрын
Thank you for information
@henrylitton3941
@henrylitton3941 3 жыл бұрын
What is the refrigerant use and what is the correct pressure for low and high pressure iwant to learn in reefer van thanks
@r.4169
@r.4169 3 жыл бұрын
💯
@adamy6116
@adamy6116 4 жыл бұрын
sir, what is the normal reading for hpt and lpt for -18 to -21'c..
@weatherdonemulenga9711
@weatherdonemulenga9711 3 жыл бұрын
I am working on Daikin LXE10E-A33A , giving me the Alarm code F101. Upon disconnecting the compressor outlet, the compressor started running ok and the alarm message disappeared.we come to conclude that the compressor is not ok and especially it is becoming very hot on it's upper area. I need your view on this one.
@leckyjake
@leckyjake 3 жыл бұрын
F101 activates when your High Pressure Switch activated. You have to check your discharge pressure first and analyze what is causing the pressure to get high.
@weatherdonemulenga9711
@weatherdonemulenga9711 3 жыл бұрын
@@leckyjake Thanks very much to respond. I 'll check as you have said. I am in Zambia . I would love if we can arrange and communicate on video call. I admire your expertise
@courtrutherford8913
@courtrutherford8913 3 жыл бұрын
You should try using Nylog on the EEV threads. It's like pipe dope for refrigeration.
@AAminy
@AAminy 7 ай бұрын
thanks
@sergiolopez9579
@sergiolopez9579 4 жыл бұрын
Muy bien
@vijayakrishnankogulan7738
@vijayakrishnankogulan7738 2 жыл бұрын
May i known what is the normal value of hot,lpt???
@luisedward3336
@luisedward3336 3 жыл бұрын
Hey mate need some help.Was getting a E205 alarm on a daikin freezer container ( evaporator fan motor failure)Changed one of the evaporator fan motor because it had a bearing issue. After hours of operation the same alarm still appears. I’ve checked the running amperage of both motors and they appear to be fine. Is there something I’m missing?
@leckyjake
@leckyjake 3 жыл бұрын
there might be a lot of factors. but with conventional way of troubleshooting, check the rotation of both fans. sometimes the brand new one is faster than the old. 2nd. check the level of your cargo since the compartment is open. 3rd. check the contactor if you are single phasing. you might probably need to change the other fan.
@luisedward3336
@luisedward3336 3 жыл бұрын
@@leckyjake I have checked all that everything checks out good . I forgot to mention that there is a lot of flooding back to compressor. And when it goes on alarm the system goes on defrost.
@leckyjake
@leckyjake 3 жыл бұрын
then check the CTP of your compressor. this may sound weird but there are times that 205 appears if this is activated.
@rasssike5941
@rasssike5941 3 жыл бұрын
wow sir aspiring seaman here sana sir matulingan niyo ako pano po ba mag appy sa ganyan
@sherwinsarmiento1688
@sherwinsarmiento1688 2 жыл бұрын
What is the running pressure of lowside sir
@bikermotards7956
@bikermotards7956 3 жыл бұрын
Hi, tank you for this class! Can you help me, I need to buy some refees world wide and I need Honest suplyers. Can you mention some. Please
@zeinz8309
@zeinz8309 2 жыл бұрын
EEV How to check for good or bad?
@krishnakumarvv254
@krishnakumarvv254 2 жыл бұрын
Sir can i ask you one dout regarding Aconis 2000
@Dom-uw4pn
@Dom-uw4pn 2 жыл бұрын
Sir, i already cleaned the eev and now running. What does it mean when evap in temperature is colder than evap out?
@joelboyd9266
@joelboyd9266 3 жыл бұрын
I have a p268 alarm on a diakin unit what is this about
@leckyjake
@leckyjake 3 жыл бұрын
Hi, pxxx alarm means pull down timer. It will disappear automatically once your unit will get in range.
@chinoyrocks2806
@chinoyrocks2806 4 жыл бұрын
Lecky request about sa refcon naman salamat
@leckyjake
@leckyjake 4 жыл бұрын
Wala na kaming refcon sa barko. May bagong system which is called RCM. Real time temp monitoring ng mismong customer.
@chinoyrocks2806
@chinoyrocks2806 4 жыл бұрын
@@leckyjake yun bayong isa isang naka connect sa reefer tapos tangalin pag for discharging na?
@hendrowahyudi5207
@hendrowahyudi5207 3 жыл бұрын
Hai sir.. What if the temperature only goes down to -10°C can't reach -20°C,,what should i do.. Pleasee..
@RupeshThapa-zs1db
@RupeshThapa-zs1db 5 ай бұрын
E307 alarm how to troubleshoot this problem
@rafaelparane2501
@rafaelparane2501 4 жыл бұрын
Sir..do you have an asst electrician on board..or are you a solo ETO..?
@leckyjake
@leckyjake 4 жыл бұрын
I am a solo ETO but i think next month I will have a Cadet
@tusharkhanvilkar7991
@tusharkhanvilkar7991 Жыл бұрын
We have an issue with our container , if set Temp is - 25 C and supply Temp is - 17 C then why Return Temp is stop at - 11 C
@arnaldomagallanes5767
@arnaldomagallanes5767 3 жыл бұрын
Sir, daikin reefer model LXE10E 147. HOW TO RESET THE FAULT ALARM CODE
@izharpatwegar
@izharpatwegar 3 жыл бұрын
HPT high 1632, & lpt 60 21.8©°daikin container Expansion valve change Solnat valve change. Expansion coil change What problem please problem solution??????
@leckyjake
@leckyjake 3 жыл бұрын
High pressure. Clean the EEV and purge a little bit
@senly4147
@senly4147 3 жыл бұрын
Hi bro could i ask you something my daikin has a problem with ice in evapor to compressor
@leckyjake
@leckyjake 3 жыл бұрын
check your eev and clean it. if situation still the same and the icing is reaching the compressor then remove all the freon and charge the right amount of refrigerant
@andrewdeguzman4823
@andrewdeguzman4823 3 жыл бұрын
Hi sir sana mapansin mo paano po. Mag calibrate ng smv sir
@hakhakuuba5073
@hakhakuuba5073 3 жыл бұрын
I live in Mongolia. I want to work as salaryfree worker at your ship as salaryfree worker. I just want to learn how to check and repair reefers...
@TheYachtEngineer
@TheYachtEngineer 4 жыл бұрын
Thank you for this guide. I wish I was your Ass. Elec. Please tell what is the difference in responsibility between ETO and Electrician on Maersk ships. And if they call me to join as Electrician will there be an ETO as my boss? And is it possible to become ETO after working as Electrician on MAERSK???
@alexsyzo2645
@alexsyzo2645 2 жыл бұрын
Мктф привет
@senly4147
@senly4147 3 жыл бұрын
sir i check the evapo solenoid lock so good not restric clog sir but still ice
@leckyjake
@leckyjake 3 жыл бұрын
Check your refrigerant level
@reymarkdeguzman9347
@reymarkdeguzman9347 4 жыл бұрын
Sir pano mag apply ng electrical cadet sa maerks line sana po masagot or magawan nyo po ng content salamat sir
@senly4147
@senly4147 3 жыл бұрын
sir cuold tell me gauge how many psi in the low side and highside and how many psi is enought and how many is not enought sir
@ivanfmartinezm
@ivanfmartinezm 3 жыл бұрын
It depend what type of refrigerant gas uses the system 134 a or R 22 you need to see the PT Table or the app danfoss tool ref slider
@octinocabrito8202
@octinocabrito8202 3 жыл бұрын
sir my problem is the digital display is not ligthing,, thank you
@senly4147
@senly4147 3 жыл бұрын
hello sir i have some problem with my daikin container freezer with the ice frome evaborator to the compressor what i shuold i do sir?
@leckyjake
@leckyjake 3 жыл бұрын
First check the freon level. If less then charge 2. Dismantle the eev and clean. 3. Check your filter drier it might be blocked 4. Check your evap sensor and fans
@senly4147
@senly4147 3 жыл бұрын
i am not yet finish it sir you know sometime it reach to set point most of it is became an ice not to set point sir
@christophertreeby5008
@christophertreeby5008 4 жыл бұрын
Hands down the worst job on a ship is fixing reefer containers. I would rather crawl around in the bilge testing float switches.
@phaseelectrical9462
@phaseelectrical9462 4 жыл бұрын
Eto cource details please
@fredricfrancisco7134
@fredricfrancisco7134 2 жыл бұрын
guys stop calling it Freon. call it Refrigerant. Freon is a brand.
@patricioflores4669
@patricioflores4669 2 ай бұрын
Excelente video gracias por compartir tu experiencia, me gustaría hacerte una consulta sobre estos equipos , tendrías algún correo o número de WhatsApp?
@sherwinsarmiento1688
@sherwinsarmiento1688 2 жыл бұрын
Very helpful sir thank you very much
@arulgnanaesther3942
@arulgnanaesther3942 8 ай бұрын
great job bro
@RupeshThapa-zs1db
@RupeshThapa-zs1db 5 ай бұрын
E307 alarm how to troubleshoot this problem
@senly4147
@senly4147 3 жыл бұрын
i am not yet finish it sir you know sometime it reach to set point most of it is became an ice not to set point sir
@RupeshThapa-zs1db
@RupeshThapa-zs1db 5 ай бұрын
E307 alarm how to troubleshoot this problem
REF COMPRESSOR OVERLOADING TROUBLE
9:48
leckyjake
Рет қаралды 22 М.
Молодой боец приземлил легенду!
01:02
МИНУС БАЛЛ
Рет қаралды 2,2 МЛН
ТЮРЕМЩИК В БОКСЕ! #shorts
00:58
HARD_MMA
Рет қаралды 2,7 МЛН
ALARM E707, F701 & F705? - DAIKIN REEFER CONTAINER ALARMS
4:49
Reefer Container PH
Рет қаралды 9 М.
Electric Expansion Valve (EEV) Operation and Testing! HVAC Metering Device Training!
16:34
ETO BYPASSING STARCOOL FREQUENCY CONVERTER
9:13
leckyjake
Рет қаралды 20 М.
How To Troubleshoot a Walk In Freezer Running Warm
10:57
Rookie Refrigeration
Рет қаралды 85 М.
ETO's Jobs & Responsibility | Shanghai Departure | Snowfall Dalian
12:44
BUSTED FUSE NO. 3? - ALARM E109 / DAIKIN REEFER CONTAINER
4:07
Reefer Container PH
Рет қаралды 10 М.
PROVISION REFRIGERATION TROUBLESHOOTING | Marine Electrician
8:38