I had a lot of trouble making analog inputs to work properly. This video really clarifies many questions I had before.. Thank You very much! :D
@QuickPLC-kh5of3 ай бұрын
Great. If you haven't already, have a look at Analog amplifier gain & offset: kzbin.info/www/bejne/jKjVgZKjgpJ-isksi=9lG3zvsgCJJcVvVq.
@Dzhookac3 ай бұрын
@@QuickPLC-kh5of thank you! Great video!
@СергейДигтенко7 ай бұрын
The video is very informative, hardware and programing are very clear. Thank you Sir! Regards from Ukraine.
@QuickPLC-kh5of7 ай бұрын
Thank you for the feedback. We hope that your lives can get back to normal as soon as possible. There are many refugees from your country in my town in Ireland.
@СергейДигтенко7 ай бұрын
@@QuickPLC-kh5of Thank you for the support!
@QuickPLC-kh5of6 ай бұрын
I did some more analog work. See quickplc.com/?Home___LOGO%21_index___Analog_amp_config and the video.
@ingbjellb42363 сағат бұрын
Hoi! Super video, thanks! You should look into Logo Web Editor:-)
@mellorenato923 ай бұрын
Excelente Mister! Um abraço.
@dalematthews87486 ай бұрын
Very clearly explained 👌🏽
@chandradasaarachchilage83062 ай бұрын
Very clearly instruction thankuou❤
@Samath1809 ай бұрын
❤ I love ..from Sri Lanka
@farazdeqnajim42059 ай бұрын
Thank you 🎉
@slimenkabil4 ай бұрын
Thank you
@mobisat958 ай бұрын
Can you do one with pressure sensor (or temperature) to include threshold triggers and mathematic instructions? Let me expand. You have a 0-10V, 0 to 16 bar pressure sensor and you set up the gain, install it and instead of showing the working pressure of 3.8 bar, it reads 3.2 bar. Can you show using mathematic instruction or similar how to trim the resulting pressure to read correctly. Also add threshold triggers for alarms on same.
@QuickPLC-kh5of8 ай бұрын
What is the configuration of your analog amplifier? The analog videos seem to be of higher interest than others. I'll see if I can do some more. Thanks!
@QuickPLC-kh5of8 ай бұрын
First check the signal arriving at the LOGO! 3.8 bar / 16 bar * 10 V = 2.37 V. If you don't measure that with a meter then the problem is outside the LOGO! If you can't fix it then you need to rescale your reading by 3.8 / 3.2 = 1.1875. So instead of Measurement Range maximum = 160 or 1600 make it 160 * 1.1875 = 190 or 1900. Set the decimal places in message text to 1 or 2 depending on your 160 or 1600 for 0.1 bar or 0.01 bar steps.
@zegarmistrz009 ай бұрын
Please do more videos about logo :)
@QuickPLC-kh5of9 ай бұрын
I am, thank you. What did you like? What could I do better?
@Samath1809 ай бұрын
I wish continued..PLC logo programming..
@thien7319874 ай бұрын
Fan you
@raedalabsi8 ай бұрын
I really benefited a lot from your wonderful channel I have a solar energy system to charge 54 VDC batteries, and I want to control the turning on and off of the electric generator at values for example: 44 - 60 VDC volts using the Siemens logo!8. Is there a voltage sensor for this? or any anther ideas Thank you for your help🌹
@QuickPLC-kh5of8 ай бұрын
If the LOGO! M (negative) is connected to the solar system negative then you can just use a pair of resistors to make a potential divider. A 9k - 1k divider would give you 4.4 to 6.0 V input to the LOGO! and that would give you 440 to 600 counts inside the LOGO! Make sure to calculate the power dissipated in the resistors using V^2/R for each resistor.
@raedalabsi8 ай бұрын
@@QuickPLC-kh5of Thanks Sir
@adssaeed9 ай бұрын
thanks could you please explain for me the gain and offset
@QuickPLC-kh5of9 ай бұрын
What do you not understand. Give enough details that someone could provide an answer.
@QuickPLC-kh5of6 ай бұрын
I made another video and a calculator for gain and offset. See quickplc.com/?Home___LOGO%21_index___Analog_amp_config.
@bahiense626 ай бұрын
The problem, you lost 200 counts in the AI or the same, resoluton.
@QuickPLC-kh5of6 ай бұрын
Correct. This is explained clearly at around 3:27. While you lose some resolution, you gain a ""live zero" and save the cost and space of an analog module. You said, "... or the same resolution." I don't understand that part of your comment. Thank you for the feedback.