LOGO! 4 - 20 mA on the 0 - 10 V input? | Siemens PLC programming

  Рет қаралды 14,206

Quick PLC

Quick PLC

Күн бұрын

Пікірлер: 29
@Dzhookac
@Dzhookac 3 ай бұрын
I had a lot of trouble making analog inputs to work properly. This video really clarifies many questions I had before.. Thank You very much! :D
@QuickPLC-kh5of
@QuickPLC-kh5of 3 ай бұрын
Great. If you haven't already, have a look at Analog amplifier gain & offset: kzbin.info/www/bejne/jKjVgZKjgpJ-isksi=9lG3zvsgCJJcVvVq.
@Dzhookac
@Dzhookac 3 ай бұрын
@@QuickPLC-kh5of thank you! Great video!
@СергейДигтенко
@СергейДигтенко 7 ай бұрын
The video is very informative, hardware and programing are very clear. Thank you Sir! Regards from Ukraine.
@QuickPLC-kh5of
@QuickPLC-kh5of 7 ай бұрын
Thank you for the feedback. We hope that your lives can get back to normal as soon as possible. There are many refugees from your country in my town in Ireland.
@СергейДигтенко
@СергейДигтенко 7 ай бұрын
@@QuickPLC-kh5of Thank you for the support!
@QuickPLC-kh5of
@QuickPLC-kh5of 6 ай бұрын
I did some more analog work. See quickplc.com/?Home___LOGO%21_index___Analog_amp_config and the video.
@ingbjellb4236
@ingbjellb4236 3 сағат бұрын
Hoi! Super video, thanks! You should look into Logo Web Editor:-)
@mellorenato92
@mellorenato92 3 ай бұрын
Excelente Mister! Um abraço.
@dalematthews8748
@dalematthews8748 6 ай бұрын
Very clearly explained 👌🏽
@chandradasaarachchilage8306
@chandradasaarachchilage8306 2 ай бұрын
Very clearly instruction thankuou❤
@Samath180
@Samath180 9 ай бұрын
❤ I love ..from Sri Lanka
@farazdeqnajim4205
@farazdeqnajim4205 9 ай бұрын
Thank you 🎉
@slimenkabil
@slimenkabil 4 ай бұрын
Thank you
@mobisat95
@mobisat95 8 ай бұрын
Can you do one with pressure sensor (or temperature) to include threshold triggers and mathematic instructions? Let me expand. You have a 0-10V, 0 to 16 bar pressure sensor and you set up the gain, install it and instead of showing the working pressure of 3.8 bar, it reads 3.2 bar. Can you show using mathematic instruction or similar how to trim the resulting pressure to read correctly. Also add threshold triggers for alarms on same.
@QuickPLC-kh5of
@QuickPLC-kh5of 8 ай бұрын
What is the configuration of your analog amplifier? The analog videos seem to be of higher interest than others. I'll see if I can do some more. Thanks!
@QuickPLC-kh5of
@QuickPLC-kh5of 8 ай бұрын
First check the signal arriving at the LOGO! 3.8 bar / 16 bar * 10 V = 2.37 V. If you don't measure that with a meter then the problem is outside the LOGO! If you can't fix it then you need to rescale your reading by 3.8 / 3.2 = 1.1875. So instead of Measurement Range maximum = 160 or 1600 make it 160 * 1.1875 = 190 or 1900. Set the decimal places in message text to 1 or 2 depending on your 160 or 1600 for 0.1 bar or 0.01 bar steps.
@zegarmistrz00
@zegarmistrz00 9 ай бұрын
Please do more videos about logo :)
@QuickPLC-kh5of
@QuickPLC-kh5of 9 ай бұрын
I am, thank you. What did you like? What could I do better?
@Samath180
@Samath180 9 ай бұрын
I wish continued..PLC logo programming..
@thien731987
@thien731987 4 ай бұрын
Fan you
@raedalabsi
@raedalabsi 8 ай бұрын
I really benefited a lot from your wonderful channel I have a solar energy system to charge 54 VDC batteries, and I want to control the turning on and off of the electric generator at values for example: 44 - 60 VDC volts using the Siemens logo!8. Is there a voltage sensor for this? or any anther ideas Thank you for your help🌹
@QuickPLC-kh5of
@QuickPLC-kh5of 8 ай бұрын
If the LOGO! M (negative) is connected to the solar system negative then you can just use a pair of resistors to make a potential divider. A 9k - 1k divider would give you 4.4 to 6.0 V input to the LOGO! and that would give you 440 to 600 counts inside the LOGO! Make sure to calculate the power dissipated in the resistors using V^2/R for each resistor.
@raedalabsi
@raedalabsi 8 ай бұрын
@@QuickPLC-kh5of Thanks Sir
@adssaeed
@adssaeed 9 ай бұрын
thanks could you please explain for me the gain and offset
@QuickPLC-kh5of
@QuickPLC-kh5of 9 ай бұрын
What do you not understand. Give enough details that someone could provide an answer.
@QuickPLC-kh5of
@QuickPLC-kh5of 6 ай бұрын
I made another video and a calculator for gain and offset. See quickplc.com/?Home___LOGO%21_index___Analog_amp_config.
@bahiense62
@bahiense62 6 ай бұрын
The problem, you lost 200 counts in the AI or the same, resoluton.
@QuickPLC-kh5of
@QuickPLC-kh5of 6 ай бұрын
Correct. This is explained clearly at around 3:27. While you lose some resolution, you gain a ""live zero" and save the cost and space of an analog module. You said, "... or the same resolution." I don't understand that part of your comment. Thank you for the feedback.
LOGO! Analog basics 1 | Siemens PLC programming
12:21
Quick PLC
Рет қаралды 8 М.
LOGO! Slow PWM | Siemens PLC Programming
12:14
Quick PLC
Рет қаралды 2,7 М.
VIP ACCESS
00:47
Natan por Aí
Рет қаралды 30 МЛН
It works #beatbox #tiktok
00:34
BeatboxJCOP
Рет қаралды 41 МЛН
So Cute 🥰 who is better?
00:15
dednahype
Рет қаралды 19 МЛН
Control de nivel de líquidos con sensor 4-20 mA y Logo Siemens
22:04
How the photoelectric sensor is connected and works?
5:37
MAX-About-DEVICE
Рет қаралды 173
Read encoder pulse and calculate motor rotation speed on PLC Logo! 8
11:48
Siemens Logo PLC analog input scaling and bar graph
7:31
Stable Automation
Рет қаралды 30 М.
Siemens LOGO! Unboxing and Setting up the PLC Basic Simulation
9:50
Bartosz Barlowski
Рет қаралды 273 М.
LOGO! programming without software | Siemens PLC programming
4:32
VIP ACCESS
00:47
Natan por Aí
Рет қаралды 30 МЛН