Siemens Logo PLC analog input scaling and bar graph

  Рет қаралды 27,927

Stable Automation

Stable Automation

Күн бұрын

In this video , we will scale on board AI for (1) 4-20 ma and then for (2) 0-10VDC input.
Also demonstrating bar graph functionality.
on board analogue input of logo plc supports 0-10V DC input only.
so for sensor with 4-20 ma output , we require to connect 500 ohm resistor.
#Siemens #LogoPLC #beginner #Logo
#AI #Analog #Input #Scale #Scaling
Check out other training videos:
Siemens Software License - Online software Delivery / OSD
• Siemens OSD - Online S...
S7 200 PLC data over OPC DA - PC Access SMART
• S7 200 PLC data over O...
Siemens LOGO PLC as Modbus TCP Client
• Siemens LOGO PLC as Mo...
Synchronize Siemens HMI time with S7 PLC using Area Pointer
• Synchronize Siemens HM...
S7 200 SMART Analog Input scaling (Applicable for SMAI04 / AI08 / AM03 / AM06)
• Synchronize Siemens HM...

Пікірлер: 17
@flex01223
@flex01223 4 жыл бұрын
Very nice video!
@StableAutomation
@StableAutomation 4 жыл бұрын
Thanks for the visit
@rabiburrahmanrabbi8307
@rabiburrahmanrabbi8307 3 жыл бұрын
Thank you
@ranjiththekkepara3871
@ranjiththekkepara3871 2 жыл бұрын
sensor input is 4-20ma, but logo input is only adopt 0-10v. so used 500ohm resistor to convert 4-20ma to 0-10vdc. but why did you configure the logo AI 4-20ma? should configure 0-10v right?
@StableAutomation
@StableAutomation 2 жыл бұрын
becase at 4ma you will get 2V. so 0-10V wont work.
@rajeshc6292
@rajeshc6292 4 ай бұрын
Sir, I am facing scaling issue 4to 20 mA into 0-100 %convertion in logo analog input module.I wanted to discuss.
@joeltshiela4605
@joeltshiela4605 Жыл бұрын
how to make a siemens logo program to drive the AM2 AQ analog outputs without using an input (no sensor). THANKS
@Kejtoo
@Kejtoo 2 жыл бұрын
is it possible to change pulse frequency by the analog input?
@rajeshc6292
@rajeshc6292 Жыл бұрын
Is it possible to connect the 3 wire transmitter in logo PLC ???
@StableAutomation
@StableAutomation Жыл бұрын
It's possible. But wiring depends on where you are connecting - either on on board PLC input (0-10V) or external module (4-20 ma)
@moindalvs
@moindalvs 3 жыл бұрын
PLEASE SHOW WIRING FOR ANALOG INPUT ASSIGNED? DID YOU USE I7 AND I8 AS 0V AND 10V OR M LOGO PLC POWER SUPPLY 0V ?
@StableAutomation
@StableAutomation 3 жыл бұрын
M as 0V and I7 , I8 as 10V +(input) Plz refer wiring diagram in manual.
@moindalvs
@moindalvs 3 жыл бұрын
@@StableAutomation thanks alot sir
@moindalvs
@moindalvs 3 жыл бұрын
Dear Sir, So can i consider I7 as AI1 and I8 as different Analog input ie AI2?
@StableAutomation
@StableAutomation 3 жыл бұрын
@@moindalvs Yes..
@ericdenja2122
@ericdenja2122 3 жыл бұрын
Asuuming I want to have I7 as 50% and I8 as 100% can I use one pressure transducer (4-20mA) for the same?
@ericdenja2122
@ericdenja2122 3 жыл бұрын
To give me two outputs?
Siemens LOGO PLC as Modbus Server
4:53
Stable Automation
Рет қаралды 48 М.
Doing This Instead Of Studying.. 😳
00:12
Jojo Sim
Рет қаралды 36 МЛН
Smart Sigma Kid #funny #sigma #comedy
00:40
CRAZY GREAPA
Рет қаралды 39 МЛН
Пройди игру и получи 5 чупа-чупсов (2024)
00:49
Екатерина Ковалева
Рет қаралды 3,7 МЛН
WORLD'S SHORTEST WOMAN
00:58
Stokes Twins
Рет қаралды 200 МЛН
PLC Analog Inputs and Signals
8:55
RealPars
Рет қаралды 704 М.
LOGO! Slow PWM | Siemens PLC Programming
12:14
Quick PLC
Рет қаралды 1 М.
Siemens LOGO PLC Software: Free Download and Installation Guide
9:20
Instrumentation Tools
Рет қаралды 2,3 М.
Analog input schematic for pt100/1000 in LOGO!
7:27
Rex Imperator
Рет қаралды 28 М.
LOGO! Analog basics 1 | Siemens PLC programming
12:21
Quick PLC
Рет қаралды 2,1 М.
SIEMENS LOGO  -ANALOG INPUT SCALING AND CONTROL 0-10V
7:01
Switch Gear & Automation
Рет қаралды 32 М.
PLC S7-1500 analog input scaling, configuration 4-20mA/0-20mA/0-10V full tutorial
48:15
General Technology Knowledge
Рет қаралды 8 М.
Analog Signals Programming using PLC + HMI Part 1
12:39
Nabil
Рет қаралды 84 М.
Doing This Instead Of Studying.. 😳
00:12
Jojo Sim
Рет қаралды 36 МЛН