LOTS OF CIRCUITS FOR A SIMPLE 4 BED REWIRE....WHY?????!!!

  Рет қаралды 4,940

Bristolsparky

Bristolsparky

Күн бұрын

Пікірлер: 55
@pjmorgan
@pjmorgan 2 ай бұрын
Impressed that you managed to get Darth Vader to do the filming for this 😂
@bristolsparky
@bristolsparky 2 ай бұрын
😂😂😂😂
@dannyrimmer2717
@dannyrimmer2717 2 ай бұрын
The letters OTT come to mind and there’s not many clients that will pay for all these safety extras 🙃
@bristolsparky
@bristolsparky 2 ай бұрын
@@dannyrimmer2717 how do you know what the budget was? It's all included and very competitive
@davecowan860
@davecowan860 Ай бұрын
I’d say that was good going time wise, top job 👌🏽👍🏼!
@bristolsparky
@bristolsparky Ай бұрын
Thanks, it was a mission!!
@peterigrenyi9176
@peterigrenyi9176 2 ай бұрын
How did the SPD end up at the furthest point from the incommer on that top row? Bit odd.
@bristolsparky
@bristolsparky 2 ай бұрын
Type 1,2,3 SPD made by surge devices, google it and look at the wiring diagram and location of terminals
@OCD_Sparkies
@OCD_Sparkies 2 ай бұрын
If I need to label sockets etc I use clear labels, they look a lot more subtle than white background labels. To the point you can label coloured accessories and as long as you get the label on straight it looks alright!
@bristolsparky
@bristolsparky 2 ай бұрын
Clear labels are perfect for decorative accessories 🫡
@nodwaa9227
@nodwaa9227 2 ай бұрын
the emergency light is a beauty. i shall be using that :D
@bristolsparky
@bristolsparky 2 ай бұрын
Thankyou🤙🏻
@bramcoteelectrical1088
@bramcoteelectrical1088 2 ай бұрын
I do that on fusebaords. Clients love it Good work mate and like your channel
@rofl4332
@rofl4332 2 ай бұрын
great work!
@bristolsparky
@bristolsparky 2 ай бұрын
Thank you! Cheers!
@hogg8888
@hogg8888 2 ай бұрын
Great work 🎉🎉🎉 i do the same with smokes in garages
@bristolsparky
@bristolsparky 2 ай бұрын
Thanks!
@hughblount1983
@hughblount1983 2 ай бұрын
I much prefer having separate lighting and socket trips for upstairs and downstairs so if there's a fault the customer still has some supply and I really like the idea of having an emergency light by the consumer unit saves worrying about looking fir a torch
@bristolsparky
@bristolsparky 2 ай бұрын
As standard 🫡🫡
@munemabdul1199
@munemabdul1199 2 ай бұрын
Can’t lie bro you’re a certy sparky 👌🔥
@bristolsparky
@bristolsparky 2 ай бұрын
Thanks!
@yammy613
@yammy613 2 ай бұрын
That job was a long way from home for you. Venturing over the border to Wales.
@bristolsparky
@bristolsparky 2 ай бұрын
It really was, it's probably the furthest I'd like to travel now
@calumclark1719
@calumclark1719 2 ай бұрын
Do you guys have the THTC tariff south too? it very common here in the north isles of Scotland , Wylex used to make a split board which had the spacing for the tariffs the new ones you have to make to fit, and the OLD MEMs used to have a double stacker specifically for it too but when Eaton bought them out it disappeared, Nothing wrong with the triple stacker looks nice, the EM light is great its standard aboard boats that is where i knicked the idea from 😂. and I can tell you in regard to the Storage heater if its pre 74 it will have asbestos but you can access the connections without going near it and then just hard wire the flex into the switched fuse
@bristolsparky
@bristolsparky 2 ай бұрын
The flex wouldn't reach hence it was kinda like 2 birds 1 stone. Relocate and not mess with them
@karlparhad7805
@karlparhad7805 2 ай бұрын
What does your max demand work out to ?
@bristolsparky
@bristolsparky 2 ай бұрын
Calculated around 90-something amps
@keiththesparky
@keiththesparky 2 ай бұрын
I seem to run into this problem quite often. By offering more selectivity in the form of dedicated circuits you can often end up around 200amp or more before diversity is applied which can still exceed the 100amp main fuse and equipment ratings after diversity is applied. Think they should be more allowances for such installations as if they are affordable it makes more sense to separate circuits more. Great Install by the way 👍🏼
@bristolsparky
@bristolsparky 2 ай бұрын
@ thanks
@dubmono
@dubmono 2 ай бұрын
Wouldve fitted the outside light on its own RCBO. Hate to trip the upstairs if theres a water leak outside
@bristolsparky
@bristolsparky 2 ай бұрын
That's also a great idea, I've done that before 👍🏻
@MegaMetinMetin
@MegaMetinMetin 2 ай бұрын
Is surge ok on the other side of the switch? So it’s last to feel the voltage spike after all the circuits
@bristolsparky
@bristolsparky 2 ай бұрын
Of course it is, some manufacturers have it before, some after🤷‍♂️
@MADSPARKS31
@MADSPARKS31 2 ай бұрын
SPD is recommended to be as close to the main switch.
@MADSPARKS31
@MADSPARKS31 2 ай бұрын
Either side is fine, cable lengths as short as possible.
@bristolsparky
@bristolsparky 2 ай бұрын
@@MADSPARKS31 correct
@dangallagher2306
@dangallagher2306 2 ай бұрын
How have you fixed the conduit back? No complaints i just dont see any saddles ?
@bristolsparky
@bristolsparky 2 ай бұрын
That's because I've used D-line saddles, discrete & compliant conduit fixings....Google them and come back to me👍🏻
@briangriffiths1285
@briangriffiths1285 2 ай бұрын
Where is the heat pump provision? Future proofing heating would surely be an ASHP?
@bristolsparky
@bristolsparky 2 ай бұрын
Because that's the direction the client wants to go in
@nightmagic3304
@nightmagic3304 2 ай бұрын
I'm not looking to pick fault but just curious, looks like a two phase and neutral supply so 400v potential between phases, do fusebox allow two phases in their domestic enclosures? Hager (not fusebox I know) technical told me no on a recent job where we had storage heaters on a separate phase so we had to use two separate single phase DB'S where one would have been neater like you've done here.
@bristolsparky
@bristolsparky 2 ай бұрын
It's not 2 phase
@nightmagic3304
@nightmagic3304 2 ай бұрын
@bristolsparky I stand corrected, apologies. Tidy work :)
@bearbin
@bearbin 2 ай бұрын
Looks a bit over the top, but that's what I would want it it was my house :)
@bristolsparky
@bristolsparky 2 ай бұрын
☺️☺️thankyou...I think
@richardcawrey
@richardcawrey 2 ай бұрын
Same
@bristolsparky
@bristolsparky 2 ай бұрын
Thanks!
@timballam3675
@timballam3675 2 ай бұрын
Jesus, with the price of electricity why not use a hetapump?
@bristolsparky
@bristolsparky 2 ай бұрын
Client's choice
@georgemcclelland5207
@georgemcclelland5207 2 ай бұрын
Are you willing to publicly give a ballpark figure for the invoice amount on this job? I know it can be a sensitive matter so no worries if not. Always interesting to see what people charge though
@bristolsparky
@bristolsparky 2 ай бұрын
Unfortunately not
@danvictor3934
@danvictor3934 Ай бұрын
Hi i still think this thermal de rating is a load of pants in the Regulations you will find nothing about it.
@bristolsparky
@bristolsparky Ай бұрын
All manufacturers instructions tell you about it
@danvictor3934
@danvictor3934 Ай бұрын
@bristolsparky Hi I can understand it with afdds that have computer chips in them but of all the Rcbo Consumer Unit i have ever installed I have never seen any instructions I use Fusebox Hager Lewden Crabtree Starbreaker Mk Honeywell mcg etc
@bristolsparky
@bristolsparky Ай бұрын
@ go and read the manufacturer's data sheets on all of those brands
ELECTRICIANS ARE MADE OF SUGAR!
14:20
Bristolsparky
Рет қаралды 2,4 М.
REWIRING A LARGE HOUSE - INCLUDING CAT6
15:15
Bristolsparky
Рет қаралды 5 М.
How to treat Acne💉
00:31
ISSEI / いっせい
Рет қаралды 108 МЛН
Сестра обхитрила!
00:17
Victoria Portfolio
Рет қаралды 958 М.
Quilt Challenge, No Skills, Just Luck#Funnyfamily #Partygames #Funny
00:32
Family Games Media
Рет қаралды 55 МЛН
It is cheaper to leave your  heating on 24/7, true or myth
11:30
Tomkat Gas Training
Рет қаралды 300 М.
Animals Ate My Customers Cables... And Now Nothing Works
17:32
SOTA Electrical
Рет қаралды 7 М.
The Big Retrofit - It's finished with Jonathan Evans
3:29
Skipton Building Society for Intermediaries
Рет қаралды 754
Neatest Job To Date - Bare Brick Rewire UK Electrics
22:20
N Bundy Electrical
Рет қаралды 24 М.
HOW TO REMOVE BATH FOR WALK IN SHOWER - Step By Step
26:19
plumberparts
Рет қаралды 489 М.
Ultimate Heat Pump Installation. Rip It Out & Start Again!
31:15
Skill Builder
Рет қаралды 142 М.
Customer Refusing to Pay… AGAIN! 😡
13:18
Artisan Electrics
Рет қаралды 183 М.
Island Power - Chasing Concrete & Parquet Flooring
15:08
N Bundy Electrical
Рет қаралды 15 М.
DIY DISASTER CONSUMER UNIT - Off-Grid Wiring Deep Dive | ØY47
15:18
Cory Mac - ØY Electrical
Рет қаралды 66 М.
HEATING NEVER INSTALLED CORRECTLY - Bart's MASSIVE Problem!
22:09
plumberparts
Рет қаралды 88 М.
How to treat Acne💉
00:31
ISSEI / いっせい
Рет қаралды 108 МЛН