Mitsubishi Mini Split Throwing Codes!!! How to Diagnose a Mini Split. EP66

  Рет қаралды 43,381

Nighthawk HVAC

Nighthawk HVAC

2 жыл бұрын

Mitsubishi Mini Split not cooling in the kitchen. The system was showing a abnormal voltage error. Here's how to diagnose the issues with this mini split. Ended up being a short in the main power board. Check it out!
Follow me on Facebook and Instagram
nighthawkhvac
nighthawk_hvac
Intro and Outro Music
"Alive" by CHOIX
#nighthawkhvac #hvac, #hvaclife, #airconditioning #maintenance, #heating, #cooling #refrigerator, #refrigeration #refrigerationcycle #airflow #refrigerant #techlife #installation, #hvachacks, #tools, #furnace, #tech, #electric, #residential, #commercial, #heat, #comfort, #ac, #hvacservice, #hvactools, #repair#toolreviews #fieldpiece #aircon #zoning #honeywell #zonedamper#packageunit #howto #VAV #exhaustfan #Ignitor #trane #TXV #expansionvalve #Intellipak #Trane #Self-contained #Boiler #Coolingtower #noisyinducer #noisyidm #failedIDM #condenserinattic #failedinducerdraftmotor #howtocleancoils #condensercoilcleaning #sparkignitor #nospark #minisplit #mitsubishi #ductless #powerboard #powerboardreplacement #short

Пікірлер: 53
@jamespatrick9449
@jamespatrick9449 2 жыл бұрын
Far from a horrible Tech. I really like your videos, I always learn something new. To the point and informative. Thanks for taking the time to make them.
@tyl8ter
@tyl8ter 2 жыл бұрын
Nighthawk...keep them comin...great vidz
@josephmoxley5792
@josephmoxley5792 2 жыл бұрын
Mini Splits on Commercial Roof tops usually have this issue. They aren't meant to be on top of the roof. Lighting strikes Electrical Surges doesn't take much to get the CPU fried. Need some type of Surge protection to slow the electrical issues. Put an AMP Fuse so It pops the fuse and the board.
@hvacmania8323
@hvacmania8323 Жыл бұрын
Shade
@KuntalGhosh
@KuntalGhosh Жыл бұрын
That is not a cpu. That is called ipm. Basically the huge chip that is screwed onto the heatsink. Contains a full bridge 3 phase igbt set and control circuitry with protections and other sensors. This is the part that makes the 3 phase ac at variable frequency to control compressor speed and cooling power. I have 5 panasonic inverter mini splits and they are working fine since 2017 , not a single issue on one of them. They run 12 hours a day in Indian summer heat. Today it was 44c and it has been above 40 for this whole month touching 45 sometimes. None of these inverters have issues with the heat. You just keep them in shade and oversize the units. I have 1200sq ft floor space and installed capacity of 7tons. It uses 2 3 tons of capacity when the set temperature is reached. This puts lot less strain on the inverter. And i will never go back to those non inverters.
@hkhsm359
@hkhsm359 2 жыл бұрын
Nice video. Thanks for sharing
@UltraElite-ju8bb
@UltraElite-ju8bb 2 ай бұрын
Tech support free resource
@djsm0609ify
@djsm0609ify 2 жыл бұрын
Great video, babe!
@calvinnewcastle5899
@calvinnewcastle5899 2 ай бұрын
Nice work brother
@frankcastillo9199
@frankcastillo9199 Ай бұрын
Great tips 👌
@winkhvac62
@winkhvac62 2 жыл бұрын
Good video
@hvacmania8323
@hvacmania8323 Жыл бұрын
Outstanding 🎉 videos thanks for posting. You think maybe some shade would prevent this issue?
@gpowerdragon9852
@gpowerdragon9852 Жыл бұрын
if the electronics break often it's usually indication of high voltage Spike like thunderstrike that has been close by before you need surge protector plug on it
@christianneal8204
@christianneal8204 Жыл бұрын
You might want to put a Koolguard 2 on that system. It's a voltage monitoring surge protector.
@SuperSincere1
@SuperSincere1 2 жыл бұрын
But why does the boards keep blowing?????
@Patriot20233
@Patriot20233 8 күн бұрын
Thanks
@chrislester3152
@chrislester3152 Жыл бұрын
So that might help in the future to make sure that none of these inverter mini splits are put on twin breaker because it will cause a compressor over current protection code and probably burn one up if not fixed after a while
@Yukonjackman1
@Yukonjackman1 Жыл бұрын
Mine was a poor connection in the electric part had no heat on its setting.
@TandNServices
@TandNServices Жыл бұрын
As soon as I saw the back of the board @ 5:11 I knew it was because of the thermal paste not being installed properly. I warn guys all the time about the importance of it.
@NighthawkHVAC
@NighthawkHVAC Жыл бұрын
100%. Agreed. Love your channel by the way!
@gowkarranpooran4771
@gowkarranpooran4771 5 ай бұрын
Thanks for sharing
@zabalaan
@zabalaan Ай бұрын
Solid red and yellow and 11 blinks on green. What does that mean? The manuals dont even mention green led on the outside unit
@mikemoore466
@mikemoore466 2 жыл бұрын
They make surge protectors for these units. I would definitely install one on this unit.
@NighthawkHVAC
@NighthawkHVAC 2 жыл бұрын
I agree. The client doesn’t what to pay for it though.
@mikemoore466
@mikemoore466 2 жыл бұрын
@@NighthawkHVAC well they can keep installing boards then. 👍
@zigavucic754
@zigavucic754 4 ай бұрын
I think you will be back for same problem,this is a compressor winding problem.
@westsidehvac1097
@westsidehvac1097 5 ай бұрын
compressor is bad is gonna keep popping pct board
@KuntalGhosh
@KuntalGhosh Жыл бұрын
Always keep air conditioners in under shed. Make tiny sheeds around them . Putting them under direct sunlight not only increase your electricity bill it also puts lot more strain on the inverter parts. These do not like to run hotter than 70c internally. You don't need too much paste . The thing that you need to do is to properly clean both the heatsink and the ipm chip with tissue and isopropyl to remove any oil residue and old crusty paste. Then install fresh thermal paste and spread it with the supplied spoon that comes with lots of pc thermal paste. And you can use pc thermal paste those are lot better than these thermal grease. They aren't much more expensive and you can get the 30gram tubes of noctua h1 or h2 and that would last you 60 installations.
@KevinfinityDrums
@KevinfinityDrums 6 ай бұрын
What? You should never restrict or stifle air flow around a unit.
@jhoney2346
@jhoney2346 Жыл бұрын
I’m dealing with this exact problem currently. Any more issues from this unit after this video?
@NighthawkHVAC
@NighthawkHVAC Жыл бұрын
It’s still going.
@chrislester3152
@chrislester3152 Жыл бұрын
I have cured protect compressor codes by changing them off Tandom breakers , they don’t like being on them ,
@haochen6247
@haochen6247 2 жыл бұрын
The suction pressure looks too high isn't? Is the system over charge which is causing the high compressor over current protection?
@NighthawkHVAC
@NighthawkHVAC 2 жыл бұрын
This system has a variable compressor and charge can’t be determined by pressures as they may look high or low. The only way to check the charge is to weigh the charge. This units charge was to factory specifications.
@haochen6247
@haochen6247 2 жыл бұрын
@@NighthawkHVAC I agree that inverter unit is best to weight in refrigerant. However, as alternative, you can also have all the indoor unit run at the max cooling mode, and charge it based on the gauge reading to around 125. There got to be reason for repeated blown circuit board. The mini split come with pre-charged refrigerant up to certain length and also have requirement for minimum total pipe length. For what I have seem with many Fujitsu and other brand that I have fixed, in cooling mode, when compressor is running, it never get this high suction pressure. while when the compressor is not running, it could get above 200 psi. I would suggest if all choice is out, check if the system is overcharged.
@Ricky32908
@Ricky32908 7 ай бұрын
That board should have insulation on whatever is on top of it. If it doesn’t and it’s bare metal it will short every time
@briandonovan7099
@briandonovan7099 Жыл бұрын
Sorry to sound like a newbie but how do you use that reset lever on the back 😂
@julieanehurley-hv4bv
@julieanehurley-hv4bv 2 ай бұрын
Good question...the exact box on the mini split I have has the fuses.
@theduffster2581
@theduffster2581 2 жыл бұрын
What about installing a phase monitor?
@NighthawkHVAC
@NighthawkHVAC 2 жыл бұрын
My thoughts exactly. Client didn’t want to pay for it though.
@theduffster2581
@theduffster2581 2 жыл бұрын
@@NighthawkHVAC I figured as much bud 👍🏻 benn through it many times but the callbacks become costly sometimes
@NighthawkHVAC
@NighthawkHVAC 2 жыл бұрын
I told him if it happens again it’s on him.
@garry9586
@garry9586 2 жыл бұрын
Where is the surge protector at?
@NighthawkHVAC
@NighthawkHVAC 2 жыл бұрын
Lol. Good luck getting a client to pay for that!
@pcar5
@pcar5 Жыл бұрын
You will be beck. Something is causing the failures. Always told my techs...troubleshoot the cause not the symptom.
@NighthawkHVAC
@NighthawkHVAC Жыл бұрын
Been over a year and still works. I think the previous tech didn’t tighten the screws tight enough to make good contact to the heat sink causing it to overheat.
@jhonnybenito7464
@jhonnybenito7464 Жыл бұрын
Maybe someone seated on top of it and create the short
@roundedges2
@roundedges2 Жыл бұрын
Ok but what causes 2 boards to burn?
@NighthawkHVAC
@NighthawkHVAC Жыл бұрын
First one was a surge. 2nd one the previous tech did not use thermal paste and did not secure the board to the heat sink properly.
@ezhilbenit630
@ezhilbenit630 2 жыл бұрын
comprser heter
@PabloRodriguez-ck7ph
@PabloRodriguez-ck7ph 2 жыл бұрын
Pues qué fácil es repararlo cambiando toda la tarjeta, sería mucho mejor tratar de reparar la tarjeta Eso sería algo mejor.
@trinito97
@trinito97 Жыл бұрын
Put a new one
@sparkyobrian6417
@sparkyobrian6417 9 ай бұрын
i have 4 large Mitsubishi units (5 years old) and they have been nothing but trouble , labor is very high , and the companies in my area have a hard time fixing them. ill never buy Mitsubishi high dollar junk again
How to Work on Mini Splits?
30:30
Taddy Digest
Рет қаралды 112 М.
MISS CIRCLE STUDENTS BULLY ME!
00:12
Andreas Eskander
Рет қаралды 10 МЛН
Happy 4th of July 😂
00:12
Alyssa's Ways
Рет қаралды 67 МЛН
50 YouTubers Fight For $1,000,000
41:27
MrBeast
Рет қаралды 192 МЛН
MINI SPLIT Parts Explained! Understand What They Do!
19:31
AC Service Tech LLC
Рет қаралды 623 М.
Technically Speaking EP1: Mitsubishi Electrical Troubleshooting
6:08
I HATE Mitsubishi MiniSplits
15:41
HVACR Survival
Рет қаралды 123 М.
#1 Reason Why DUCTLESS Units Fail | How I Fix It...
13:59
Quality HVACR
Рет қаралды 789 М.
10 Reasons Why A Mini Split Flare May Be Leaking Refrigerant!
18:15
AC Service Tech LLC
Рет қаралды 717 М.
Mini-split Heat Pump Not Cooling / How To Properly Flare Without Leaks
28:44
Mitsubishi Ductless Split Shut Off on OverCurrent Faults
24:25
The HVAC Hacker
Рет қаралды 43 М.
Amazing! Taiwanese Giant Watermelon Juice - Fruit Cutting Skills
0:47
Foodie Camp 푸디캠프
Рет қаралды 59 МЛН
Love conquers all rules?
0:26
Den Do It
Рет қаралды 11 МЛН
how do you wash carrots?
0:11
dednahype
Рет қаралды 2 МЛН
It’S So Fun To Wash My Son’S Hair! #funny #baby#cute  #funnybaby
0:14
Amazing Children Toys
Рет қаралды 11 МЛН
Waka Waka #10 🤣 #shorts #adanifamily
0:15
Adani Family
Рет қаралды 3,6 МЛН