NEC Motor Load Calculations Example

  Рет қаралды 68,327

Electrical 101

Electrical 101

Күн бұрын

Пікірлер: 78
@Sincoola27
@Sincoola27 Жыл бұрын
I took this guys full prep class a few years ago. Passed my masters exam on the first try thanks to it! great teacher
@soundman2604
@soundman2604 2 жыл бұрын
Very well laid ou,t with Code articles as references. Nice job!
@electrical1019
@electrical1019 Жыл бұрын
Thank you!
@jeremyjpegan
@jeremyjpegan Жыл бұрын
agreed! Thank you for the schooling. Do you do anything on motor controls?
@electrical1019
@electrical1019 Жыл бұрын
Thank you, it's what our goal is! We're hoping to have some material on controls as well as basic branch wiring up once the fall semester of school is out!
@stevenwarren206
@stevenwarren206 Жыл бұрын
The overloads are calculated at nameplate FLA, right? Everything else is calculated from the FLC from from 430 tables , am I right about this?
@electrical1019
@electrical1019 Жыл бұрын
For field calculations that is correct. These lectures are intended for students taking a licensing exam in Kentucky, in which on the exam typically the FLC is used to calculate overload protection.
@santiagocid5908
@santiagocid5908 Жыл бұрын
You are right 👍
@reynaldomartinez4918
@reynaldomartinez4918 6 ай бұрын
I find that pretty odd since the motor nameplate FLA is tipically different than the FLC. If the FLC is much higher than the FLA by many amps, then the overload will be set much higher than the FLA.. interesting
@wesleythorpe7855
@wesleythorpe7855 2 ай бұрын
@@electrical1019wouldn’t you use the FLA from the name plate for overload for exam purposes as well? It calls out name plate in the code reference.
@TheMadhatter0710
@TheMadhatter0710 Жыл бұрын
Information is thrown out very thoroughly. Thumbs up!
@JesusCruz-wt2zp
@JesusCruz-wt2zp Жыл бұрын
Your videos are great. Please do more ..
@electrical1019
@electrical1019 Жыл бұрын
Thank you! We are always looking to upload new content!
@daltondelaney9534
@daltondelaney9534 Жыл бұрын
Why do you always use 75C degrees column for motor feeder wire size? (8:30 in video)
@JV503
@JV503 9 ай бұрын
110.14 NEC
@EbagOmocaigid
@EbagOmocaigid Жыл бұрын
wouldn't the feeder size in step 5 be calculated as THWN-2 like the motor wires? And thus be a number 6 wire rated for 75 AMPS? Great video though, thanks
@controlsgirl
@controlsgirl Жыл бұрын
Great example!! Way to walk through it!
@electrical1019
@electrical1019 Жыл бұрын
Thank you!
@kylecropanese8744
@kylecropanese8744 10 ай бұрын
Thank you so much about to go for my exam shitting bricks this helps so much
@marmars1081
@marmars1081 8 ай бұрын
Did you pass?
@Luminous116
@Luminous116 5 ай бұрын
I've noticed you use 75° column for the branch ckt conductor size. However I was told to use 60°C column for circuits rated 100 amperes or less (per NEC 110.14-C) regardless of conductor insulation rating. Was there an exception that I missed?
@Makitafan
@Makitafan 5 ай бұрын
I'm not sitting in front of my code book but he said all motors are size it 75 degree column. Finger your way through 430 and see if you can find something backing up his statement.
@mywifesboyfriendisfire
@mywifesboyfriendisfire 2 ай бұрын
He used 90°C for the branch circuits since we're told we're running THWN-2 wire to the motors. The *feeders* to the panel main breaker are calculated using the 75°C column for motors.
@BobbaFett312
@BobbaFett312 Жыл бұрын
i have same question as others on using 75C when ampacity column. 75C can be used only when terminations are also 75C. why is 75C used here?
@rigobertoruiz6136
@rigobertoruiz6136 Ай бұрын
Amazing video thanks!
@MensLifestyle1985
@MensLifestyle1985 10 ай бұрын
For Step #6, why wouldn't you add 150A to 20A for the remaining motor? Why did you only add the FLC and not the Branch Circuit protection from step #4 like you did for the larger motor?
@juliorojas7276
@juliorojas7276 5 ай бұрын
Service factor is 1.4 and the code is 1.5 or grater to be × 125%. If is not 1.5 por greater it should be × 1.15.
@MrTomObama
@MrTomObama Ай бұрын
On step #3 if its THWN-2 at 9.5 amps wouldn't the answer be 18 for copper? Or is it 14 because of the temp rating? Confused. I understand how you got the answer for the 65 amps just not the 9.5 amps.
@narendergodara1992
@narendergodara1992 Жыл бұрын
EXCELLENT VEDIO👌👌🙏🙏
@mcarroll598
@mcarroll598 Жыл бұрын
When you size breakers for motors, wouldn’t you round down to the next standard circuit breaker size?
@electrical1019
@electrical1019 Жыл бұрын
430.52 exception number 1 allows us to go up to the next standard size for overprotective devices serving branch circuits for motors; 430.62 does not have this exception, so we have to go down to the next standard size for overcurrent devices serving feeder circuits for motors.
@mcarroll598
@mcarroll598 Жыл бұрын
@@electrical1019 thank you so much
@mr.write1433
@mr.write1433 Жыл бұрын
what nec edition is this ?
@oscar27ization
@oscar27ization Жыл бұрын
I think you made a small mistake by multiplying your overload protection device with your FULL LOAD CURRENT instead of your FULL LOAD AMP??
@sekwanmerritt6235
@sekwanmerritt6235 Жыл бұрын
Yes for step 3 Sizing the Branch Circuit conductor he multiplied a %125 by the value of Overload Protection instead of the instead of the Full Load Current.
@paulpbe1
@paulpbe1 2 ай бұрын
Overload size should be sized by the amperage on the motor name plate not the the FLC table
@wadetaney8642
@wadetaney8642 Жыл бұрын
Well put!! Great teacher.
@mcarroll598
@mcarroll598 Жыл бұрын
Wouldn’t you size your OVERLOADS to your FLA on the motor? Not your FLC from the code book?
@electrical1019
@electrical1019 Жыл бұрын
In the field/"real-world", yes, you would. This video assumes you do not have that information, and is more for those taking a licensing exam rather than practical application.
@mcarroll598
@mcarroll598 Жыл бұрын
@@electrical1019 thanks. One other question. I understand how to size for fuses and breakers but what’s confusing is when you round up or round down. Any explanation would be great. Thank you.
@electrical1019
@electrical1019 Жыл бұрын
@@mcarroll598 I believe we just responded to that in another comment you left!
@mcarroll598
@mcarroll598 Жыл бұрын
@@electrical1019 thank you
@hebrewlessons2348
@hebrewlessons2348 2 ай бұрын
great great great instruction!
@thanmaysudev
@thanmaysudev 6 ай бұрын
Could you please tell me why the 40hp motor doesn't have any starter
@Tito-nw6te
@Tito-nw6te Жыл бұрын
How can i get these work sheets ??
@Mike-ec4zp
@Mike-ec4zp Жыл бұрын
Where does table 430.22(E) fall in these steps? If asked for any of these rating percentages? Answer be helpful
@electrical1019
@electrical1019 Жыл бұрын
You would only use table 430.22(E) if you are sizing conductors for a motor that is not continuous duty (step 4). The NEC tells us that anytime we use a motor we have to consider it to be for continuous duty unless we meet certain conditions, so we generally speaking don't bring this table up. If you are using this information for real work application, and you consistently work with intermittent use motors like on an elevator, it is very good to know though!
@Primez8902
@Primez8902 Жыл бұрын
You dont need the FLA to do these calculations?
@Primez8902
@Primez8902 Жыл бұрын
Im using the 2014 code book
@electrical1019
@electrical1019 Жыл бұрын
Actually, FLA comes from the motor nameplate. FLC comes from tables 430.248 and 430.250. 430.6(A)(1) requires us to use the FLC from the tables for all calculation other than overload protection rather than the FLA (in this videos we assume that the FLA is not provided and just use the FLC for over overload protection). Hope that helps!
@kythuatcongnghiep8559
@kythuatcongnghiep8559 Жыл бұрын
thank you, very helpfully for me
@scottdonahue6417
@scottdonahue6417 3 ай бұрын
There is a standard 70 amp breaker by the way
@aaronwidder9624
@aaronwidder9624 Жыл бұрын
I thought if you rated your ocp at 250% it would be the next "lowest" size breaker or if it's sized at 125% it would be the next "highest" size breaker? Great Info sir! 👍
@aaronwidder9624
@aaronwidder9624 Жыл бұрын
@@mitcheljames7053 ooo ok, I read over that and understand now. Thanks for the clarification sir! 🫡
@theonetrueanthonylong1843
@theonetrueanthonylong1843 Жыл бұрын
@@mitcheljames7053 Yes, thank you!
@electrical1019
@electrical1019 Жыл бұрын
It looks like we got beat to the explanation, but yes, Mitchel provided a perfect breakdown of why we are able to go up to the next size breaker!
@CallmeDr773
@CallmeDr773 7 ай бұрын
Super helpful! Thank you
@purpleraptor1183
@purpleraptor1183 Жыл бұрын
I am doing 50 HP [FLC= 65A, 65A*125% = 81.25A got Conductor size AWG 4] and 250 HP [FLC= 302A, 302A*125% = 377.5A got Conductor size AWG 500MCM table 310.16(75 ,Copper)]. For 50 HP - I am doing 65 A * 250% = 162.5 Amp breaker. But from ugly book, for 50 HP size breaker-150A. Same for 250 HP - 302 * 250% = 755 A. Should I not go up and standard size of breaker?
@johnnyroloff8118
@johnnyroloff8118 9 ай бұрын
I think it is because the 250% from Table 430.52(C)(1) is a maximum rating, so the ugly book selects the closest standard size under 250% of the FLC.
@cevtongooden1836
@cevtongooden1836 Жыл бұрын
Thanks so much send more
@paasdfasd
@paasdfasd 3 ай бұрын
what happens if the motor is 400V AC?
@danielgriffin2674
@danielgriffin2674 Жыл бұрын
Some guys are just cut out to be teachers, nice job.
@Kowloonhongkong
@Kowloonhongkong 11 ай бұрын
why dont protect the wire?
@stuffthings9618
@stuffthings9618 Жыл бұрын
Arent you supposed to calculate the Overload from nameplate amps????
@Resistculturaldecline
@Resistculturaldecline Жыл бұрын
If the nameplate info is provided, you are to use nameplate for separate overload devices. If nameplate is not given, you're to use table FLC. At least, that how I think I understand it.
@TheKaracay
@TheKaracay 2 ай бұрын
he messed up on overload for big motor other than that I like the way he teaches
@natename797
@natename797 Жыл бұрын
Why is the first wire size not # 18?
@TheMoody2006
@TheMoody2006 Жыл бұрын
I'm looking for the same answer. I THINK he made a mistake with the chart (read the AMPS as the wire size) but was technically correct because 14 AWG is the smallest size permissible for a branch circuit.
@mr.write1433
@mr.write1433 4 ай бұрын
FLA not equal to flc? Why put FLC?
@kentbinaoro9164
@kentbinaoro9164 Жыл бұрын
I am now very confused, but anyways I only know things for residential wiring only, I thought 14awg must use 15a breaker to protect the wire
@Makitafan
@Makitafan 5 ай бұрын
The "test" gave a wire insulation choice that was in the 90 degree C column. So that's why it was chosen.
@alexramos9459
@alexramos9459 10 ай бұрын
So I just did this by calculator and field knowledge on wires and experience wiring things actual amperage it’s 7.7 not 6 learning ohms law helps a lot and makes easy to calculate by using the calculator
@pingpongpaddlehead
@pingpongpaddlehead 8 ай бұрын
fascinating
@jass1989
@jass1989 11 ай бұрын
Last i checked. 1.4 was less than 1.5 Mis heard him
@jacobhess3n327
@jacobhess3n327 5 ай бұрын
Yeah I’m confused too. There are inaccuracies throughout the entire video
@jass1989
@jass1989 5 ай бұрын
​@jacobhess3n327 I re-watched it. Sf of the motor is 1.4. Code says 1.15 or greater. 1.4 is .35 great then 1.15.
@orangaharris640
@orangaharris640 Жыл бұрын
Beginer here.. dont understand most of it 😅
@mywifesboyfriendisfire
@mywifesboyfriendisfire Ай бұрын
Watch it over and over
Motor Load Calculations
19:33
Electrical 101
Рет қаралды 29 М.
NEC Dwelling Service Calculation Example
19:28
Electrical 101
Рет қаралды 98 М.
Леон киллер и Оля Полякова 😹
00:42
Канал Смеха
Рет қаралды 4,1 МЛН
УДИВИЛ ВСЕХ СВОИМ УХОДОМ!😳 #shorts
00:49
Creative Justice at the Checkout: Bananas and Eggs Showdown #shorts
00:18
Fabiosa Best Lifehacks
Рет қаралды 35 МЛН
The Best Band 😅 #toshleh #viralshort
00:11
Toshleh
Рет қаралды 19 МЛН
5 Formulas Electricians Should Have Memorized!
17:00
Electrician U
Рет қаралды 1 МЛН
Motors: Conductor sizing and overcurrent protection
58:34
Ryan Jackson
Рет қаралды 9 М.
How to Size a Motor using WOLF method
14:57
Craig Michaud- Electrical Instructor
Рет қаралды 53 М.
What's the Difference Between All These Wire Types?!?!
14:48
Electrician U
Рет қаралды 283 М.
Motor Branch Circuit Conductor Sizing [430.22(A)] (14min:30sec)
14:30
Single Phase Motors- Simple Branch Circuit Sizing
9:11
Master The NEC
Рет қаралды 6 М.
How to Calculate Motor Full Load Current
10:23
Electrical 101
Рет қаралды 8 М.
Calculating Motor Overloads
7:55
schulerruler
Рет қаралды 69 М.
Residential Load Calculations Pt 1
1:33:33
Jarod V Electric
Рет қаралды 5 М.
Everything you need to know to solve Voltage Drop Calculations!!
14:57
Craig Michaud- Electrical Instructor
Рет қаралды 238 М.
Леон киллер и Оля Полякова 😹
00:42
Канал Смеха
Рет қаралды 4,1 МЛН