Pulling in 34.5kv cu cable in new vaults sometimes a little bit difficult because most of the pulling anchors are not always in the best location to pull in multiple cables and hoping there is anchors in and around the vault.
Пікірлер: 1
@shawncampbell179211 ай бұрын
Looks like a nice setup, sometimes you can put in a big radius roller in the vault and pull the cable thru the roller but when you are dealing with 35kV cable in such large sizes you need too big of a radius roller and you can blow out the sidewall from too much tension so pulling it straight to the vault wall /block and then pulling a bit more slack at the end works well like this. What kinds of terminations are you using with these, t-bodies? Looks like a DWP setup, I think they use T-bodies/vault stretchers for 35kV taps and straight splices for straight through cabling. Richards makes a nice premolded 35kV Y joint which is nice for taps, saves some space over t-bodies.