Is the backflow preventer typically located between 2 control valves on fire suspression systems?
@rodneykough601 Жыл бұрын
The control valves are actually part of the listed device
@fitter54266 жыл бұрын
No back pressure???? No testing if the #2 shut off is holding????
@scottradcliffe43847 жыл бұрын
Wow...just wow. Check out USC 10th edition and do it correctly.
@jamesholeva44966 жыл бұрын
The differential pressure across the check valve can be accomplished correctly by connecting the high pressure hose to test cock number 2 and the low pressure hose to test cock number 3. This is a recognized and accepted method of measuring differential pressure. Read the manual!
@fitter54235 жыл бұрын
Union guys don’t use the USC 10th edition buddy. We’re trained on the ASSE method which is what he did. It’s an acceptable way to test the differential pressures.
@tomcat66419 жыл бұрын
that why sixplex grinnell are losing their contracts for ispections and services.They charge too much for doing things the wrong way.
@macsrule948 жыл бұрын
They have been known to fail back flows in Charlotte NC area and they don't offer repairs, only replacement. They like to do it on the smaller devices (Irrigation, Domestic, bypass devices). One customer we went to and tested the device after Simplex and it passed with no issues, they had forgotten to close the #2 on an RPZ and there was watering flowing thru the device so it caused the Relief not to dump. Another one had the little bypass on a RPDA fail and they told them they had to replace the entire 8" device (think big $$$ for them), there was nothing wrong with the large 8" one, just had to replace the little 3/4" bypass device.
@jamesholeva44966 жыл бұрын
They measured the differential pressure across the check valves correctly.
@fitter54235 жыл бұрын
First of all do some research, look at the cost to replace the check in backflows 1” and smaller. For the cost of material and labor to rebuild and retest is a few dollars less than to replace the whole device. It’s common sense.
@EnforcementDronEd20911 жыл бұрын
This tech needs to go back to school! On DCDA USE ONE HOSE ONLY READ YOUR MANUEL.. ANOTHER JOKE VIDEO!
@jamesholeva44966 жыл бұрын
The manuals AWWA M14 and ASSE both discuss how to measure the differential pressure across the check valve by measuring the water pressure on each side of the check valve. Acceptable procedure NO JOKE --- Read manuals.